Honeywell M896 Installation Instructions Manual Download Page 4

69-1089B–1

4

M896 DAMPER ACTUATOR

Home and Building Control
Honeywell Limited-Honeywell Limitée
155 Gordon Baker Road
North York, Ontario
M2H 3N7

Helping You Control Your World

®

69-1089B–1   G.H.   9-97   Printed in U.S.A.

Home and Building Control
Honeywell Inc.
Honeywell Plaza
P.O. Box 524
Minneapolis, MN 55408-0524

THE AIR DUCT IS CLOSED WHEN THE
INDICATOR POINTS PERPENDICULAR TO
THE DIRECTION OF THE AIR DUCT

THE AIR DUCT IS OPEN WHEN 
THE INDICATOR POINTS IN THE 
DIRECTION OF THE AIR DUCT

M3943

Fig. 6. Determining damper position.

Cooling

CAUTION

Damage to air conditioner condenser possible.
Do not operate cooling if outdoor temperature is
below 50

°

F (10

°

C).

1. Set the thermostat or controller to cool. Move the

setpoint 10

°

F (6

°

C) below the room temperature.

2. Make sure the cooling system operates.
3. Check that the damper remains in the closed

position. See Fig. 6.

4. Return the thermostat or controller to the desired

settings.

NOTE TO INSTALLER:

Explain to the homeowner that a yearly inspec-
tion by a trained, experienced service technician
is necessary for safe, efficient operation of the
vent damper and heating system. The home-
owner should check for deterioration from
corrosion or other sources between service
technician calls.

TROUBLESHOOTING

WARNING

Fire or explosion hazard.
Can cause property damage,
severe injury or death.
Explosion or carbon monoxide poisoning possible.
Never apply a jumper across or short gas control
terminals or wires. This can force the damper to
remain closed and cause an explosion.

NOTE:

If there is a power failure, the damper remains
exactly where it is at the moment of failure (open,
closed, or somewhere between). When power is
restored, the damper opens if the thermostat is
calling for heat or closes if the thermostat is not
calling for heat.

Set the thermostat or controller below the room tempera-
ture. Wait one minute and turn the thermostat or controller
above the room temperature to call for heat. If the system
does not start, leave the thermostat or controller calling for
heat and troubleshoot the M896/D896 as follows:

Use a voltmeter and check for 24 Vac at the S8600,
S8610, L8148E, gas valve or other control.

1. If no voltage, check the transformer, limit controller

and wiring.

2. If 24 Vac is present, and the D896 is open, refer to

the furnace or boiler manufacturer instructions.

3. If D896 is closed:

a.

Place the service switch in the SERV position.
See Fig. 4.

b.

Manually open the damper using a standard
screwdriver. Place screwdriver in slotted knob
(see Fig. 4) and rotate counterclockwise until
both LEDs turn on.

c.

If system does not light with damper in the
fully open position, replace the M896.

Summary of Contents for M896

Page 1: ...ess or death possible Prevent dangerous buildup of carbon monoxide Be sure damper used with M896 has a return spring that opens the damper if the coupler fails CAUTION Electrical shock or equipment damage possible 1 Disconnect power supply 2 Do not negate the action of any existing safety or operational control 3 Make sure that the damper return spring is operational prior to installing the actuat...

Page 2: ...CREWDRIVER TO MANUALLY OPEN AND CLOSE VENT DAMPER PLACE SCREWDRIVER IN SLOTTED KNOB AND ROTATE COUNTERCLOCKWISE UNTIL BOTH LEDS TURN ON 1 1 M896 M11367 Fig 4 Wiring diagram for M896 D896 connection to L8148E1166 using wiring harness with two Molex plugs MV MV PV PV GND BURNER 24V GND 24V SPARK S8600F H M S8610F H POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED REMOVE PLUG...

Page 3: ...2 B1 L2 5 4 5 5 3 4 S4 LED 2 LED 1 Fig 5 Wiring diagram for M896 D896 connection to S8600 S8610 using wiring harness with two Molex plugs SETTINGS The service switch has both a normal NORM and a service SERV mode NORM M896 opens on a call for heat and closes at the end of the heating cycle SERV M896 electrically opens after the thermostat has a call for heat and remains open CHECKOUT Heating 1 Tur...

Page 4: ...hnician calls TROUBLESHOOTING WARNING Fire or explosion hazard Can cause property damage severe injury or death Explosion or carbon monoxide poisoning possible Never apply a jumper across or short gas control terminals or wires This can force the damper to remain closed and cause an explosion NOTE If there is a power failure the damper remains exactly where it is at the moment of failure open clos...

Page 5: ...pertinente 4 Installer l actionneur de registre M896 comme pièce de rechange uniquement dans les systèmes à registre approuvés par l AGA CGA 5 Une fois l installation terminée vérifier le fonctionnement du produit comme l indique la section Vérification AVERTISSEMENT Peut causer des maladies graves et entraîner la mort Empêcher l accumulation dangereuse au monoxyde de carbone S assurer que le regi...

Page 6: ...E LE MODULE NE FONCTIONNERA QUE SI LE REGISTRE D AÉRATION EST BRANCHÉ 1 1 MF11369 SENSE TH W VENT DAMPER PLUG FAISCEAU DE FILS REGISTRE D AÉRATION M896 D896 2 2 4 Faire glisser la goupille par dessus l accouplement en flèche comme l illustre la Fig 1 Cela a pour effet de comprimer l accouplement en flèche 5 Installer l accouplement en flèche dans la fente de l arbre du registre en faisant pointer ...

Page 7: ...50 OHMS N F N O N F N O C C S1 S2 K1 N F N O C S3 T W TV Z C1 C2 L1 B2 B1 L2 5 4 5 5 3 4 S4 VOYANT 2 VOYANT 1 RÉGLAGES L interrupteur d entretien comporte la position normale NORM et la position service SERV NORM Le M896 s ouvre lors d une demande de chaleur et se referme à la fin du cycle de chauffage SERV Le M896 s ouvre électriquement après un appel de chaleur du thermostat et reste ouvert VÉRI...

Page 8: ...é et provoquer des blessures ou même entraîner la mort Risque d explosion ou d empoisonnement au monoxyde de carbone Ne jamais placer de cavalier entre les bornes ou les fils du régulateur à gaz et ne jamais court circuiter le régulateur à gaz Cela pourrait forcer le registre à rester en position de fermeture et provoquer une explosion REMARQUE En cas de panne de courant le registre restera exacte...

Reviews: