Honeywell HEAT PUMP THERMOSTAT T8411R Manual Download Page 8

T8411R ELECTRONIC HEAT PUMP THERMOSTAT

68-0185—2

8

Sequence of Operations

The Fan, Heat and Cool outputs are relay controlled. A loss of 
ac power, or a change in the SYSTEM switch setting can 

cause the outputs to turn off. Table 1 shows the sequence of 

operations for the Fan settings and System modes. 

Fan Control

The FAN switch settings are On and Auto.

On:The fan runs continuously.

Auto:The fan starts and stops with the equipment.

Heat Mode

With the SYSTEM switch in the Heat position, the thermostat 

controls the heating system. On a call for heat, the W and G 
terminals are energized and a flame is shown on the digital 

display. The B terminal is powered continuously while system 

switch is in Heat.

Cool Mode

With the SYSTEM switch in the Cool position, the thermostat 

controls the cooling system. On a call for cool, the G and Y 

terminals are energized and a snowflake is shown on the 
digital display. The O terminal is powered continuously while 

system switch is in Cool.

Em. Ht. Mode

With the system switch at Em. Ht., the thermostat controls 

Em. Ht. On a call for emergency heat, the E, G and L 
terminals are energized and an indicator is displayed on the 

LDD. The L terminal is powered continuously while system 

switch is in Em. Ht. In severe weather, the W2 terminal can 
also energize.

Minimum Off-Timing 

A minimum off-timer in the T8411R assures that the compressor does 

not come on again for at least five minutes after it turns off. The 

minimum-off timer is triggered when the compressor turns off.

 If the 

compressor turns off when the setpoint is changed, then the 

minimum-off timer is triggered. Power interruption and power 

restoration also trigger the minimum off-timer which operates 
on the first stage of heating and cooling.

Table 1. Sequence of Operations.

a

The O terminal is powered continuously in cooling, the B terminal is powered continuously in heating and the L terminal is 

powered continuously in emergency heat as a function of the system switch position even without a call for heat or cool.

CHECKOUT

Heating

1.

Slide the SYSTEM switch to Heat and the FAN switch to 

Auto.

2.

Press and hold the s key to raise the temperature set-
ting several degrees above the room temperature. After 

approximately five minutes the W1 and G terminals are 

energized and the heating equipment starts.

3.

Press the 

 key to lower the temperature setting below 

the room temperature. Heating equipment should stop.

Cooling

CAUTION

Compressor Damage Hazard

Operating at too low of an outdoor temperature 

can cause compressor damage.

Do not operate cooling if outdoor temperature is below 

50°F (10°C). Refer to manufacturer recommendations. 

Allow the compressor to remain off for five minutes 
before restarting.

1.

Slide the SYSTEM switch to Cool and the FAN switch to 

Auto.

2.

Press the 

 key to lower the temperature setting sev-

eral degrees below the room temperature. After approx-

imately five minutes the G and Y terminals are 
energized and the cooling equipment starts.

3.

Press the 

 key to raise the temperature setting above 

the room temperature. Cooling system should shut 
down.

Fan

1.

Slide the SYSTEM switch to Off and the FAN switch to 

On. The fan should run continuously.

2.

Slide the FAN switch to Auto. The system turns the fan 

on or off with the equipment.

Make certain all equipment responds properly to the 

thermostat.

FAN Switch Settings SYSTEM Switch Settings Call for Action Energize Terminals

Display Icons

Auto

Cool

None

O

None

Cooling

O, Y, G

Heat

None

B

None

Stage 1 heat

B, W1, G

Stage 2 heat

B, W1, W2, G

, Aux Ht indicator

Em Ht

None

L

Em Ht indicator

Stage 1 heat

L, E, G

, Em Ht indicator

Stage 2 heat

L, E, W2, G

, Em Ht and Aux Ht indicators

Summary of Contents for HEAT PUMP THERMOSTAT T8411R

Page 1: ...in a variety of locations Keys are located by the display for easy access Fan and system switches are located on the lower edge to eliminate accidental setting changes Easy installation setup and self test saves installer time and increases their productivity Manual changeover from heat to cool eliminates unexpected system operation F or C temperature display for added model flexibility Selectable...

Page 2: ...1R TRADELINE model includes a thermostat wallplate for wiring and mounting thermostat and owner s guide Power T8411R 24 Vac nominal 18 to 30 Vac 50 60 Hz Electrical Ratings First Stage Heating 0 02 to 1 5A run 7 5A inrush Second Stage Heating 0 02 to 1 5A run 3 5A inrush Cooling 0 02 to 1 5A run 7 5A inrush Fan 0 02 to 0 5A run 2 5A inrush Emergency Heat Output E 0 02 to 1 5A run 3 5A inrush Heati...

Page 3: ...on Install the thermostat about 5 ft 1 5m above the floor in an area with good air circulation at average room temperature See Fig 2 Do not install the thermostat where it can be affected by drafts or dead spots behind doors and in corners hot or cold air from ducts radiant heat from the sun or appliances concealed pipes and chimneys unheated uncooled areas such as an outside wall behind the therm...

Page 4: ...ate and con nect the system wires See Fig 4 2 Securely tighten each terminal screw 3 Push the excess wire back into the hole 4 Plug the hole with nonflammable insulation to prevent drafts from affecting the thermostat Mounting Thermostat to Wallplate 1 Engage the tabs at the top of the thermostat and wall plate 2 Swing down the thermostat and press the lower edge of the thermostat onto the wallpla...

Page 5: ... TERMINALS SYSTEM SWITCH HEAT OFF COOL R W2 L B O Y EM HT W1 E AUXILARY HEAT RELAY CHANGEOVER VALVE HEAT CHANGEOVER VALVE COOL COMPRESSOR CONTACTOR COMPRESSOR CONTACTOR HEAT FAN RELAY RELAY EMERGENCY HEAT RELAY G C THERMOSTAT LOGIC THERMISTOR SENSOR POWER SUPPLY ON AUTO STAGE 2 RELAY STAGE 1 RELAY FAN SWITCH M11333A 3 3 M18577 SYSTEM Cool Off Heat Em Ht Auto On FAN DASHED LINES INDICATE TABS ON BA...

Page 6: ...heating load Set Temperature Setpoint NOTE Temperature setpoint range is 40 to 99 F 4 to 39 C The temperature setpoint and the room temperature are shown separately on the display The indicator points to Set when the temperature setpoint is displayed and to Room when the room temperature is displayed To set temperature setpoint 1 Select Heat or Cool by sliding the SYSTEM switch in the lower right ...

Page 7: ... displayed A typical example is shown but CC varies by model This informa tion is for factory use only 10 Press to save all changes exit installer setup mode and return to normal operation NOTE After exiting installer setup mode change the set point to the desired room temperature OPERATION The T8411R Thermostat provides two stage heat and one stage cool temperature control with proportional plus ...

Page 8: ...ting and cooling Table 1 Sequence of Operations a The O terminal is powered continuously in cooling the B terminal is powered continuously in heating and the L terminal is powered continuously in emergency heat as a function of the system switch position even without a call for heat or cool CHECKOUT Heating 1 Slide the SYSTEM switch to Heat and the FAN switch to Auto 2 Press and hold the s key to ...

Page 9: ... THERMOSTAT PARTIAL DISPLAY INOPERATIVE THERMOSTAT SEE THE SETTINGS AND ADJUSTMENTS SECTION FOR INSTRUCTIONS ON INSTALLER SETUP MODE STILL IN INSTALLER SETUP MODE RECONFIGURE THE DISPLAY SEE SETTINGS AND ADJUSTMENTS SECTION TEMPERATURE DISPLAY IS INCORRECT THERMOSTAT IS CONFIGURED FOR F OR C DISPLAY CHECK THAT C TERMINAL IS CONNECTED TO THE SYSTEM TRANSFORMER CHECK POWER TO HEATING AND COOLING EQU...

Page 10: ...68 0185 2 10 ...

Page 11: ...11 68 0185 2 ...

Page 12: ...ilding Control Home and Building Control Honeywell Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 Printed in U S A on recycled paper containing at least 10 post consumer paper fibers ...

Reviews: