Revision 6
HC900 Process & Safety Controller User and Installation Manual
245
21 April 2017
16 Point Analog Output
Step
Action
4
Connect field wiring.
RTP A for
Outputs 1 to 8, 9+ and 10+
RTP B for
Outputs 11 to 16, 9- and 10-)
1
2
3
4
5
6
7
8
9 10 11 12 13 14 15 16 17 18 19 20
21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40
LOADS ARE 0 to 750 ohm
A
O1
+
A
O1
-
A
O2
+
A
O2
-
L
OA
D
AO
-1
L
OA
D
AO
-2
L
OA
D
AO
-1
L
OA
D
AO
-2
A
O3
+
A
O3
-
A
O4
+
A
O4
-
A
O5
+
A
O5
-
A
O6
+
A
O6
-
A
O7
+
A
O7
-
A
O8
+
A
O8
-
ETC.
1
2
3
4
5
6
7
8
9 10 11 12 13 14 15 16 17 18 19 20
21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40
A
O9
-
A
O1
1
+
A
O1
0
-
A
O1
2
+
A
O1
1
-
A
O1
3
+
A
O1
2
-
A
O1
4
+
A
O1
3
-
A
O1
5
+
A
O1
4
-
A
O1
6
+
A
O1
5
-
A
O1
6
-
External 24VDC supply
DC+ SDC
+
EXT 24V RTN
EXT +24V
A
O1
0
+
A
O9
+
Install 24V wires as shown:
22 to 10
22 to 12
24VRTN to 9
24VRTN to 11
16 Point Analog Input
Step
Action
1
ATTENTION: RTP and cables are intended for permanent installation within their own enclosure.
ATTENTION: The RTP
labeled “DI, DO, AO RTP ASSY” with jumpers J2-J9 is the correct one for 16
point AI.
Mount RTP cable assembly to HC900 Controller
Remove appropriate key tabs from terminal board to allow mating with the module. See page 85.
Connect terminal block end of desired cable assembly to 16 point Analog Input module at controller.
Choose from:
900RTC-3210
Remote Terminal Cable assembly, 1.0 meters long
900RTC-3225
Remote Terminal Cable assembly, 2.5 meters long
Install 16 point Analog Input label into the module connector cover.
Connect both shield drain wires to the grounding bars at the base of the HC900 rack. All field-wiring
shields must be grounded as described in the shield grounding section (page 81).