Checking the usage

The bus module BCM 400..B1 is used as a commu-

nication interface for burner control units BCU 460, 
BCU 465 or BCU 480 for connection to a fieldbus 
interface via PROFIBUS.
Networking via the fieldbus enables the BCUs to be 
controlled and monitored by an automation system 
(e.g. PLC). The communications network must be 
protected against unauthorized access.

This function is only guaranteed when used within the 

specified limits – see page 6 (Technical data). Any 
other use is considered as non-compliant.

Type code

Code

Description

BCM

Bus module

400

Series 400

S0 

S

Standard communication 

SafetyLink

B 

B 

B 

B4

PROFIBUS DP 

PROFINET 

EtherNet/IP 

Modbus TCP

/ 

/

9-pin D-Sub 

Two RJ45 sockets

-0 

-

– 

Three-point step control via bus

Part designations

3

4

1

2

BCM../1 with 9-pin D-Sub connection

9-pin D-Sub connection

Code switches

4

Type label

Ambient temperature (

A + B

) – see type label.

Elster GmbH

Osnabrück, Made in Germany

-

A

B

Installation

  

 Disconnect the BCU from the electrical power 

supply.

  

 Open the cover of the BCU.

  

 Insert the bus module in the slot provided.

Replacement

  

 Disconnect the BCU from the electrical power 

supply.

  

 Open the cover of the BCU.

  

 Remove the connection plug from the power 

and bus module.

 4 

 Remove the modules in the following order to 

facilitate handling:

 

.

 Power module,

 

.

 Bus module.

2.

1.

 

Installation of the modules in reverse order.

Summary of Contents for Kromschroder BCM 400 B1 Series

Page 1: ...ctions Information that is relevant for safety is indicated in the instructions as follows DANGER Indicates potentially fatal situations WARNING Indicates possible danger to life and limb CAUTION Indicates possible material damage All interventions may only be carried out by qualified gas technicians Electrical interventions may only be carried out by qualified electricians Conversion spare parts ...

Page 2: ...tandard communication SafetyLink B1 B2 B3 B4 PROFIBUS DP PROFINET EtherNet IP Modbus TCP 1 3 9 pin D Sub Two RJ45 sockets 0 3 Three point step control via bus Part designations 3 4 1 2 1 BCM 1 with 9 pin D Sub connection 2 9 pin D Sub connection 3 Code switches 4 Type label Ambient temperature A B see type label Elster GmbH Osnabrück Made in Germany A B Installation 1 Disconnect the BCU from the e...

Page 3: ... and software can be downloaded from www docuthek com 1 Set parameter A080 2 Fieldbus communica tion without address check 2 Check the code switch settings 001 to 125 on the BCM for PROFIBUS communication between BCSoft and the control unit Each code switch setting combination may only exist once within the fieldbus system Each device name network name may only be allocated once within the fieldbu...

Page 4: ...P 4 ϑ2 5 Reserved 6 Reserved 7 Reserved P A A P DI on on on 1 2 Operating signal pilot burner P A A P DI on on on 1 2 Operating signal main burner P A A P DI on on on 1 2 Fault signal P A A P DI on on on 1 2 Operating signal air actuator P A A P DI on on on 1 2 Purge operating signal P A A P DI on on on 1 2 High temperature operation P A A P DI on on on 1 2 Ready for operation P A A P DI on on on ...

Page 5: ...missioning If the transfer rate is reduced remember that this will increase the signal running times to and from the individual units Poor shielding Check whether the shield is connected to the shield clips in the PROFIBUS DP plugs in full and over a wide area Poor equipotential bond Check whether the PROFIBUS DP shield is con nected at all points to the same ground potential via the grounding sys...

Page 6: ... location min IP 65 for installation in BCU 4xx Permitted operating altitude 2000 m AMSL Mechanical data Dimensions W H D 96 63 23 mm 3 78 2 48 0 91 inch Weight 0 3 kg Electrical data Power consumption 1 2 VA Power loss 0 7 W Designed lifetime Max service life under operating conditions 10 years after date of production Logistics Transport Protect the unit from external forces blows shocks vibrati...

Reviews: