HA71 Digital Gas Controller
Revision 3 (04/08)
HA71 Technical Manual
3-9
3.1.7 Optional Clock/Printer Interface Board
When equipped with the Clock / Printer Interface option, shown in
Figure 3-8, the HA71 Controller is capable of automatically printing time
& date stamped alarm events to a 24 PIN dot matrix printer such as
the Panasonic KX-P1131. The cable interface between the HA71 and
the KX-P1131 may be either parallel or serial. Parallel interfaces only
allow 6 feet of separation while the RS-232 serial interface allows up to
50 feet. Distances up to 4000 feet may be obtained using the 10-0229
printer interface option’s RS-422 port but requires an additional tri-port
RS-422 / RS-232 converter at the printer end of the cable.
The 10-0229 Printer Interface may also be connected to a PC running
HyperTerminal or other communications software as an alternative to
hard copy printing of the data. Printer/PC cable schematics are shown
in Figure 3-7. Printer settings for serial interfaces are 9600 baud, 8
data bits, no parity and one stop bit. Communications software settings
are 9600 baud, 8 data bits, no parity, one stop bit and FlowControl
= Hardware. Printer diagnostic red LED’s indicate printer faults such
as out of paper, overflowed buffer or loss of communications. Green
LED’s flicker to confirm good communications between the HA71 and
printer during print attempts.
Examples of printed alarm events are shown below. The format of each
event, from left to right, is DATE, TIME, 16 character ASCII channel
ID from the HA71, HA71 channel #, alarm #, IN or OUT status. A
buffer in the HA71 retains the most recent 30 – 35 printed events.
It is possible to dump the entire buffer to the printer from the menu
shown in
Figure 3-9
. This is useful if printer problems have occurred
causing missed printouts.
05/22/03
08:21:00
Storage Tank 103
Chnl 1
Alarm 2
IN
05/22/03
08:21:01
Storage Tank 103
Chnl 1
Alarm 2
OUT
05/22/03
09:12:01
Storage Tank 103
Chnl 13
Alarm 1
IN
05/22/03
09:13:00
Fuel A Flow
Chnl 9
Alarm 1
IN
05/22/03
09:13:05
Storage Tank 103
Chnl 1
FAULT
IN
05/22/03
09:13:05
Fuel Dock
Chnl 2
FAULT
IN
05/22/03
09:40:10
Storage Tank 103
Chnl 13
Alarm 2
IN
05/22/03
09:40:14
Fuel Dock
Chnl 2
FAULT
OUT
05/22/03
09:40:14
Trans Pump 103
Chnl 3
FAULT
OUT
05/22/03
09:40:14
Storage Tank 103
Chnl 1
FAULT
OUT
05/22/03
11:53:37
Fuel A Flow
Chnl 9
Alarm 1
OUT
Figure 3-8. Printer Interface Option 10-0229
Summary of Contents for HA71
Page 5: ...HA71 Digital Gas Controller Revision 3 04 08 HA71 Technical Manual 1 1 1 General Description ...
Page 9: ...HA71 Digital Gas Controller Revision 3 04 08 HA71 Technical Manual 2 1 2 Basic Operation ...
Page 31: ...HA71 Digital Gas Controller Revision 3 04 08 HA71 Technical Manual 4 1 4 System Diagnostics ...
Page 34: ...HA71 Digital Gas Controller Revision 3 04 08 HA71 Technical Manual 5 1 5 Modbus RS 485 Ports ...
Page 42: ...HA71 Digital Gas Controllers Revision 3 04 08 HA71 Technical Manual 6 1 6 HA71 Enclosures ...
Page 49: ...HA71 Digital Gas Controller Revision 3 04 08 HA71 Technical Manual A 1 A Ordering Information ...
Page 52: ...HA71 Digital Gas Controller Revision 3 04 08 HA71 Technical Manual B 1 B Warranty ...