background image

• HP24100ULWP   • HP28100ULWP

Weatherproof Power Supplies

PN 53434:A 9/9/08 ECN 08-093

Honeywell
12 Clintonville Road 
Northford, CT 06472-1610
http://www.honeywellpower.com

Product Installation Document

1 Overview

The HP24100ULWP and HP28100ULWP are weatherproof power supplies that provide power for access control, security 
and CCTV applications that require outdoor installation.  The HP24100ULWP provides a non-power limited output of 
24VAC at a maximum of 4.0A.  The HP28100ULWP provides a non-power limited output of 28VAC @ 3.6A.  Each unit 
consists of a thermally-fused transformer and an electrically-fused  primary input in a NEMA 4X IP66 weatherproof 
enclosure.

2 Features

NEMA 4X weatherproof enclosure with included hardware.

Input AC terminal block with fuse protection.

Thermally-fused transformer.

Designed for quick installation.

3 Specifications

UL Listed to UL Standard UL 2044 Commercial CCTV Equipment.

Input:
– HP24100ULWP:  115VAC, 60Hz, 1.0 A
– HP28100ULWP:  115VAC, 60Hz, 1.0 A

Output:
– HP24100ULWP:  4.0A @ 24VAC (100VA)
– HP28100ULWP:  3.6A @ 24VAC (100VA)

Overload Protection:
– Terminal Block Fuse; 3A. 250V, 5 x 20mm cartridge

Maximum Temperature Range:  32°F to 120°F (0°C to 49°C)

Enclosure Dimensions:  12.5”H x 11.5”W x 7.5”D (cm: 31.75H x 29.21W x 19.05D)

4 Installation Instructions

1. Unpack product.  Do not discard packing materials until installation and checkout are successfully completed.
2. Pre-drill holes where enclosure is to be mounted.  Choose a vertical surface, strong enough to support the full weight 

of the assembly.  Not the added dimensions of the required mounting brackets.

3. Secure enclosure to the desire location using the supplied hardware.
4. Use a knockout punch, standard hole saw, or other means to punch holes for the incoming AC power and low voltage 

wiring.  AC mains and low voltage wiring must be wired separately using weatherproof conduit or suitable outdoor 
wiring.

5. Disconnect AC mains power to the branch circuit where the product will be connected.
6. Route AC field wiring to power supply in weatherproof conduit or use other suitable outdoor wiring.
7. Connect AC mains wiring (115V, 60Hz) to the terminal block while maintaining a 1/4” separation between AC mains 

and low voltage wiring as shown (see Figure 1).
– Hot (black) to terminal marked “L”
– Neutral (white) to terminal marked “N”