14
MagneW 3000
PLUS Specification and Application Guide
1/98
Installation Planning Considerations
The MagneW 3000
PLUS planning considerations are summarized in Table 5. To ensure proper flowmeter selection
and operation, the following installation conditions should be reviewed:
• Environmental conditions
• Fluid to be measured
• Measured liquid flow conditions
• Detector location in piping
• Clearance for maintenance and inspection
Table 5—Summary of Installation Considerations
Factor
Consideration
Environmental conditions
The following should be considered when installing the MagneW 3000
PLUS.
• The ambient temperature should be within the following ranges:
–
Integral model:
–25 to +60
°
C (–13 to +140
°
F)
–
Remote converter:
–25 to +60
°
C (–13 to +140
°
F)
–
Remote detector:
PFA lining:
–30 to +80
°
C (–22 to +176
°
F)
Polyurethane rubber or Chloroprene rubber lining:
–30 to +60
°
C (–22 to +140
°
F)
• Whenever possible, the flowmeter should not be exposed to direct sunlight, rain, or other
unfavorable weather.
• The flowmeter should be installed as far from any pump in the line as practical, so that the flow
does not pulsate.
• The flowmeter must not be subjected to severe vibration, as equipment damage could result.
• The flowmeter must not be subjected to a highly corrosive atmosphere, as equipment damage
could result.
• The flowmeter must be installed sufficiently apart from high-current power lines, motors,
transformers, or any other source of electromagnetic interference.