Honeywell MICRONIK 200 R7426A Installation & Start-Up Instructions Download Page 11

 

R7426A,B,C  TEMPERATURE CONTROLLER WITH AND WITHOUT REAL TIME CLOCK

 

 11 

EN1B-0203GE51 

R0507C 

Y (%)

100

T ( )

°

C

SOFFS

SOFFS

CTRPH CTRPC

Xph

Xpc

OCCUPIED

UNOCCUPIED

 

Fig. 5. Night cycle NightLow and NightHigh 

 
The night cycle program automatically cycles between the 
user selected upper and lower limits and turns on full heating 
or cooling with forced return air recirculation or full energy 
recovery whenever the limits are reached. The switching 
hysteresis is fixed to 1 K. 
This function can be disabled for heating and/or cooling by 
setting 

NightLow

 and/or 

NightHigh

 to OFF. 

 

Calibration of Temperature Sensors 

T1CAL, T2CAL, or T3CAL (P.17...P.19) 

The controllers include a calibration setting and are factory 
calibrated. In case of an offset as a result of long wiring 
lengths the temperature sensor inputs (T1, T2, and T3) can 
be adjusted separately by the control parameters 

T1CAL

T2CAL

 and 

T3CAL

 

Return Air Offset RetOffs (P.20) 

The control parameter 

RetOffs

 is available only on R7426B,C 

controllers and is used to activate economizer mode (

RetOffs

 

 OFF) for mixed air damper (

Y1CTRF

 = 0) or energy 

recovery system control (

Y1CTRF

 = 1). 

If the main temperature sensor (T1) is installed in the exhaust 
air, the control parameter 

RetOffs

 should be set to 0. In 

applications with the main sensor installed in the room and 
with a constant offset between room and exhaust air 
conditions, this offset value can be adjusted within 0...5 K by 
the control parameter

 RetOffs.

 This will be added to the 

actual measured room temperature value to simulate exhaust 
air conditions. 
The economizer mode is disabled if the value of the control 
parameter 

RetOffs

 is programmed to OFF or if no outdoor air 

temperature sensor is connected. 

 

Minimum Position MINPOS (P.14) 

The control parameter adjustment 

MINPOS

 is available on 

R7426B,C controllers only and determines the minimum open 
position to which an outdoor air damper actuator can be 
driven from the controller. In mixed air damper applications it 
maintains the minimum outdoor air damper setting, even 
though the temperature input condition calls for a fully closed 
position. 

If the controller is in OFF mode, the time schedule program 
overrides the minimum position by the ON/OFF input for 
plant/system shut off and the damper is driven into the fully 
closed position at OFF condition together with the heating and 
cooling valve actuators. 
 

Runtimex, x = Y1, Y2, or Y3 (P.21...P.23) 

The control parameters 

Runtimex

 (x = Y1 for R7426A;  

x = Y1, Y2 or Y3 for R7426B) are available only on  
R7426A, B controllers. 
The controller converts the deviation signal to a proportional 
output pulse which drives the actuators depending on the 

Runtimex

 parameter value. 

An automatic synchronization function ensures correct 
positioning of the actuators. The run time for synchronization 
is derived by control parameter 

Runtimex 

multiplied by 1.25. 

By selection of the output to pwm mode, the pulse-width 
modulated output is suitable for driving electric heat current 
valves and is controlled from the heating signal. The total 
cycle time is set by the control parameter 

Runtimex

 

OPERATING OVERVIEW 

Display and Operation Elements 

The MicroniK 200 user interface is described in Fig. 6. 

NOTE:

 Pushing 

the 

+

 or 

-

 button increments/decrements 

values or scrolls through the parameter list: 

  pushing one time: single step 

  pushing without release: automatically inc./dec. or scroll 

  after 3 sec pushing without release: fast automatically 

increment/decrement or scroll 

 

°C

%

Date Off

rh

MoTuWeTh Fr SaSu H1 H2 H3

min sec K

DISPLAY

PUSH BUTTONS

FREEZE PROTECTION

TIME*

OFF

NIGHT*

STANDBY

CONTROLLER MODE

COMFORT

ENGINEERING UNITS

LOW BATTERY*

SELECTION OR ESCAPE

*ON CONTROLLERS WITH REAL-TIME CLOCKS, ONLY.

ADJUSTMENT OR SELECTION

PARAMETER / VALUE

CONFIRMATION

VALUE

HOLIDAY SCHEDULE TYPES*

WEEKDAYS / GROUPS*

 

Fig. 6. User interface 

 

Summary of Contents for MICRONIK 200 R7426A

Page 1: ...installation information and mounting location Verify the controllers will be adequately separated from the main power supply relays or other equip ment which can possibly generate electromagnetic interference Verify that the ambient temperature and the humidity at the controllers will not exceed 0 50 C 32 122 F and 5 to 95 rh Use shielded wiring in areas with high EMI All wiring should be separat...

Page 2: ...by this controller W303 open T3 supplied from another controller 1 Default jumper position closed Cut open jumper W303 only if the T3 input is fed from another controller parallel connection max six devices This disconnects the T3 input from the internal power supply Wiring should be done only according to the actual job wiring diagrams or wiring diagrams shown in the mounting instruction sheet EN...

Page 3: ...CPA 5K internal 1 953 1053Ω CPA 5K T7412B1016 Pt 1000 2 100kΩ 0Ω CPA 5K T7412B1057 T7412C1030 Pt 1000 T7412B1008 T7412C1006 NTC 20kΩ 43193982 001 3 10 20kΩ SPA 15 30 C T7412B1024 BALCO 500 T7412B1040 Pt 1000 4 0 10kΩ CPA 5K HCW 23 setpt wheel printed with 5 K 5 0 100kΩ SPA 15 30 C 43193982 001 6 0 100kΩ SPA 0 50 C or 0 130 C 43193982 001 C 06 YRange Selects the output control range for all outputs...

Page 4: ... Adjusts the month for summer winter time change 10 x x x Min Max 0 disables summer winter time change 12 Oct C 18 PSTG_H 2 3 Determines the prestart gradient to reach the comfort setpoint for heating 0 K min x x x Min Max 0 disabled 2 C 19 PSTG_C 2 3 Determines the prestart gradient to reach the comfort setpoint for cooling 0 K min x x x Min Max 0 disabled 2 C 20 tvd2 Determines the damper presta...

Page 5: ... P 13 tr2 1 Reset time cascade control loop OFF 20 sec 20 min OFF 10 0 5 sec min x x x P 14 MINPOS Minimal pos for air damper actuators 0 50 20 1 x x P 15 Ystart Start point for mid range shift of output Y1 20 20 0 0 5 K x x x P 16 SOFFS Offset of main setpoint in Standby mode 0 10 2 0 1 K x x x P 17 T1Cal Calibration of temperature sensor T1 20 20 0 0 1 K x x x P 18 T2Cal Calibration of temperatu...

Page 6: ...guration parameter Ctrltyp value from Hi to Lo control range or vice versa causes the controller to change all parameter values to default depending on the selected Ctrltyp value For a direct parameter reset by the user refer to chapter How to reset Parameter Values to Default Values on page 12 Control Point Setpoint Adjustment CPATYP C 05 The control point or setpoint can be adjusted via the inte...

Page 7: ...T1 and T2 input internally and the sensor has to be connected only to the T1 input By using a limit temperate sensor T2 the parameter T2ext has to be set to 0 default Limit Type LimTyp C 13 The configuration parameter LimTyp allows the selection of high or low limit control High limit control is performed if configuration parameter LimTyp 1 low limit control is performed if configuration parameter...

Page 8: ...tion and control parameters time schedules input and output values of the connected controllers and easy setting of these via the bus by mouse click or keyboard Default Programming DefProg C 23 Setting the control parameter DefProg to 1 resets all control and configuration parameters to defaults see Table 4 and Table 5 Default programming is indicated by a display of def After default programming ...

Page 9: ...oling valve Setting Guidelines for Proportional Band of P and P I Control To estimate the proportional band throttling range Xp for stable control under all different load conditions the control or correcting range Xh of the heating or cooling coil must be known This is the maximum air temperature increase pro duced by the heating coil or decrease of a cooling coil if the control valve is fully op...

Page 10: ...Summer Winter Compensation Authority Su Wi P 04 P 05 These authority settings determine the reset effect OATComp the compensation sensor T3 has on the main setpoint W1 in percentages Outside temperature reset in summer and winter time are commonly used applications To calculate winter and summer authority the throttling range must be considered in proportional only control according to Table 12 Ta...

Page 11: ...controllers only and determines the minimum open position to which an outdoor air damper actuator can be driven from the controller In mixed air damper applications it maintains the minimum outdoor air damper setting even though the temperature input condition calls for a fully closed position If the controller is in OFF mode the time schedule program overrides the minimum position by the ON OFF i...

Page 12: ... controller returns to selection mode by pushing the SET or SEL button Pushing the SEL button leads back to standard display mode Pushing the SET and SEL button simultaneously for approx 1 sec causes the controller to leave the standard display mode and to enter the output data selection mode Fig 11 Pushing the SET button causes the controller to accept the selected output data no and to enter the...

Page 13: ...TIME CLOCK ONLY R7426B C ONLY R7426B C ONLY DATE COMPENSATION TEMPERATURE T3 SUBMASTER LIMIT SETPOINT CTRP2 MAIN TEMPERATURE T1 HUMIDITY DEVIATION XWrh MAIN SETPOINT CTRP1 OUTPUT Y1 OUTPUT Y2 OUTPUT Y3 LIMITATION CASCADE TEMPERATURE T2 A A B A B OUTPUT TYPE FLOATING 0 10VDC 2 10VDC 0 100 0 100 0 120 0 12V DIR 20 100 12 0V REV 25 125 0 12V 0 100 0 100 CONTROL RANGE OUTPUT RANGE THE OUTPUT DATAS Y1 ...

Page 14: ...f the selected parameter Ranges are shown in Table 4 and Table 5 An adjustment example is shown in Fig 18 Pushing the SEL button retains the old parameter value Pushing the SET button accepts the parameter value and returns to parameter configuration selection mode Resetting Param Values to Default Values Pushing simultaneously the and button during the power up or setting the control parameter De...

Page 15: ...e SEL button leads back to standard display mode R7426B AND R7426C ONLY WITHOUT CONTROL LOOP IS ACTIVE WITH MANUAL OVERRIDE IS ACTIVE Fig 11 Output Selection Mode AND TO ADJUST OUTPUT VALUE OUTPUT VALUE ADJUSTMENT OUTPUT VALUE ADJUSTMENT AUTOMATIC DISPLAY FOR APPROX 1 SEC OUTPUT SELECTION OUTPUT SELECTION OUTPUT SELECTION RELEASE OF MANUAL OVERRIDE NO MANUAL OVERRIDE MANUAL OVERRIDE OR Fig 12 Outp...

Page 16: ...ts of the used holiday types H1 H2 or H3 must be programmed in the standard schedule Table 15 shows a programmed example of the holiday schedule 2 7 till 28 7 holiday type H1 and 1 5 holiday type H3 The H1 and H2 holidays will not be influenced if the user changes the actual date If power supply is interrupted for more than one day all H1 and H2 holidays within the date of power supply error and t...

Page 17: ...like a controller without real time clock If the occupancy input is inactive the controller will be assumed as occupied Date Date Date TO ADJUST YEAR OR TO ADJUST MONTH OR TO ADJUST DAY OR TO ADJUST MINUTES OR TO ADJUST HOURS OR TIME ADJUSTMENT DATE ADJUSTMENT Fig 14 Date and time adjustment mode Programming Standard Schedule with RTC only The standard schedule programming is used to program up to...

Page 18: ...e Th Sa Fig 16 Holiday schedule programming Interpreting Error Messages Different analog input errors can be identified by the controller Error handling The defective analog input T1 T2 T3 or Xwrh will be displayed in the standard display mode see Fig 17 after the corresponding value is selected NOTE For the external CPA SPA potentiometer input no error message is indicated if the potentiometer or...

Page 19: ...y Jan Feb March April May June July August Sept Oct Nov Dec 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 1 30 31 1 If the 29th of February is programmed to be a H1 or H2 holiday and the current year is not a leap year this holiday will be deleted on March 1 Table 16 Annual schedule ...

Page 20: ...l GmbH Böblinger Straße 17 D 71101 Schönaich Phone 49 7031 63701 Fax 49 7031 637493 http europe hbc honeywell com Subject to change without notice Printed in Germany Manufacturing location certified to EN1B 0203GE51 R0507C point 1 point 2 point 3 point 4 point 5 point 6 day 1 time SMode 2 time SMode 2 time SMode 2 time SMode 2 time SMode 2 time SMode 2 Mo Tu We Th Fr Sa Su H1 H2 H3 1 Weekday or ho...

Reviews: