IC 40 · Edition 07.18
55
Function
Blue LED
Red LED
BCSoft fault
code
Warning/fault
Description
Cause
According to
operating state
Flashing light (7×)
21
Warning
Service note: number of OPEN/CLOSE
cycles > limit value
According to
operating state
Flashing light (8×)
22
Warning
Service note: number of changes of
direction > limit value
According to
operating state
Flashing light (9×)
23
Warning
Service note: number of relay output RO
1 or RO 2 switching operations > limit
value
Flashing light (1×)
Permanent light
5
Fault
Internal fault
- e.g. EEPROM reading or writing error
Flashing light (2×)
Permanent light
11
Fault
Zero position check: reference switch
does not close
- Valve blocked
- Internal error
- Actuator offset
- Valve not closed (BVHS)
Flashing light (3×)
Permanent light
12
Fault
Zero position check: reference switch
does not open
- Valve blocked
- Internal error
- Actuator offset
Flashing light (6×)
Permanent light
30
Fault
Saving error for adjustable parameters,
etc.
Flashing light (7×)
Permanent light
31
Fault
Saving error: factory default parameters
Flashing light (8×)
Permanent light
32
Fault
Saving error: user calibration
Flashing light (9×)
Permanent light
15
Fault
Low voltage
Check actuator mains voltage supply