MU1H-1408GE23 R0305
16
Honeywell GmbH
GB
9.2.1 Water hardness
1. Simultaneously press the and buttons for 5
seconds.
2. Enter the calculated set value via the and
buttons.
3. Press the button once to go to the next setting.
9.2.2 Regeneration
Note:
In operation or water consumption the residual capaci-
ty is reduced from the set amount to zero.
Time-delayed, volume-controlled regeneration
Regeneration is triggered at the set time.
1. Press the and buttons to change the time.
2. Press the button once to go to the next setting.
Forced regeneration
Note:
If the programmed number of days between two rege-
nerations has been reached, a forced regeneration is
triggered at the set time. The forced regeneration is
triggered irrespective of the residual volume.
1. Press the and buttons to change the num-
ber of days.
2. Press the button once to accept all the chan-
ges.
Manual regeneration
There are two manual regeneration possibilities avai-
lable.
1. Possibility
1. Press the button for 5 seconds.
Manual regeneration starts immediately.
2
. Possibility
1. Press the button for a short time.
Manual regeneration starts at the set time
(
☞
Chapter 9.2.2)
Change to the next regeneration phase
1. Press the button once to go to the next regene-
ration phase..
If the water conditioning device is in between two
phases, pressing the button has no effect.
10. Power Failure
10.1Settings
The time has to be reentered after a power failure
☞
Chapter 9.1.
All the control valve settings remain and are restored
once the power supply has been reconnected.
10.2General Information
If the power is down for a longer period, the water con-
ditioning device should be set to "Bypass"
(
☞
Chapter 8.4)
i
Set to 1750 at the factory!
CAUTION!
If
is displayed, press no further
buttons (test mode manufacturer)!
Wait for approx. 10 seconds until the current
time is redisplayed!
Residual volume 530 litres Residual volume 0 litres
i
Set to 2.00 a.m. at the factory!
Input: 24-hour mode
Time regeneration
i
Set to 14 days at the factory!
Input: OFF up to 99 days
Forced regeneration
i
LED operating display flashes(
☞
Chapter 8.1)