IC 40 · Edition 07.18
22
middle
t [s]
high
low
closed
DI 1
DI 2
t [s]
t
1
t
2
t
3
t
4
t
5
t
6
Function
Operating mode 6
DI 1 with continuous signal, for instance resulting from
inversion of the logic, see page 48 (Switching logic):
The actuator operates in high/low (high/closed) inter-
mittent mode via digital input DI 2 with two successive
running times up to 51 s (2 x 25.5 s).
DI 1 and DI 2 are connected in parallel:
The actuator operates with one signal in high/closed
intermittent mode with three successive running times
up to 76.5 s (3 x 25.5 s).
With three successive running times via interpolation
points, it is possible to change the opening character-
istic of the butterfly valve. For example, the character-
istic of the air circuit can be adapted to that of the gas
circuit.
Control via two digital inputs
If all possible combinations of the two inputs are used,
for instance by a PLC control system, it is possible to
implement high/middle/low/closed intermittent mode
(3 stages plus the “closed” position).
Possible parameter set for this operating mode:
P 68001, see page 45 (Parameter sets).