Installation

 CAUTION

Please observe the following to ensure that the DG 

is not damaged during installation and operation:

–   Continuous operation with gases containing 

more than 0.1 %-by-vol. H

2

S or ozone con-

centrations exceeding 200 µg/m³ accelerate 

the ageing of elastomer materials and reduce 

the service life.

–   Use approved sealing material only.

–  

Dropping the device can cause permanent dam-

age. In this event, replace the entire device and 

associated modules before use.

–   Check max. ambient temperature  – see 

page 3 (Technical data).

–   When using silicone tubes, only use silicone 

tubes which have been sufficiently cured.

–   Vapours containing silicone can adversely affect 

the functioning of electrical contacts.

–   Condensation or vapours containing silicone 

must not be allowed to get into the housing. 

At subzero temperatures malfunctions/failures 

due to icing can occur.

–  

When installing outdoors, place the DG in a 

roofed area and protect from direct sunlight 

(even IP 65 version). To avoid condensation, a 

cover with pressure equalization element (Order 

No. 74923391) can be used.

–   Avoid strong impact on the unit.

–   In case of highly fluctuating pressures, install a 

restrictor orifice (Order No. 75456321).

 

Installation position as required, preferably with 
vertical diaphragm. Then the switching point p

S

 

corresponds to the scale value SK set on the 
hand wheel. In other installation positions, the 
switching point p

S

 will change and no longer 

correspond to the scale value SK set on the 
hand wheel. Check the switching point.

ps = SK

ps =SK + 0,18 mbar ps = SK - 0,18 mbar

 

The DG must not be in contact with masonry. 

Minimum clearance 20 mm.

 

Ensure that there is sufficient installation space.

 

Ensure unobstructed view of the hand wheel.

 1 

  Disconnect the system from the electrical power 

supply.

 2 

 Shut off the gas supply.

 3 

 Ensure that the pipeline is clean.

2

1

3

4

and

 2

Positive pressure (Rp ¼)

and

 4

Negative pressure (Rp 

1/8

)

Connect

Seal

Free

Positive pres-
sure DG..U

1

2

or

 4

2

1

or

 4

Negative pres-
sure DG..U

3

4

or

 2

4

3

or

 2

Differential pres-
sure DG..U

1

 or 

2

 for higher absolute pressure. 

3

 or 

4

 for lower absolute pressure. 

Seal the ports that are not in use.

Positive pressure 
DG..B

1

 4 

  If the electrical contacts in the DG could be soiled 

by dirt particles in the surrounding air or in the 
medium, use a filter pad (Order No. 74946199) 
at port 

3

/

4

. On IP 65 units, the filter pad is fitted 

as standard, see type label.

Wiring

 

If the DG..G has switched a voltage > 24 V and a 
current > 0.1 A at cos φ = 1 or > 0.05 A at cos φ = 
0.6 once, the gold plating on the contacts will have 
been burnt through. It can then only be operated at 
this power rating or higher power rating.

 

Pressure switch DG can be used in Zone 1 
(21) and 2 (22) hazardous areas if an isolating 
amplifier is installed upstream in the safe area 
as “Ex-i” equipment pursuant to EN 60079-11 
(VDE 0170-7):2012.

 

DG as “simple electrical equipment” pursuant to 
EN 60079-11:2012 corresponds to the Tempera-
ture class T6, Group II. The internal inductance/
capacitance is Li = 0.2 μH/Ci = 8 pF.

 CAUTION

Please observe the following to ensure that the DG 
is not damaged during operation:

–   Note the switching capacity, see page  

(Technical data).

 

In the case of low switching capacities, such as 
24 V, 8 mA, for example, we recommend using an 
RC module (22 Ω, 1 μF) in air containing silicone or oil.

 1 

  Disconnect the system from the electrical power 

supply.

M16 x 1,5:

ø 4–10 mm

3

4

2

5

6

7

 

Contacts 

3

 and 

2

 close when subject to increas-

ing pressure. Contacts 

1

 and 

3

 close when sub-

ject to falling pressure.

Summary of Contents for Krom Schroder DG B Series

Page 1: ...chnical changes are prohibited Only use OEM spare parts Changes to edition 11 17 The following chapters have been changed Declaration of conformity Checking the usage Gas pressure switches DG for monitoring increasing and decreasing gas or air pressure Positive pressure Negative pressure DG B Gas air flue gas DG U Gas air flue gas Air flue gas This function is only guaranteed when used within the ...

Page 2: ...tallation space Ensure unobstructed view of the hand wheel 1 Disconnect the system from the electrical power supply 2 Shut off the gas supply 3 Ensure that the pipeline is clean 2 1 3 4 1 and 2 Positive pressure Rp 3 and 4 Negative pressure Rp 1 8 Connect Seal Free Positive pres sure DG U 1 2 3 or 4 2 1 3 or 4 Negative pres sure DG U 3 4 1 or 2 4 3 1 or 2 Differential pres sure DG U 1 or 2 for hig...

Page 3: ... with biogas A function check can be carried out in case of decreasing pressure control e g with the PIA After carrying out the maintenance work check for tightness see page 3 Tightness test Technical data Gas type natural gas town gas LPG gaseous flue gas biogas max 0 1 by vol H2S and air Max inlet pressure pmax withstand pressure see page 3 Adjustment Max test pressure for testing the entire sys...

Page 4: ...eclare that the prod uct DG with product ID No CE 0085AP0467 com plies with the requirements of the listed Directives and Standards Directives 2009 142 EC GAD valid until 20 April 2018 2014 35 EU LVD Regulation EU 2016 426 GAR valid from 21 April 2018 Standards EN 13611 2015 AC 2016 EN 1854 2010 The relevant product corresponds to the tested type sample The production is subject to the surveillanc...

Reviews: