Honeywell GENT S4-34410 Data And Installation Download Page 4

At the end of their useful life, the packaging,
product and batteries should be disposed of
via a suitable recycling centre and in
accordance with national or local legislation.

Technical data

S4-34410

S4 1- Input

S4-34450

S4 4-Input /Output

S4-34420

S4 1-Output & 1-Input

Approval

EN54-17:2005 and EN54-18:2005

Weight-dimen. module

module in plastic box

module in metal box

92g

j

1047g

k

782g

ƒ

100g

j

1055g

k

790g

ƒ

100g

j

1055g

k

790g

ƒ

Storage temperature

-30ºC to 70ºC

Operating temperature

-10ºC to 60ºC

Relative Humidity

Up to 95% - Temperature 5ºC to 45°C (Non condensing)

Emission

BS EN 61000-6-3:2001 Residential, Commercial & Light Industry

Class B limits

Immunity

BS EN50130-4: 1996: Part 4

LVD

BS EN 60950-2002

Ingress Protection

IP31 for plastic box S4-34490 & IP40 estimated for metal box S4-34492

Colour

Module-white / Plastic box-dark grey (Lid-light grey) / Metal box-dark grey

Input mode

Input channel-1 only can be configured as a
zone input to accept conventional devices, with
a load of 2mA quiescent and 9mA alarm
maximum at 24V nominal (18V minimum). With
configurable 2s to 5s reset period and 5s to 40s
alarm validation delay.

Switch input can work
with or without a delay.

Input channel can be configured as a

switch input

of Fire*, Fault*, Supervisory*

(non fire) or Confirmation# signal.

* with input acceptance delay of up to 10

seconds for a Fire input and up to 300s for Fault or Supervisory input. # A fault is
generated if confirmation input is not seen within predefined period of the output
action (Confirmation function is not a feature of the single input module).

Output mode

-

A relay output of either NO or
NC set of contacts rated 1A -
30Vac/dc resistive load.

A relay output of change over
contacts NC, COM and NO rated
1A - 30Vac/dc resistive load.

LED output

1.5mA at 24Vdc (Normally On or Normally Off)

Load Factor

1-4 switch inputs =

1

(maximum 200 per loop)

1-4 relay outputs =

2

(maximum 200 per loop only 8 individually sectored)

Zone Input =

26

(maximum 30 per loop)

Every LED output =

+5

(maximum 100 LED outputs per loop)

EN54-17 data

V

max

V

nom

V

min

VSO max

V

SO min

I

C max

I

S max

I

L max

ZC

max

42V

40V

24V

14V

10V

0.4A

1A

20µA

0.1O

W

Panel compatibility

Fully compatible with LPC = V3.93 / V4.35 & MCC/MCB = V3.94 / V4.37.

For further information on upgrade requirements contact Gent by Honeywell

Data and Installation

Interfaces (Low voltage)

Gent by Honeywell reserves the right to revise this publication from time to time and make changes to the content hereof without
obligation to notify any person of such revisions of changes.

Hamilton Industrial Park, Waterside Road, Leicester LE5 1TN, UK

Website: www.gent.co.uk

Telephone: +44 (0) 116 246 2000

Fax (UK): +44 (0)116 246 2300

4

4188-873_issue 4_Pt.1_02/09_S4 LV Interfaces

by Honeywell

Do not dispose of with your normal household waste.
Do not burn.

WEEE Directive:

At the end of their useful life, the packaging,
product and batteries should be
disposed of via a suitable recycling centre.

90mm

93mm

23mm

227mm

245mm

Depth 77mm

Healthy

Fault

Fault

System fault

green

amber

202mm

125mm

Depth 50mm

Metal Box

Plastic Box

Summary of Contents for GENT S4-34410

Page 1: ...4 interface modules can be mounted in other equipment housings using the DIN rail mount brackets S4 34491 A module can also be fitted into a plastic box S4 34490 or metal box S4 34492 The boxes have cable termination points on the enclosure for incoming cables 4188 873_issue 4_Pt 1_02 09_S4 LV Interfaces 1 Data and Installation Interface Modules for Vigilon Low voltage LV Input Output by Honeywell...

Page 2: ...odule can be configured to provide any combination of up to four inputs or outputs An output of either normally open or normally closed relay contacts can be used to control a load of up to 1A 30Vdc ac Optionally an output can be configured to provide 1 5mA at 24V dc to drive an LED that can be normally On or normally Off An input can be programmed as a fire fault supervisory or confirmation input...

Page 3: ...inimum with End of line capacitor Can be configured as LED output The cable screens must be connected to an on the chassis or in the metal box If a module is mounted on a then the DIN rail must electrically connected to the earth terminal DIN rail loop cable screen via the earth terminal EOL 10K 10K 121110 9 8 7 6 5 4 3 2 1 Confirmation Input Optional NC COM NO Output Relay contact rating 1A 30V a...

Page 4: ...nfirmation input is not seen within predefined period of the output action Confirmation function is not a feature of the single input module Output mode A relay output of either NO or NC set of contacts rated 1A 30Vac dc resistive load A relay output of change over contacts NC COM and NO rated 1A 30Vac dc resistive load LED output 1 5mA at 24Vdc Normally On or Normally Off Load Factor 1 4 switch i...

Page 5: ...ck the LV icon on the tool bar 2 Select the required interface to be configured from the list box 3 Ensure the Number of keyswitches option is set to 0 because this feature is for future use Ensure only the applicable channel is configured when configuring the S4 34415 or S4 34420 type interfaces 4 Select a mode from the drop down menu All applicable channels must be set see next page for details ...

Page 6: ...ctive for a set period of time Settings for Supervisory Fault and Fire inputs are similar Fault I P This option sets the channel as a fault input The acceptance of the input signal can be delayed until it has remained active for a set period of time Fire I P This option sets the channel as a fire input The acceptance of the input signal can be delayed until it has remained active for a set period ...

Page 7: ...output will operate within 1s of the input being accepted design must also allow for any input delay settings 4188 873 02_Pt 2_04 07_DRAFT6_S4 LV Interfaces 3 Interfaces Low voltage Commissioning information The associated channel cannot be the same channel as the channel Input Confirmation O P 8 7 6 5 Ch 2 Ch 2 Confirmation Output External equipment Ch 1 Input Ch 1 4 I O Interface module External...

Page 8: ...allows the fire alarm system to monitor external equipment Keyswitch mode This feature is a future option Commissioning information Interfaces Low voltage Gent by Honeywell reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions of changes Hamilton Industrial Park Waterside Road Leicester LE5 1...

Reviews: