1.1.2 Bar Graphs Screen
The HA71 Bar Graphs screen shown in Figure 1-3 allows all active
channels to be viewed simultaneously. Both engineering units values
and bar graph values are indicated
in real time. Lines across the bars
indicate the alarm trip points making
it easy to identify channels at or near
alarm. A feature in the Systems menu
tree allows new alarms to always
force the LCD to the bar graphs
screen. This is useful for applications
requiring channels with alarms to be
displayed.
1.1.3 Combination Screen
The HA71 Combination screen shown in Figure 1-4 offers a view of a
single channel but displays the data as a 10 minute trend, bar graph
and large engineering units. It is also useful for testing inputs for
stability since MAX, MIN and AVERAGE values refresh each time this
screen is selected. For example, to
test stability over a one hour period for
an input, begin timing as soon as the
channel is selected. One hour later
record the MAX, MIN and AVERAGE
values. The difference between MAX
and MIN indicates peak to peak
excursions over the one hour period
and AVERAGE is the average for the
hour. Longer or shorter tests may
also be run. The numeric value shown below the bar-graph indicates
number of minutes samples have been taken. After 999 minutes the
AVERAGE buffer overflows and the error message UPDATE appears
in the AVERAGE field. Exiting this screen resets the buffer and clears
the error message.
1.2 Specifications
1.2.1 DC Power Supply Requirements
Standard HA71 power requirements are 10-30VDC @ 3 watts applied
to terminals 9 & 11 of TB2 on the standard I/O PCB (see
Section 3.0
).
Optional features increase power consumption as described below:
Discrete Relay PCB option; add 2 watts per PCB.
•
Analog Input PCB option; add 1/2 watt.
•
4-20mA Output PCB option; add 1 watt.
•
Catalytic Bead Sensor Input option; add 12 watts max (depends
•
upon sensor power).
TB2 terminals 10 & 12 of the standard I/O PCB provide a
•
maximum of 500mA fused output power for powering of auxiliary
external devices such as relays, lamps or transmitters. Power
consumed from these terminals should be considered when
calculating system power consumption.
1.2.2 150 Watt AC – 24VDC Power Supply
110-120 VAC @3.2A max
•
220-240VAC @ 1.6A max
•
A slide switch on the front of the power supply selects AC input
•
range.
The 10-0172 150 watt power supply (
Section 3.1.9
) is for powering
the HA71 and up to 16 detectors. A minimum of 5 watts per channel
is available for powering of external transmitters.
HA71 Digital Gas Controller
Ch01
Ch02
Ch03
Ch04
Ch05
Ch06
Ch07
Ch08
0 PCTLEL
10 PCTLEL
0 PCTLEL
50 PCTLEL
0 PCTLEL
0 PCTLEL
0 PCTLEL
0 PCTLEL
1
2
3
4
5
6
7
8
Figure 1-3. Bar Graphs Screen
HA71 Digital Gas Controller
10 MINUTES
Ch02 Measurement Name
01117 COUNTS
MAX
MIN
AVG
SPAN
ZERO
%FS
03
PCTLEL
10
0
3
100
0
Figure 1-4. Combination Screen
Summary of Contents for HA71
Page 5: ...HA71 Digital Gas Controller Revision 3 04 08 HA71 Technical Manual 1 1 1 General Description ...
Page 9: ...HA71 Digital Gas Controller Revision 3 04 08 HA71 Technical Manual 2 1 2 Basic Operation ...
Page 31: ...HA71 Digital Gas Controller Revision 3 04 08 HA71 Technical Manual 4 1 4 System Diagnostics ...
Page 34: ...HA71 Digital Gas Controller Revision 3 04 08 HA71 Technical Manual 5 1 5 Modbus RS 485 Ports ...
Page 42: ...HA71 Digital Gas Controllers Revision 3 04 08 HA71 Technical Manual 6 1 6 HA71 Enclosures ...
Page 49: ...HA71 Digital Gas Controller Revision 3 04 08 HA71 Technical Manual A 1 A Ordering Information ...
Page 52: ...HA71 Digital Gas Controller Revision 3 04 08 HA71 Technical Manual B 1 B Warranty ...