background image

VALUP

AK-II · Edition 11.22

EN-4

Please observe the following to ensure that no damage occurs:

 

– Before initiating the following start-up and adjustment proce-

dure, it is important that a check be made to verify that all of 
the equipment associated with and necessary to the safe 
operating of the VALUPAK-II burner system has been installed 
and piped in accordance with the general installation instruc-
tions.

 

– If the burner system is part of an oven or other heating unit 

which has been purchased as a complete prepiped and 
pre-wired package, it may be assumed that these instructions 
have already been carried out by the individual or company 
responsible for the overall installation.

 

Initial adjustment and light-off should be undertaken only by trained 
and experienced personnel familiar with combustion systems, 
with control/safety circuitry and with knowledge of the overall 
installation.

7.1 to start-up a VALUPAK-II burner for the first time

 1 

Close main gas cock.

 2 

Check tightness of gas piping.

 3 

Connect U-tube manometer to burner test connection on the 
burner gas nozzle inlet.

 4 

Note burner type and required gas pressure, see  page 5 (10 
Technical data).

 5 

Establish correct blower direction of rotation of all fans. See arrow 
on blower housings.

 6 

Disconnect automatic control motor wiring to avoid unexpected 
motor travel.

 7 

Check that gas control valve is at low fire position (as supplied): 
For size 150, 300, 600 and 900 control motor rotation is counter 
clockwise when looking towards controls linkage going from low 
to high fire. For the size 60 when looking to the linkage the air 
butterfly crank rotation is counterclockwise. Since the control 
motor is located at the opposite side of the linkage its rotation is 
clockwise from low to high fire.

 

When operating the burner with LPG instead of natural gas, the 
linkage connection on the air valve crank needs to be changed.

 8 

In order to do this, unscrew the nut (M6) at the back of the crank 
and relocate the linkage from the hole marked “C1–NG” to the 
hole “C3–LPG” by slightly rotating the crank and linkage.

 9 

Screw the nut back in place. No further modification on the burn-
er needs to be done.

C

Detail C

C

Detail C

 10 

Bleed air from the fuel supply line.

 11 

Remove the cover from the gas pressure regulator and establish 
that regulator is at low end of control range.

 12 

Check the adjustments of the flame rod, spark ignitor and/or 
pilot, see  page 3 (4.6.2 Spark ignitor arrangement).

 13 

Start all machine air blowers.

 14 

Start burner with its start-stop switch. Motor of combustion air 
fan will be started shortly after, by means of the burner flame 
safeguard programming relay.

 15 

Purge the combustion chamber, purging any explosive vapors 
that may have accumulated prior to the start.

 

The length of purge time required will usually be specified by 
insurance or approval agency having jurisdiction and depends on 
the total amount of fresh air and the volume of combustion space.

 

A 5-fold refresh rate should be minimum. At the end of the purge 
time of the burner flame safeguard programming relay ignition is 
energized and the main gas valve will be energized shortly after.

 

Because main gas cock is closed the programmer will lock out 
requiring manual reset. Operation of programmer is correct.

 16 

Check setting of low and high gas pressure switches and com-
bustion air pressure switch.

 17 

Check burner control valve at LO position.

 18 

Slowly open main gas cock.

 19 

Reset burner relay and start burner.

 

After the burner flame safeguard programmer relay prepurge time 
ignition is energized and main gas valve opened. Flame should 
be established within safety time of programmer.

 

If again flame failure, air could still be in gas supply line just before 
burner.

 20 

Reset programmer and restart until low fire flame is established.

 21 

Check gas supply pressure with information on  page 5 (10 
Technical data) and correct with adjusting screw of gas pressure 
regulator.

 22 

In the case of LPG firing, multiply the referenced natural gas 
pressures by 0.4 to arrive at optimal LPG pressures.

 23 

Observe flame through observation port at rear of burner.

 24 

Slowly bring burner to high fire position and avoid maximum 
temperature of dryer.

 25 

Close cover on pressure regulator and adjust all pressure switch-
es. High gas pressure switch at low fire. Low gas pressure switch 
at high fire.

 26 

Close cover on pressure regulator and adjust all pressure switch-
es. High gas pressure switch at low fire. Low gas pressure switch 
at high fire.

 27 

Air pressure switch at high fire by closing of air inlet until flame 
color start to change. Burner should trip by air pressure switch.

 28 

Reconnect control motor wiring, start burner and change sever-
al times between low and high fire position by changing temper-
ature controller settings.

 29 

Check all other safety devices such as pressure switches, high 
temperature limits etc. and adjust these devices to their correct 
values.

8 VALUPAK PACKAGe AnD BACK PRessURe

8.1 stable back pressure

Burner capacity will depend on back-pressure.
VP-II-150–900: The standard package can be used with stable back 
pressure between -2.0 and +2.0 mbar except for VP-II-60.
VP-II-60: See the table below.

Back-pressure

Capacities kW (HHV)

VP-II-60 

UHC102

VP-II-60 

UHC122

VP-II-60 

UMI300

min.

max.

min.

max.

min.

max.

< 2 mbar

not possible

2 mbar

not possible

not possible

3

65

1 mbar

2

25

2

50

3

75

0 mbar

2

40

2

60

3

80

- 1 mbar

3

45

3

65

4

90

- 2 mbar

3

50

4

70

5

100

< - 2 mbar

Not advised, please contact HTS sales or 

customer contact.

Once set for a specific back pressure:

 

– The package can fire stable on lower back pressures, but (min 

and max) capacity will increase, excess air will increase and 
higher CO/C

x

H

y

 could be the result.

 

– The package cannot be used on higher back pressures: this 

would result in reduced air factor, possible below 1.0 (with 
longer flames, incomplete combustion etc.).

Summary of Contents for Maxon VALUPAK-II

Page 1: ...rventions may only be carried out by qualified gas techni cians Electrical interventions may only be carried out by qualified electricians 1 5 Conversion spare parts All technical changes are prohibited Only use OEM spare parts 1 6 Instructions provided by the company Instructions provided by the company or individual responsible for the manufacture and or overall installation of a complete system...

Page 2: ...ditional loads will be created on the burner 3 4 Burner mounting flange loads Check burner weight and reinforce burner mounting flange or combustion chamber furnace back wall if necessary to take the complete burner weight 4 INSTALLATION 4 1 Handling of VALUPAK II burners VALUPAK II burners are shipped as complete units Handle burn ers with care using proper equipment during unpacking transport li...

Page 3: ...r 4 6 1 Spark ignitor orientation The spark igniter can be mounted in 4 different positions on the burner housing seen from the back of the burner left standard position right up blower side and bottom if the air inlet is on top VP II 60 has only 3 different positions There s no up connection to the blower side only left right and bottom down All spark ignitor arrangements 1 2 NPT connection D R L...

Page 4: ...ance or approval agency having jurisdiction and depends on the total amount of fresh air and the volume of combustion space A 5 fold refresh rate should be minimum At the end of the purge time of the burner flame safeguard programming relay ignition is energized and the main gas valve will be energized shortly after Because main gas cock is closed the programmer will lock out requiring manual rese...

Page 5: ...n equip ment according to the installation s manual are an integral part of its safety Inspection activities and frequencies shall be carried out as spec ified in the installation s manual Perform the following activities at least annually as part of a rec ommended preventative maintenance routine 1 Inspect burner internal parts for wear and oxidation paying spe cial attention to the refractory of...

Page 6: ...lease kW HHV 6 10 12 6 15 15 15 15 Pilot capacity typical kW HHV 28 35 51 44 50 49 59 Turndown1 58 1 43 1 50 1 45 1 51 1 71 1 85 1 Q gas max m3 h st 33 7 41 8 61 3 64 8 73 6 102 6 123 1 Q gas min m3 h st 0 6 1 0 1 2 1 5 1 5 1 5 1 5 Q air max m3 h st 388 482 706 747 848 1133 1418 Q air min m3 h st 64 82 117 148 209 230 276 Excess air at max n 1 2 1 2 1 2 1 2 1 2 1 15 1 2 Excess air at min n 11 4 8 ...

Page 7: ...se kW HHV 6 10 12 6 15 15 15 15 Pilot capacity typical kW HHV 23 29 51 37 42 41 49 Turndown1 48 1 36 1 50 1 37 1 42 1 59 1 71 1 Q gas max m3 h st 28 1 34 8 61 3 54 0 61 4 85 2 102 6 Q gas min m3 h st 0 6 1 0 1 2 1 5 1 5 1 5 1 5 Q air max m3 h st 323 401 706 622 707 981 1133 Q air min m3 h st 55 72 117 144 174 205 230 Excess air at max n 1 2 1 2 1 2 1 2 1 2 1 2 1 15 Excess air at min n 9 9 7 8 10 1...

Page 8: ...all be stored dry inside Burner blocks have been cured carefully before shipment and shall be kept dry Wetting of the blocks could result in premature failures Packaging Do not discard packing material until loose items are accounted for The packaging material is to be disposed of in accordance with local regulations 12 CERTIFICATION 12 1 Eurasian Customs Union The products VALUPAK II meet the tec...

Reviews: