Honeywell INNCOM e528 Series Product Manual Download Page 11

E528 Product Guide 

 

Rev 8.0 12/16/2016

 

11

 

 

 

RS485 centrally controlled system), door/window switch, or external PIR 

wiring within the electrical box (Figure 8). Plug the 6-pin low voltage 

harness onto the e528 low voltage comm. / device connection header.  

2.  Use wire nuts to connect the 10-pin Molex wiring harness to the power and 

valve/fan control signal wires within the electrical box.  

3.  Plug the pre-wired 10-pin connector into the female receptacle at the back 

of the e528.  

4.  Hook the tabs at the top rear of the e528 housing into the matching 

depressions at the top of the mounting plate and rotate the bottom of the 

housing toward the wall until it snaps into place on the mounting plate.  

5.  Secure the housing to the mounting plate with the two small screws 

removed in Step 1 of the 

Mounting 

section.  

6.  Apply power to the e528 by closing the applicable supply breaker. Verify 

that the e528 powers up. Several values should begin appearing on the 

LCD display.  

7.  Once installed and connected to power, the e528 Digital Thermostat 

typically requires some configuration, specifically:  

 

If installing the e528 as part of a networked, centrally controlled EMS, 

a unique network address must be assigned to the e528. This is done 

by entering Service Parameter mode on the e528 and changing the 

values of Parameters 10, 11, and 12, which hold the 5-digit network 

address of the e528. This 5-digit number is typically the room number 

in most applications. A “Room List” document is typically available that 

lists all rooms and the associated values to set into Parameters 10, 11, 

and 12. Refer to Reference A, Section 5.1, for complete instructions for 

setting the e528 network address.  

 

If the particular HVAC equipment installed was not known when the 

e528 was shipped, the fan and heat/cool control outputs of the e528 

must be configured to correctly operate the installed HVAC equipment. 

Setting the appropriate HVAC control parameters of the e528 to the 

required values and resetting the device reconfigures the e528 to 

properly control most HVAC units. Refer to Reference A, Section 5.2, 

for instructions on changing the e528 HVAC related parameters.  

NOTE: 

If installing 01-9560 64K memory e528 Digital Thermostats, be aware 

that these devices support the INNCOM ES-1 Flash Memory Module. The ES-

1 provides the ability to copy HVAC related parameter settings from a “golden” 

e528 that has previously been installed in a room and had its HVAC related 

parameters set correctly and verified operationally with the HVAC equipment. 
Once these settings are copied to the ES-1 module, plugging the ES-1 into a 

new thermostat automatically uploads the settings. 

 

 

Summary of Contents for INNCOM e528 Series

Page 1: ...ge 1 Overview and General Concept Page 2 Application Page 2 Wireless Communication Page 4 Installation Requirements Page 4 Mounting Page 5 Input Output Page 6 E528 4G New Installation Page 8 Wiring Page 10 Load Specifications Page 13 FCC Information Page 13 Technical Specifications Page 14 Document Revision History Page 15 ...

Page 2: ...r cool by pressing the OFF AUTO button and cycling through OFF AUTO HEAT and COOL The e528 is also an intelligent device capable of linking ancillary sensors and serving as an information gateway For example coupled with a magnetic door switch wired or wireless motion detectors and other devices the e528 becomes the brain of a highly effective Energy Management System EMS application communicating...

Page 3: ...m PMS BMS interface A centrally controlled EMS package is created when the e528 is connected to the property s Central Interface Network CINET with a pair of low voltage wires or by the property s high speed TCP IP network with the addition of a TCT an Ethernet gateway device RF networking is possible with radio equipped models The e528 features a guest friendly graphic interface with intuitive co...

Page 4: ...he wall and mounted level in both the horizontal and vertical planes incorrect mounting can degrade IR PIR and temperature measurement performance Installation Requirements for e4 equipped with PIR Motion Detection The e4 thermostat can be equipped with a PIR detector to augment the energy management scheme by detecting motion in the guestroom Consider the PIR s view angle range characteristics an...

Page 5: ...pull the back mounting plate down 3 Position the back plate insulator within the mounting plate as shown in Figure 4 4 Attach the mounting plate to the junction box using the mounting screws provided with the e528 Ensure that the plate is mounted with the raised arrow pointing UP To simplify installing and removing the e528 the headers and sockets described below and shown in Figure 5 are located ...

Page 6: ...and 4G For specifics refer to the as built wiring diagrams 3G and 4G are internal INNCOM product designations used for convenience to differentiate individual hardware configurations No difference in device capability or effectiveness is implied Due to end of life for certain 3G components the e528 4G is now the standard INNCOM install but 3G installations are still supported E528 3G headers E528 ...

Page 7: ...t common way to connect the e528 3G is to connect a PC 485 S5 P N 01 9905 on the S5bus E528 4G to 2G RS485 Networked Application with or without door switch input See Figure 6 Using the adapter P N 203 251 connect the harness from the wall box P N 62 1462 previously connected to the thermostat being replaced to H1 of the adapter Connect the harness H3 rainbow of 203 251 to the low voltage comm dev...

Page 8: ...See Figure 7 Using the harness P N 62 1467 make the appropriate wire connections then plug the harness into the low voltage comm device connection of the e528 4G Using the adapter P N 203 250 and P N 62 1532 B 12 cables connect the RS485 A pair to the two pin RS485 In header and the RS485 B pair going to the next thermostat to RS485 Out header on the 203 250 Connect the harness of 203 250 to the R...

Page 9: ...ing leads These leads should be connected to the 24VAC or 100 277VAC power valve fan control wiring from the FCU or other HVAC device with wire nuts inside in the wall junction box in accordance with the wiring diagram provided by INNCOM Note For installations in which all leads are not required the extraneous leads should be cut off at the Molex connector Figure 8 shows the pinout for the 10 posi...

Page 10: ...Medium Fan or Second Stage Heat 6 Red Cold Water Valve FCU or Compressor Signal Heat Pump 7 Brown Hot Water Valve FCU or Reversing Valve Heat Pump 8 Grey Valve Power 9 Violet Fan Power 10 Blue Low Fan Wiring The steps below provide an overview of the wiring process Refer to the as built wiring diagrams provided for exact details 1 If applicable use wire nuts to connect the 6 pin low voltage harnes...

Page 11: ...ne by entering Service Parameter mode on the e528 and changing the values of Parameters 10 11 and 12 which hold the 5 digit network address of the e528 This 5 digit number is typically the room number in most applications A Room List document is typically available that lists all rooms and the associated values to set into Parameters 10 11 and 12 Refer to Reference A Section 5 1 for complete instr...

Page 12: ...al Separator Figure 11 Electrical Box Connections 24VAC 24 volt and ground wires must be routed to the low voltage side of the box passing over the top of the physical separator They should be connected on the low voltage side with appropriate size wire nuts 24 volt transmitter Low voltage communication door window switch external PIR wiring 24 VAC or 100 277 VAC power valve fan control wiring fro...

Page 13: ... Fan Relay K2 3 3 amps 125 277VAC General purpose 3 amps 125 277VAC General purpose 2 2 LLA 13 2 LRA 2 2 LLA 13 2 LRA 2 2 LLA 13 2 LRA 2 2 LLA 13 2 LRA MFCC ID GTC202150TXR or GTC202152TXR This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful int...

Page 14: ...sceptible d en compromettre le fonctionnement Technical Specifications Table 7 Technical Specifications Power Requirements 24 VAC at 50 60 Hz 24 VDC nominal 2 4 VA e528 3xx 7xx and e528 4xx 100 to 277 VAC at 50 60 Hz 2 4 VA e528 8xx Relay Contact Rating See Table 4 Triac Relay Contact Rating 50 m at minimum 250 m at maximum e528 4xx Recommended Wire Size 18 gauge Thermostat Measurement Range 33 to...

Page 15: ... v6 2 28 Oct 2010 Added 3G pinout note v7 0 05 Apr 2012 Added 4G information v7 1 18 Dec 2012 Revised FCC IC statements v7 2 12 Feb 2013 Removed ordering information V7 3 10 Feb 2014 Updated connector photos V8 15 Dec 2016 Reformat to HON branding Remove G2 Legacy info The material in this document is for information purposes only The content and the product it describes are subject to change with...

Reviews: