Zone I/P

"

The Zone I/P is only applicable for Channel 1.

This option sets the channel to accept the connection of conventional fire detectors and manual call points.

Confirmation O/P

This option sets two channels, one as an input and another as a confirmation output. This facility allows
external equipment to monitor the fire alarm system.

The confirmation output will operate within 1s of the input being accepted (design must also allow for any
input delay settings).

4188-873.02_Pt.2_04/07_DRAFT6_S4 LV Interfaces

3

Interfaces (Low voltage)

Commissioning information

The associated

channel cannot be the same

channel as the

channel.

Input

Confirmation O/P

8

7

6

5

Ch. 2

Ch. 2 Confirmation Output

External
equipment

Ch. 1 Input

Ch. 1

4-I/O Interface
module

External equipment monitors the
fire alarm system

A duration after

which the input is accepted.

Extendable reset duration with a

default value of 2s plus this value.

Summary of Contents for GENT S4-34410

Page 1: ...4 interface modules can be mounted in other equipment housings using the DIN rail mount brackets S4 34491 A module can also be fitted into a plastic box S4 34490 or metal box S4 34492 The boxes have cable termination points on the enclosure for incoming cables 4188 873_issue 4_Pt 1_02 09_S4 LV Interfaces 1 Data and Installation Interface Modules for Vigilon Low voltage LV Input Output by Honeywell...

Page 2: ...odule can be configured to provide any combination of up to four inputs or outputs An output of either normally open or normally closed relay contacts can be used to control a load of up to 1A 30Vdc ac Optionally an output can be configured to provide 1 5mA at 24V dc to drive an LED that can be normally On or normally Off An input can be programmed as a fire fault supervisory or confirmation input...

Page 3: ...inimum with End of line capacitor Can be configured as LED output The cable screens must be connected to an on the chassis or in the metal box If a module is mounted on a then the DIN rail must electrically connected to the earth terminal DIN rail loop cable screen via the earth terminal EOL 10K 10K 121110 9 8 7 6 5 4 3 2 1 Confirmation Input Optional NC COM NO Output Relay contact rating 1A 30V a...

Page 4: ...nfirmation input is not seen within predefined period of the output action Confirmation function is not a feature of the single input module Output mode A relay output of either NO or NC set of contacts rated 1A 30Vac dc resistive load A relay output of change over contacts NC COM and NO rated 1A 30Vac dc resistive load LED output 1 5mA at 24Vdc Normally On or Normally Off Load Factor 1 4 switch i...

Page 5: ...ck the LV icon on the tool bar 2 Select the required interface to be configured from the list box 3 Ensure the Number of keyswitches option is set to 0 because this feature is for future use Ensure only the applicable channel is configured when configuring the S4 34415 or S4 34420 type interfaces 4 Select a mode from the drop down menu All applicable channels must be set see next page for details ...

Page 6: ...ctive for a set period of time Settings for Supervisory Fault and Fire inputs are similar Fault I P This option sets the channel as a fault input The acceptance of the input signal can be delayed until it has remained active for a set period of time Fire I P This option sets the channel as a fire input The acceptance of the input signal can be delayed until it has remained active for a set period ...

Page 7: ...output will operate within 1s of the input being accepted design must also allow for any input delay settings 4188 873 02_Pt 2_04 07_DRAFT6_S4 LV Interfaces 3 Interfaces Low voltage Commissioning information The associated channel cannot be the same channel as the channel Input Confirmation O P 8 7 6 5 Ch 2 Ch 2 Confirmation Output External equipment Ch 1 Input Ch 1 4 I O Interface module External...

Page 8: ...allows the fire alarm system to monitor external equipment Keyswitch mode This feature is a future option Commissioning information Interfaces Low voltage Gent by Honeywell reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions of changes Hamilton Industrial Park Waterside Road Leicester LE5 1...

Reviews: