background image

Audio Pack 1

The micro-DAU will have Audio Pack 0 fitted as standard from September 2010 onwards and pre September
2010 (legacy) Audio Pack 1 as standard. The Audio Pack 1 has the following messages for No.: 2, 3, 5, 6
and 13 in place of the ones stated for Audio pack 0 in the previous table.

No.

Type of message

Voice

Message

2

Alert

(default - Emergency 1)

Female

Your attention please, the fire alarm has been activated in another
area, please remain where you are and await further instructions.

3

Evacuate

(default - Emergency 2)

Male

Attention please, attention please, this is an emergency, please leave
the building by the nearest available exit. Do not use the lifts or
escalator.

5

Alert
(alternative)

Female

May I have your attention please, may I have your attention please,
an incident has been reported in the building, whilst this report is
being investigated, please remain at your workplace.

6

Evacuate
(alternative)

Male

Ladies and gentlemen, due to unforeseen circumstances we are
required to evacuate the building, please leave the building
immediately by the nearest available exit.

13#

Gent Limited
advertisement

Female

Ladies and gentlemen this speech message is produced by Gent
Limited's Vigilon Compact Voice Alarm system. This product
integrates voice alarm functions into an analogue fire alarm system
ideal for small to medium sized buildings.

"

If there is a mix of legacy and post September 2010 Vigilon Compact VA panel, Mains Powered DAU and

micro DAUs in the system then consideration must be given to ensure correct messages are programmed during
commissioning of the system. The best solution to avoid confusion is to ensure Audio Packs are consistent throughout
the system.

4188-781 issue 6_Part 2_ 08/10_micro DAU commission

3

micro Distributed Amplifier Unit

Commissioning information

Summary of Contents for GENT COMPACT-DAU

Page 1: ... powered by the control panel via a loop circuit The micro DAU is supplied in two assemblies Backbox with front cover micro DAU PCB assembly Parts in the spares pack Quantity Allen key 1 M4 Socket head screw for door 2 Cable entry bungs 3 Screw PCB fixing 1 Washer use with PCB fixing screw 1 Open the outer door using the allen key Backbox Flush fixing the micro DAU The micro DAU can be flush fixed...

Page 2: ...to time and make changes to the content hereof without obligation to notify any person of such revisions of changes Hamilton Industrial Park Waterside Road Leicester LE5 1TN UK Website www gent co uk Telephone 44 0 116 246 2000 Tech Support www gentexpert co uk Fax UK 44 0 116 246 2300 4188 781 issue 6_Part 1_08 10_micro DAU install by Honeywell At the end of their useful life the packaging produc...

Page 3: ...operate with any of the above conditions in any combination A A and B B Speaker circuits These terminals accept the connection of two speaker circuits Each speaker circuit can have up to 5 x 64ohms speakers 4188 781 issue 6_Part 2_ 08 10_micro DAU commission 1 Commissioning information micro Distributed Amplifier Unit COMPACT DAU by Honeywell P4 L1 01 L2 02 Audio Status I R SENSOR LOOP P1 N01 C1 N...

Page 4: ...tention please excessive carbon monoxide levels have been detected please leave the area immediately by the nearest available exit 8 Gas Fixed Extinguishant Male May I have your attention please may I have your attention please extinguishant gas release imminent please evacuate the area immediately by the nearest available exit 9 Fire alarm test default Auxiliary 1 Female Attention please attentio...

Page 5: ...in the building whilst this report is being investigated please remain at your workplace 6 Evacuate alternative Male Ladies and gentlemen due to unforeseen circumstances we are required to evacuate the building please leave the building immediately by the nearest available exit 13 Gent Limited advertisement Female Ladies and gentlemen this speech message is produced by Gent Limited s Vigilon Compa...

Page 6: ...ted Amplifier Unit 4 4188 781 issue 6_Part 2_ 08 10_micro DAU commission L 1 0 1 L 2 0 2 L1 0V Mains Distributed Amplifier unit L2 0V VIGILON COMPACT VOICE ALARM PANEL Master Control Board P7 L1 0V L2 0V L1 0V L2 0V DEVICE LOOP CIRCUIT 1 Note The 0V terminals in the device terminal plate are electrically connected together LOOP 2 LOOP 1 P14 PB1 L1 01 L2 02 P13 P12 O A O B I A I B AUDIO LOOP 1 O A ...

Page 7: ...er circuits fast 8 quick flashes blinks every 1s slow 1 slow flash every 0 5s On 0 5s Off every 1s Amplifiers and Speaker circuits healthy CAL micro DAU PCB Press the CAL button on micro DAU PCB to recover from Amplifier fault If the amplifier is still faulty then these indications will reappear Fault on Speaker Circuit B slow No Power to micro DAU Quiescent blink micro DAU in Fall back mode fast ...

Page 8: ...P2 P9 LD1 CAL P5 P11 DISCHARGE LED P6 A B LOCAL AUDIO P17 P17 NVM protect Enabled NVM protect Disabled After the micro DAU is configured insert the NVM link across pins 1 2 of P17 to preserve the data at the unit When the micro DAU is being configured ensure the NVM link is NOT fitted across pins 1 2 of P17 NVM Link DISCHARGE LED LD4 Normally OFF Ensure the SPRING is fitted to Switch SW2 CAL FAULT...

Page 9: ...utes You may also hear a popping sound from the speakers during calibration Audio Status Circuit B fault Circuit A fault 3 m m a xi m u m ra n g e Remote Control Trouble shooting If the remote control fails to operate in close proximity to the indication aperture on micro DAU then a possible cause may be the battery Replace the battery in the remote control micro DAU Audio Status Circuit B fault C...

Page 10: ...emote control You are now in BGM background music volume adjust mode ƒ Press and hold the Power button to save the settings made and release the button after about 2 seconds If PA or VA then go to step 5 Press the button to allow mode change Press or button to change from BGM to PA to VA volume adjust mode The micr DAU LEDs indicate which mode has been selected Press the button to accept the mode ...

Page 11: ...ing on the Background music system How to enable or disable Background music or PA The background music and PA can be enabled or disabled to do this press the Menu On Off button and then select Control followed by Enable Disable and then momentarily press etc and select Audio now select either PA or Music followed by Enter 4188 781 issue 6_Part 2_ 08 10_micro DAU commission 9 micro Distributed Amp...

Page 12: ...uld be disposed of via a suitable recycling centre and in accordance with national or local legislation Gent by Honeywell reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions of changes Hamilton Industrial Park Waterside Road Leicester LE5 1TN UK Website www gent co uk Telephone 44 0 116 246...