![Honeywell FS20X Series Installation Manual And Operating Manual Download Page 5](http://html.mh-extra.com/html/honeywell/fs20x-series/fs20x-series_installation-manual-and-operating-manual_150812005.webp)
Installation Guide and Operating Manual // Model FS20X™ Series
Honeywell
3
1.2
Detector Technical Specifications
1.2.1 Mechanical
Specifications
Enclosure Material:
Copper Free Aluminum (red)
316 Stainless Steel
Physical Dimensions:
Assembly 4.35 in. (
110.49 mm
) Height X 4.81 in. (
122.24 mm
) Diameter
Mounting Holes ¼ in. (
6.35 mm
) Diameter, 5.50 in. (
139.70 mm
) Center to Center
Conduit Entries Two (2) ¾ in. NPT or Two (2) 25 mm
Weight:
Aluminum 3 lbs. 11 oz. (
1.7 kg
) approximately
Stainless Steel 7 lbs. 7 oz. (
3.4 kg
) approximately
Enclosure Rating:
IP66 / NEMA 4 / NEMA 4X
Vibration:
Meets or exceeds Mil Spec 810C,
Method 514.2, Curve AW
1.2.2 Electrical
Specifications
Input Voltage Range:
18 VDC to 32 VDC
Normal Operation Current:
85 mA (
nominal
)
175 mA (
nominal with heater
P
1
P
)
Maximum Fire Alarm Current:
135 mA (
maximum
)
220 mA (
maximum with heater
P
1
P
)
Relay Contact Rating:
1 Amp @ 24 VDC resistive
Analog Current Output:
0.0 to 20.0 mA (
Non-Isolated Source or Sink, User Selectable
)
(
400 Ohms Max Load [loop resistance]
)
0.0 mA (
<0.6 mA
) = Fault
2.0 mA (
±0.6 mA
) = Dirty Window Lens
4.0 mA (
±0.6 mA
) = Normal, Safe (
no Fault, no Fire
)
8.0 mA (
±0.6 mA
) = Background IR
12.0 mA (
±0.6 mA
) = Background UV
16.0 mA (
±0.6 mA
) = Fire Alarm
20.0 mA (
±0.6 mA
) = Verified Fire Alarm
Screw Terminal Wire Sizes:
12 AWG to 22 AWG (
2.50 mm to 0.762 mm
)
Use stranded conductors (
U
not
U
solid core
)
1.2.3 Environmental
Specifications
Operating Temperature
Standard: -40° F to +185° F (-40° C to +85° C)
Operating Humidity Range:
0 to 95% RH,
100% RH condensing for short periods of time
Storage Temperature:
-67° F to +221° F (-55° C to +105° C)
1.2.4 Performance
Specifications
P
2
P
Field of View:
FS20X detectors have a cone of view of 90° horizontal and
80° vertical with the highest sensitivity on the central axis
Sensitivity
One (1) sq. ft. heptane fire at 200 feet (
± 45° from axis
)
Speed of Response:
Typically, 2 to 5 seconds
High Speed Response:
Less than 0.5 seconds to “fireball” type fires
Spectral Sensitivity
~0.185 to 0.26 microns and 0.4 microns to 3.5 microns
1.2.5
Hazardous Area Classifications
(See Section 4.7.3 on Pages 32)
Class
I
, Division 1, Groups A, B, C & D
Class
II
, Division 1 Groups E, F & G
Class
I
, Zone 1, AEx d/ Ex d
II
C
Class
III
Ex db
II
C, Ex tb IIIC
T4: Ta = -40°C to +110°C
T4: Ta = -40°C to +110°C
T5: Ta = -40°C to +75°C
T5: Ta = -40°C to +75°C
T6: Ta = -40°C to +60°C
T6: Ta = -40°C to +60°C
1
P
Heater circuit turns ON only when temperature drops below zero degrees Fahrenheit (-17° C)
P
2
The supply connection wiring shall be rated at least 10°C above the rated service temperature (120°C for T4 applications and 85°C for
T5 applications)