If you have any technical questions, please contact 
your local branch office/agent. The addresses are 
available on the Internet or from Elster GmbH.

We reserve the right to make technical modifications 

in the interests of progress.

Elster GmbH

Strotheweg 1, D-49504 Lotte (Büren)

Tel. +49 541 1214-0

Fax +49 541 1214-370

[email protected], www.kromschroeder.com

Contact

Technical data

Ambient conditions

Avoid direct sunlight or radiation from red-hot 

surfaces on the unit. 

Avoid corrosive influences, e.g. salty ambient air 

or SO

2

The unit may only be stored/installed in enclosed 

rooms/buildings. 

This unit is not suitable for cleaning with a high-

pressure cleaner and/or cleaning products.

Ambient temperature:   

-20 to +70°C (-4 to +158°F),  

no condensation permitted.

Transport temperature = ambient temperature.

Storage temperature: -20 to +70°C (-4 to +158°F).
Enclosure: IP 20 pursuant to IEC 529.
Installation location: min. IP 65 (for installation in 
BCU 4xx).
Permitted operating altitude: < 2000 m AMSL.

Mechanical data

Dimensions (W × H × D):
96 × 63 × 23 mm (3.78 × 2.48 × 0.91 inch).
Weight: 0.3 kg.

Electrical data

Power consumption: 1.2 VA.
Power loss: 0.7 W.

Designed lifetime

Max. service life under operating conditions:

10 years after date of production.

Logistics

Transport

Protect the unit from external forces (blows, shocks, 
vibration). 

Transport temperature: see page  6 (Technical 

data)

Transport is subject to the ambient conditions de-

scribed. 
Report any transport damage on the unit or packag-
ing without delay. 
Check that the delivery is complete, see page 2 
(Part designations).

Storage

Storage temperature: see page 6 (Technical data).
Storage is subject to the ambient conditions de-
scribed. 
Storage time: 6 months before using for the first 
time. If stored for longer than this, the overall service 
life will be reduced by the corresponding amount of 
extra storage time.

Packaging

The packaging material is to be disposed of in ac-

cordance with local regulations.

Disposal

Components are to be disposed of separately in 
accordance with local regulations.

Summary of Contents for Kromschroder BCM 400 B1 Series

Page 1: ...ctions Information that is relevant for safety is indicated in the instructions as follows DANGER Indicates potentially fatal situations WARNING Indicates possible danger to life and limb CAUTION Indicates possible material damage All interventions may only be carried out by qualified gas technicians Electrical interventions may only be carried out by qualified electricians Conversion spare parts ...

Page 2: ...tandard communication SafetyLink B1 B2 B3 B4 PROFIBUS DP PROFINET EtherNet IP Modbus TCP 1 3 9 pin D Sub Two RJ45 sockets 0 3 Three point step control via bus Part designations 3 4 1 2 1 BCM 1 with 9 pin D Sub connection 2 9 pin D Sub connection 3 Code switches 4 Type label Ambient temperature A B see type label Elster GmbH Osnabrück Made in Germany A B Installation 1 Disconnect the BCU from the e...

Page 3: ... and software can be downloaded from www docuthek com 1 Set parameter A080 2 Fieldbus communica tion without address check 2 Check the code switch settings 001 to 125 on the BCM for PROFIBUS communication between BCSoft and the control unit Each code switch setting combination may only exist once within the fieldbus system Each device name network name may only be allocated once within the fieldbu...

Page 4: ...P 4 ϑ2 5 Reserved 6 Reserved 7 Reserved P A A P DI on on on 1 2 Operating signal pilot burner P A A P DI on on on 1 2 Operating signal main burner P A A P DI on on on 1 2 Fault signal P A A P DI on on on 1 2 Operating signal air actuator P A A P DI on on on 1 2 Purge operating signal P A A P DI on on on 1 2 High temperature operation P A A P DI on on on 1 2 Ready for operation P A A P DI on on on ...

Page 5: ...missioning If the transfer rate is reduced remember that this will increase the signal running times to and from the individual units Poor shielding Check whether the shield is connected to the shield clips in the PROFIBUS DP plugs in full and over a wide area Poor equipotential bond Check whether the PROFIBUS DP shield is con nected at all points to the same ground potential via the grounding sys...

Page 6: ... location min IP 65 for installation in BCU 4xx Permitted operating altitude 2000 m AMSL Mechanical data Dimensions W H D 96 63 23 mm 3 78 2 48 0 91 inch Weight 0 3 kg Electrical data Power consumption 1 2 VA Power loss 0 7 W Designed lifetime Max service life under operating conditions 10 years after date of production Logistics Transport Protect the unit from external forces blows shocks vibrati...

Reviews: