HPF-PS Series Instruction Manual —
P/N LS10227-003HP-E:C 2/2/2022
17
FACP with HPF-PS Power Supply in Slave Configuration
Installation
2.5 FACP with HPF-PS Power Supply in Slave Configuration
In this application, the power supply is configured as a Slave unit and connected to a master FACP programmed for synchronized output. .
The following notes apply to Figure 2.7 on page 17
1.
Refer to NFPA 72, Chapter 4-4, Visible Characteristics, Public Mode.
2.
Use only devices from the same manufacturer in each system.
3.
Set Output DIP Switch: position 3=ON, 4 = OFF, 5 = ON, 6 = OFF.
4.
If the FACP has a dedicated sync output connector, wire the remote sync output connector to Input #1 terminals 2 and 3.
5.
In this example, the output is mapped to Input#1 in Slave Configuration, but it can programmed to another input using the DIP switches.
6.
For NFPA 72 compliance, notification appliances cannot be installed on the FACP control circuit connecting to the HPF-PS input
circuits.
2.6 HPF-PS Power Supply in Master Configuration Connected to FACP
In this application, a master HPF-PS power supply, set for synchronization, is connected to an FACP with non-synchronized output.
The following notes apply to Figure 2.8.
1.
Refer to NFPA 72, Chapter 4-4, Visible Characteristics, Public Mode.
2.
Set Output DIP switches to the desired sync protocol as described below. Refer to the
Device Compatibility Document
for devices.
TB15
A
- B
+
B
-
A
+
A
-
B
+
B
-
A
+
A
-
B
+
B
-
A
+
HPF-PS
FACP
NAC programmed for sync
or remote sync output
ELR for
FACP
NAC
Figure 2.7 Supervised Master/Slave Connections
DIP Switch Position
Synchronization Type
3
4
5
6
OFF
ON
ON
OFF
Master Configuration - ANSI Temporal (Temporal 3)
ON
ON
ON
OFF
Master Configuration - CO Temporal (Temporal 4)
OFF
OFF
OFF
ON
Master Configuration - Amseco/Potter
OFF
ON
OFF
ON
Master Configuration - Gentex
OFF
OFF
ON
ON
Master Configuration - System Sensor
OFF
ON
ON
ON
Master Configuration - Wheelock
ON
OFF
OFF
ON
Master Configuration, Selective Silence - Amseco/Potter
ON
ON
OFF
ON
Master Configuration, Selective Silence - Gentex
ON
OFF
ON
ON
Master Configuration, Selective Silence - System Sensor
ON
ON
ON
ON
Master Configuration, Selective Silence - Wheelock
TB15
A
- B
+
B
-
A
+
A
-
B
+
B
-
A
+
A
-
B
+
B
-
A
+
HPF-PS
Figure 2.8 Supervised FACP to Master Connections (non-synchronized source)
FACP
(also can be triggered by a
control module or relay module)
NAC with no synchronization
NAC1
ELR for
FACP
NAC