PN-292-103
I/O Map
Description
Default Address
21
Window Segment 4 Inverted
215
22
Window Segment 5
216
23
Window Segment 5 Inverted
216
24
Window Segment 6
217
25
Window Segment 6 Inverted
217
26
Window Segment 7
218
27
Window Segment 7 Inverted
218
28
Smoke
219
29
Smoke Inverted
219
30
Key Tag
219
K595 Functionality Testing
K595 functionality depends on the specific I/O Map used in
the binding.
Testing Motion Detection
After the unit is bound to the thermostat, press the bind
switch two times on the K595. The unit will transition into the
PIR walk test mode for 60 seconds, which will sound the
piezo on the thermostat when the K595 detects motion.
References
1
RF Transmit Power (Tx) and RF Channel are displayed
together in hexadecimal (hex) notation as RF Tx Power RF
Channel.h. Hexadecimal is a Base 16 notation using the
alphanumeric figures 0 through F. See a
conversion chart
or
website like
Statman.info
for help. Tx is limited to four fixed
values—0=0dB, 1=+3dB, 2=-6dB, 3=-25dB. 0db is default
Tx power. +3db is 2x (twice) the default Tx power.
Use
only 0db or +3dB.