Battery Mhos Chart

~72°F Environment

~62°F Environment

~52°F Environment

~42°F Environment

Ideal Conditions

-8% Degrade

-13% Degrade

-18% Degrade

Ah. Size

Bad

Weak

Good

Best

Bad

Weak

Good

Best

Bad

Weak

Good

Best

Bad

Weak

Good

Best

.8

0-19

20-21

22-24

25+

0-17

18-20

21-22

23+

0-16

17-18

19-21

22+

0-15

16-17

18-20

21+

1.3

0-24

25-28

29-31

32+

0-22

23-25

26-29

30+

0-21

22-24

25-27

28+

0-20

21-23

24-26

27+

2.3

0-40

41-45

46-51

52+

0-36

37-42

43-47

48+

0-34

35-39

40-44

45+

0-32

33-37

38-42

43+

2.6

0-44

45-50

51-57

58+

0-40

41-46

47-52

53+

0-38

39-44

45-49

50+

0-36

37-41

42-46

47+

3.0

0-48

49-55

56-62

63+

0-44

45-51

52-57

56+

0-42

43-48

49-54

55+

0-39

40-45

46-51

52+

3.3

0-49

50-57

58-64

65+

0-45

46-52

53-59

60+

0-43

44-49

50-55

56+

0-40

41-46

47-52

53+

4.0

0-64

65-73

74-83

84+

0-59

60-67

68-76

77+

0-56

57-64

65-72

73+

0-52

53-60

61-68

69+

4.5

0-73

74-83

84-94

95+

0-67

68-76

77-86

87+

0-63

64-72

73-81

82+

0-59

60-68

69-76

77+

5.0

0-76

77-87

88-98

99+

0-70

71-80

81-90

91+

0-66

67-76

77-85

86+

0-62

63-71

72-80

81+

7.0

0-139

140-159 160-179

180+

0-128

129-146 147-165

166+

0-121

122-138 139-156

157+

0-114

115-130 131-147

148+

7.5

0-153

154-175 176-197

198+

0-141

142-161 162-181

182+

0-133

134-152 153-171

172+

0-125

126-143 144-161

152+

8.0

0-157

158-179 180-202

203+

0-144

145-165 166-185

186+

0-136

137-156 157-175

176+

0-128

129-147 148-165

166+

10.0

0-185

186-211 212-238

239+

0-170

171-194 195-218

219+

0-160

161-183 184-206

207+

0-151

152-173 174-195

196+

12.0

0-192

193-219 220-241

248+

0-176

177-201 202-227

228+

0-166

167-190 191-214

215+

0-157

158-179 180-202

203+

17.0

0-265

266-303 304-341

342+

0-244

245-279 280-314

315+

0-230

231-263 264-297

298+

0-217

218-248 249-279

280+

18.0

0-279

280-319 320-359

360+

0-257

258-293 294-330

331+

0-243

244-277 278-312

313+

0-229

230-261 262-294

295+

24.0

0-321

322-367 368-413

414+

0-295

296-338 339-380

381+

0-279

280-319 320-359

360+

0-263

264-301 302-338

339+

25.0

0-328

329-375 376-422

423+

0-302

303-345 346-388

389+

0-285

286-326 327-367

368+

0-289

270-307 308-346

347+

26.0

0-335

336-386 384-431

432+

0-308

309-352 353-396

397+

0-291

292-333 334-375

376+

0-275

276-314 315-353

354+

Bad

Replace immediately.

Weak

Nearing end of life; replace soon.

Good

Adequate standby power.

Best

Battery is fresh and well charged

Honeywell is not responsible for misprints or errors.  These Mhos values are benchmark averages created from fresh samples of major brand batteries.  If you find consistent, minor variations in readings from multiple 
samples of a battery, it is likely due to manufacturing differences.  However, if the readings are excessively low, the battery is not as good as the benchmark average.  If this chart does not include the battery you are 
testing, it may be necessary to generate the values using the procedure listed above.

Summary of Contents for HPBLT

Page 1: ...4 W x 3 H x 1 15 D w o carrying case 4 Installation Instructions 1 Disconnect the battery from its equipment 2 Connect the BLACK test clip to the Negative battery terminal and the RED to the Positive terminal For accurate readings the test clips must be tightly clipped directly to the battery posts not to the battery bolts Err or a blank screen indicates that battery voltage is too low for testing...

Page 2: ...e current the battery can deliver Therefore a new 7 amp hour battery will have a higher Mhos value than a new 4 amp hour battery of similar construction 6 Temperature Effects on a Battery Generally speaking temperatures below 72 F tend to slow down a battery s internal activity causing a significant decrease in the Mhos conductivity reading as the temperature falls Cool temperatures not below free...

Page 3: ...y before a system failure 9 Using Mhos to Estimate Battery Life For standby batteries peak capacity is normally reached after about three months on a float charging system For cyclic use batteries full capacity may not be reached until after ten to thirty cycles If a new battery has been in storage for an extended period say over six months without being charges plate oxidation from self discharge...

Page 4: ... 134 152 153 171 172 0 125 126 143 144 161 152 8 0 0 157 158 179 180 202 203 0 144 145 165 166 185 186 0 136 137 156 157 175 176 0 128 129 147 148 165 166 10 0 0 185 186 211 212 238 239 0 170 171 194 195 218 219 0 160 161 183 184 206 207 0 151 152 173 174 195 196 12 0 0 192 193 219 220 241 248 0 176 177 201 202 227 228 0 166 167 190 191 214 215 0 157 158 179 180 202 203 17 0 0 265 266 303 304 341 ...

Reviews: