L91A,B,D PROPORTIONING PRESSURETROL

®

 CONTROLLERS

7

60-2152—08

point). The L91B settings provide system modulation between 

70 and 75 psi or between 75 and 80 psi, depending on the 

exact setting of the L91B main scale setpoint.

Due to device tolerances, the scaleplate settings are 

approximate and, therefore, the settings should be fine-tuned 

with the system operating.

Proportioning Range (L91B,D Only)

Adjust the proportioning range (throttling range) by turning the 

proportioning range adjusting screw (Fig. 6) on the top of the 

case until the proportioning range setting indicator is at the 

desired value. The proportioning range scale is graduated from 

A to F with a MIN (minimum) value below A. The value of each 

division depends on the operating range of the controller. Refer 

to Table 2 in the Specifications section.

Typical Operation

Pressure variations cause the bellows to expand or contract. 

Linkage between the bellows and the potentiometer wiper 

causes the wiper to move across the potentiometer windings. 

This varies the resistance between R and B, and between R 

and W, causing an unbalance in the circuit connected to the 

controller. See Fig 7.

Fig. 5. L91A,B,D operating points.

Fig. 6. Setting L91 Proportioning Pressuretrol

®

 Controller.

A proportioning controller is used most often to regulate the 

firing rate of a burner by controlling a modulating motor (Fig. 4) 

or a modulating valve. The controller potentiometer, the 

feedback potentiometer in the motor (or in the valve actuator), 

and a balancing relay in the motor (or actuator) form an electric 

bridge circuit. As long as the pressure of the controlled medium 

remains at the setpoint of the controller, the circuit is balanced; 

that is, equal the relay contacts are open. When the circuit is 

balanced, the motor (or actuator) does not run.

If the pressure of the medium rises, the wiper in the controller 

moves toward W. This unbalances the circuit, so a larger 

current flows through one side of the balancing relay. The 

close contacts in the relay make, causing the motor (or valve 

actuator) to drive toward its closed position. As the motor (or 

actuator) runs, the wiper on the feedback potentiometer moves 

in a direction to balance the circuit. When the circuit is again in 

balance, the balancing relay contacts open and the motor (or 

actuator) stops. The valves and dampers connected to the 

motor or actuator will be partially closed, decreasing the firing 

rate and reducing the pressure.

Similarly, if the pressure of the controlled medium falls, the 

wiper on the controller potentiometer moves toward B, and the 

open contacts in the balancing relay make. The motor (or 

actuator) drives toward its open position until circuit balance is 

achieved. The valves and dampers will be opened wider and 

the firing rate will increase, thus increasing the pressure.

A small change in the pressure of the controlled medium will 

cause a change in the firing rate to compensate for it, thus 

keeping the pressure constant. This process is called 

modulation.

M8519A

1

1

2

2

PROPORTIONING

RANGE

(WIPER)

POTENTIOMTER

LOW-FIRE

(CLOSED)

HIGH-FIRE

(OPEN)

MAIN SCALE

SETPOINT

B

W

R

PRESSURE

RISE

FIXED ON L91A; ADJUSTABLE ON L91B,D.

L91D HAS TWO POTENTIOMETERS OPERATING IN UNISION.

M8525

PROPORTIONING RANGE

ADJUSTING SCREW (L91B,D ONLY)

CONTROLLER 

POTENTIOMETER

MAIN SCALE

ADJUSTING

SCREW

WIPER ARM(S)

PROPORTIONING

RANGE 

SCALEPLATE

(L19B,D ONLY)

PROPORTIONING

RANGE SETTING

INDICATOR

(L91B,D ONLY)

TERMINAL BLOCK

BELLOWS 

HOUSING

MAIN

SCALEPLATE

MAIN SCALE

SETTING 

INDICATOR

1     KNURLED ADJUSTMENT KNOB ON 10 TO 300 PSI 

       [0.07 TO 2.07 MPa] MODELS.

1

Summary of Contents for L91A

Page 1: ...iphon loop is recommended Wiper on controller potentiometer moves in response to pressure changes L91D has two potentiometers for unison control of two motors L91B D models have adjustable proportioning throttling range to allow selection of desired pressure control range Adjustments made with screws on case top Large easily read scaleplates in both U S customary oz sq in psi or in Hg and metric k...

Page 2: ...rled knob for main scale setting on 10 to 300 psi 0 07 to 2 07 MPa models Setpoint At low pressure end of proportioning throttling range Main Scaleplate Marked in both U S customary oz sq in psi or in Hg and metric kPa MPa or mm Hg units Proportioning Range Scaleplate L91B D only Gradu ated from A to F with a MIN minimum value below A See Table 2 for the value of each division Mounting Means Fitti...

Page 3: ...6 Steam Trap siphon loop 1 4 in steel pipe with 1 4 18 NPT external threads on both ends 33312B Knurled Adjustment Knob With setscrew fits on main scale pressure adjusting screw 4074BWJ Limit Stop Assembly To limit setpoint ranges includes 129564 Range Stop 107194 Range Stop Screw and 23466 Wrench Table 2 Approximate value of each division A to B B to C etc on proportioning throttling range scalep...

Page 4: ...RE ALSO AVAILABLE WITH 1 4 19 BSP TR INTERNAL THREADS SEE TABLE 1 PROPORTIONING RANGE ADJUSTING SCREW ON L91B D MODELS ONLY 33312B KNURLED ADJUSTMENT SCREW KNOB 7 8 IN 22 2 MM DIAMETER KNOB IS INCLUDED WITH 10 TO 300 PSI 0 07 TO 07 MPa MODELS OPTIONAL ACCESSORY FOR OTHER MODELS FOR 10 TO 300 PSI 0 07 TO 2 07 MPa MODELS DIM C INCLUDES THE KNURLED ADJUSTMENT KNOB TABULATION OF DIMENSIONS A B AND C O...

Page 5: ...ns in accordance with approved standards Use only a small amount of pipe compound to seal the connection joints Excess pipe compound may clog the small hole in the fitting and prevent the controller from operating properly To avoid leaks and damage to the case use a parallel jaw wrench on the controller fitting Do not tighten the controller by hand by holding onto the case and turning it Fig 2 App...

Page 6: ...ain Scale Set Point All models Adjust the main scale setpoint for the desired operating pressure by turning the main scale adjusting screw Fig 7 or knurled adjustment knob on 10 to 300 psi 0 07 to 2 07 MPa models on the top of the case until the main scale setting indicator is at the minimum pressure desired The proportioning range extends above this value The scaleplate is marked in both customar...

Page 7: ...nced that is equal the relay contacts are open When the circuit is balanced the motor or actuator does not run If the pressure of the medium rises the wiper in the controller moves toward W This unbalances the circuit so a larger current flows through one side of the balancing relay The close contacts in the relay make causing the motor or valve actuator to drive toward its closed position As the ...

Page 8: ...e controller The ohmmeter should read about 135 ohms for an L91A B or D 5 Connecting the ohmmeter between controller terminals W and R Fig 8 and raising the setpoint of the controller above the actual pressure being measured The ohmme ter should read the full value of the potentiometer mea sured in step 4 135 ohms for an L91A B or D 6 Slowly lowering the setpoint of the controller while observing ...

Page 9: ... the wiper arm and not to change the wiper tension Any damage or change in tension will decrease the life of the new potentiometer 1 Disconnect all power to the controller 2 Loosen the cover screw below the main scaleplate and remove the cover 3 Mark the wires to the external device motor or valve actuator and disconnect them from the terminal block 4 Remove the screw holding the terminal block br...

Page 10: ...A 0 4 6 2 1 3 4 5 16 14 12 10 8 0 kPa OZS IN 2 DIFF IS ADDITIVE 2 6 7 M8547A BARE WIRES ENAMEL REMOVED TERMINAL BLOCK R W B POTENTIOMETER WIRES WIPER ARM BOLT POTENTIOMETER ACTIVE WINDING POTENTIOMETER BRACKET 1 1 2 2 THE POTENTIOMETER IN AN L91A IS MOUNTED AT A 45 DEGREE ANGLE INSTEAD OF HORIZONTALLY AN L91D HAS TWO POTENTIOMETERS TERMINALS ARE LABELED DIFF MAIN MIN B D F E C A 0 4 6 2 1 3 4 5 16...

Page 11: ...L91A B D PROPORTIONING PRESSURETROL CONTROLLERS 11 60 2152 08 ...

Page 12: ...ons Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 Honeywell Limited Honeywell Limitée 35 Dynamic Drive Toronto Ontario M1V 4Z9 customer honeywell com U S Registered Trademark 2009 Honeywell International Inc 60 2152 08 K K Rev 12 09 Printed in U S A ...

Reviews: