1
FREQUENTLY ASKED QUESTIONS:
Q: Do I have to supply the generator with the 100% loaded BTU rated fuel supply and pipe size?
A: Yes, the generator needs the 100% loaded BTU fuel rating to start, run and handle loads. The fuel pipe must be sized for 100% load, regardless
of the load.
Q: Can I use a fuel shut off valve that is not “Full Flow Rated”?
A: No, it must be a Full Flow Rated valve and must also match the required fuel pipe ID dimensions.
Q: Do pipe elbows, tees, drip legs, etc. affect gas pipe size and fl ow?
A: Yes, they are restrictions to gas fl ow. You must add .76 m (2.5 ft) per each elbow, tee, etc. to the overall calcu lated distance from the source to
the generator.
Q: Can I leave the unit on the shipping pallet and install it?
A: No, it must be installed per local jurisdiction, code and the instructions as outlined by Generac.
Q: Can the generator be mounted indoors or in a structure?
A: No, it is designed, manufactured and sold for outdoor use only!
Q: Can I run the Main AC and Control Wires in the same conduit?
A: Yes, this wiring can be run in the same conduit if the appropriate rated wire and insulation is used and it meets code.
Q: Can the Transfer Switch be mounted outdoors?
A: Only if it’s a NEMA 3R rated transfer switch.