BCU 580 · Edition 11.15l
47
Profinet
“BCU input terminal information” module (device
➔
controller) – slot 9
This module transfers the signal states of the digital in-
puts on the BCU (input terminals) to the PLC.
Bit Byte n
Byte n+1
Byte n+2
Format
0
Terminal 1
Terminal 48
Terminal 68
BOOL
1
Terminal 2
Terminal 49
Free
BOOL
2
Terminal 3
Terminal 50
Free
BOOL
3
Free
Terminal 51
Free
BOOL
4
Terminal 44
Terminal 52
Free
BOOL
5
Terminal 45
Terminal 65
Free
BOOL
6
Terminal 46
Terminal 66
Free
BOOL
7
Terminal 47
Terminal 67
Free
BOOL
“BCU output terminal information” module (device
➔
controller) – slot 10
This module transfers the signal states of the digital
outputs on the BCU (output terminals) to the PLC.
Bit Byte n
Byte n+1
Format
0
Terminal 9
Terminal 42
BOOL
1
Terminal 10
Terminal 43
BOOL
2
Terminal 13
Terminal 53
1)
BOOL
3
Terminal 14
Terminal 54
BOOL
4
Terminal 15
Terminal 55
BOOL
5
Terminal 17/18
Terminal 56
BOOL
6
Terminal 37/38
Terminal 57
BOOL
7
Terminal 41
Free
BOOL
1)
Only for BCU..F2: terminal 53 is used as an input.
Bit 6 has no function.