Revision 6
HC900 Process & Safety Controller User and Installation Manual
229
21 April 2017
Analog Input/Digital Input/Digital Output/Analog Output
A single DI/DO/AO-RTP and cable is used with the following modules:
See page
4-point Analog Output
16-point Contact Digital Input
16-point DC Digital Input
16-point AC Digital Input
16-point DC Digital Output
8-point AC Digital Output
8-point Analog Output
Dual DI/DO/AO-RTPs and cables are used with the following modules:
See page
16-point Analog Output
16-point Analog Input
32-Point DC Digital Output
32-Point DC Digital Input
4 Point Analog Output
Step
Action
1
ATTENTION: RTP and cables are intended for permanent installation within their own enclosure.
Mount RTP cable assembly to HC900 Controller
Remove appropriate key tabs from terminal block to allow mating with the module. See page 85.
Connect desired cable to AO module at controller. Choose from:
900RTC-L010
Remote Terminal Low Voltage Cable Assembly, 1.0 meters long
900RTC-L025
Remote Terminal Low Voltage Cable Assembly, 2.5 meters long
900RTC-L050
Remote Terminal Low Voltage Cable Assembly, 5.0 meters long
Install AO module label onto the module connector cover.
Connect shield drain wire to the grounding bars at the base of the HC900 rack. All field-wiring
shields must be grounded as described in the shield grounding section (page 81).
2
Mount RTP to DIN rail.
Latch to rail. See page 253.
Connect cable to RTP