background image

 

OPERATOR MANUAL // SECTION 5: PINOUT DATA 

 

HONEYWELL  

20 

 

PIN 

Description 

DCRtn 

(Not Chassis Ground)

 

Data “A” (RS-485 COMM  A) 

Data “B” (RS-485 COMM  B) 

DC (

+

) Voltage  

Fault Relay Contact A  
(Normally energized CLOSED) 

Fault Relay Contact B  
(Normally energized CLOSED) 

Alarm Relay Contact A  
(Normally OPEN) 

Alarm Relay Contact B  
(Normally OPEN) 

Not used 

10 

Not Used 

Table 3: Flame Detector Connector Pin-outs for FS10-R45 type Detectors 

 

DO NOT CONNECT SHIELD AT THE FLAME DETECTOR. 

Note:  COMM as it is used in this document is an abbreviation  

for Communications.  

 

Detector relays are shown as they are during Normal

 

Operation, that is, there are no Fire Alarm conditions  
or Faults. 

Summary of Contents for FS10-R

Page 1: ...d Operating Manual Multi Spectral Digital Infrared Electro Optical Fire Detector Unitized Two Stage Quick Response FSC Model Nos FS10 R FS10 RN with Wide Band IR FS System 10TM Digital Fire Detection Process Control System ...

Page 2: ...tical Path Integrity CM1 CM1 A DartLogic FireLogic Honeywell Analytics VSD 8 Honeywell Analytics VSD 8 Visual Smoke Detection System VSD 4 VSD 8 Fire Signature Analysis FireBusI FireBusII FirePic FirePicII FirePicIII FirePix FirePicture FSC Honeywell Analytics Honeywell Analytics FSX All FSX Nomenclature Variations such as FS2 FS2X FS3 FS3X FS4 FS4X FS5 FS5X FS6 FS6X FS7 FS7X FS8 FS8X FS9 FS9X FS1...

Page 3: ...OPERATOR MANUAL NOTICES AND TRADEMARKS HONEYWELL 3 Other brand or product names are trademarks of their respective owners Honeywell Analytics ...

Page 4: ...ut This Document Read and understand this manual before installing or operating equipment No part of this document may be copied or reproduced without the express written permission of Honeywell Analytics This manual is subject to change without notice ...

Page 5: ...this booklet REFERENCE INTERNAL Identifies an additional source of information within this booklet Indicates a situation which if not avoided may result in equipment or work data on the system being damaged or lost or may result in the inability to properly operate the process CAUTION Indicates a potentially hazardous situation which if not avoided may result in minor or moderate injury It may als...

Page 6: ...duit Installation 13 2 3 Power Supply Considerations 14 2 4 Mounting the Flame Detectors 14 SECTION 3 OPERATING MODES 15 3 1 Normal Operation 15 3 2 Alert Fire Early Warning 15 3 3 Alarm Condition 15 3 4 Fault Condition 15 3 5 Automatic Detector Test 16 3 6 Manual Detector Test 16 3 7 Advanced System Diagnostics 16 SECTION 4 MAINTENANCE AND REPLACEMENT 17 4 1 Detector Faults 17 4 2 Cleaning Detect...

Page 7: ...OPERATOR MANUAL TABLE OF CONTENTS HONEYWELL 7 Index 25 Limited Warranty 26 Contact Honeywell Analytics 27 Americas 27 Europe 27 Asia Pacific 27 Internet 27 Telephone 27 ...

Page 8: ...llers The FS10 line of Detectors is designed primarily for indoor fire detection applications where combustible materials exist Typical applications include Automotive Paint Lines Aerosol Filling Paint Kitchens General Finishing Curing Ovens Paint Mixing Rooms Powder Coating Booths Warehouse Storage Compressor Modules Liquid Paint Spray Lines Diesel Generators Internal Storage Tanks 1 2 Responses ...

Page 9: ...nt energy sources The Detector simultaneously The Detector is factory set for Alert Fire Early Warning and Fire Alarm detection range of 15 feet FS10 R15 RN15 and 30 feet FS10 R30 RN30 to a one square foot Heptane reference pan fire The Alert response time is factory set to 0 3 second the Fire Early Warning response time is factory set to 1 0 second and The Fire Alarm response time is factory set ...

Page 10: ...with closed contacts The Detector contains one Fire Alarm relay with a contact rating of 1 Amp 24 VDC The relay is de energized with open contacts during Normal Operation During a Fire Alarm condition the relay is energized with closed contacts Note 1 6 3 Fault Relay Output The Fire Relay may be ordered configured in a Latching or Non Latching mode If Latching mode is configured the Fire Relay wil...

Page 11: ...l and vertical 1 6 6 Environment Range The Detector humidity range is 10 to 90 RH non condensing The operating and storage temperature range of the Detector is 40 o F to 185 o F 40 o C to 85 o C 1 6 7 Location For proper installation each Detector should be located within the detection distance ordered from the factory i e 15 feet for the FS10 R15 RN15 A15 AN15 30 feet for the FS10 R30 RN30 A30 AN...

Page 12: ...TION 2 1 Detector Views The Detector may be mounted directly on the wall or with the optional SM2 swivel mounting assembly or SM4 Stainless Steel Swivel Mount refer to Section 6 1 for details 2 09 4 66 1 10 0 67 4 38 2 40 NPT 1 50 Figure 3 Fire Detector Housing Side View ...

Page 13: ...ION 1S GF 240 Connect 240 Volts AC LAST 2 2 Conduit Installation Detectors should be located to cover the specific fire threat areas When planning the conduit observe the following recommendations 1 If only one of the two inch NPT conduit openings of the Detector enclosure is used appropriately seal the unused opening with a threaded tapered plug 2 In areas where moisture may accumulate install an...

Page 14: ...upply the panel s power supply must be able to handle at least 1 20 Amps This load current must also be considered when calculating the panel requirements for 24 hour backup 2 4 Mounting the Flame Detectors The Flame Detectors have the ability to see a one square foot heptane pan fire at half of the Detector s sensitivity off axis out to 45 degrees for a 90 degree Field of view viewing angle It is...

Page 15: ...y blink the red LED continuously energize the Alert Early Warning energize the relay or indicate a 12 mA output current record FirePic in non volatile memory record the event in the Event History file in non volatile memory 3 3 Alarm Condition During a Fire Alarm condition the Detector will turn ON the red LED continuously Energize the Fire Alarm energize the relay record FirePic in non volatile m...

Page 16: ...or s front cover is not installed Note 3 6 Manual Detector Test While ACCTTL tests are occurring the system is still functional and able to alarm to a fire WARNING Responses to the FS10 R Detector relay output must be isolated mechanically not solely by programming the control panel using software or firmware This will avoid external alarms and or suppression discharge when performing the followin...

Page 17: ...nded action Use an air Event History File Action Fault CONDITION 1 No LED illumination No power is available at the Detector Check wiring for broken or crimped cables or loose terminations Fault CONDITION 3 LED blinks 3 times Flame Detector through the lens test failure Clean the lens and grill It is important to clean underneath the grill See Section 3 5 Fault CONDITION 5 LED blinks 5 times Flame...

Page 18: ...touch the sensor windows 5 Using a small screwdriver turn the two clamp screws counter clockwise that secures the ten wire cable plug so the plug may be removed 6 Handle the Flame Detector Module with care and do not touch the sensor windows 7 Carefully wrap the Module in static protection material if none available use aluminum foil and ship to Honeywell Analytics 8 To install a Detector Module j...

Page 19: ...ault Relay Contact A Normally energized CLOSED 6 Fault Relay Contact B Normally energized CLOSED 7 Alarm Relay Contact A Normally OPEN 8 Alarm Relay Contact B Normally OPEN 9 Alert Early Warning Relay Contact A Normally OPEN 10 Alert Early Warning Relay Contact B Normally OPEN Table 2 Flame Detector Connector Pin outs for FS10 R type Detectors J1 Connector FIRE DETECTOR Module ...

Page 20: ...rmally energized CLOSED 7 Alarm Relay Contact A Normally OPEN 8 Alarm Relay Contact B Normally OPEN 9 Not used 10 Not Used Table 3 Flame Detector Connector Pin outs for FS10 R45 type Detectors DO NOT CONNECT SHIELD AT THE FLAME DETECTOR Note COMM as it is used in this document is an abbreviation for Communications Detector relays are shown as they are during Normal Operation that is there are no F...

Page 21: ...OPERATOR MANUAL SECTION 5 PINOUT DATA HONEYWELL 21 1 2 3 4 5 6 7 8 9 10 Figure 3 FS10 R Detector Module Connector Rear View ...

Page 22: ...ION 6 ACCESSORIES HONEYWELL 22 SECTION 6 ACCESSORIES 6 1 Detector Heavy Duty Swivel Mount Part No SM2 4 86 4 26 2 95 2 00 0 295 Dia 4 7 approx Figure 4 Detector Swivel Mount Figure 5 Model SM4 Stainless Steel Swivel Mount ...

Page 23: ...ance for end users with a planned maintenance schedule Should debris collect these specifically designed protective covers may be easily replaced The task of cleaning the Detector viewing windows for proper operation is eliminated 6 4 Extension Pole for Disposable Covers Part No EXPL 1 thus reducing maintenance requirements A regularly scheduled maintenance plan can virtually eliminate the need to...

Page 24: ...echargeable battery terminal box with two connecting cables a 120 VAC wall transformer for recharging the battery and User PC software interface Kit allows access to post event analysis FirePic as well as monitoring the Detector s operation SnapShot Post event analysis includes the Detector s time and date stamp of ALERT ALARM and FAULT histories Event History Note The PC Interface Kit may also be...

Page 25: ...OPERATOR MANUAL INDEX HONEYWELL 25 Index Controller Fault 17 Detector Cable 19 Cleaning 17 Input Power Milliamps 8 Test Lamp 23 Through the Lens Fault 17 ...

Page 26: ...venience commercial loss lost profits or savings or other incidental special or consequential damages arising out of or in connection with the use or inability to use such product to the full extent such may be disclaimed by law THIS WARRANTY DOES NOT COVER 1 Defects or damage resulting from use of the Product s in other than its normal and customary manner 2 Defects or damage from misuse accident...

Page 27: ...olon Science Valley 1 43 Digital Ro 34 Gil Guro Gu Seoul 152 729 Korea Email analytics ap honeywell com Internet These Honeywell websites may be of interest to Industry Solution customers Honeywell Organization URL Corporate www honeywell com Honeywell Analytics www honeywellanalytics com Telephone Contact us by telephone at these numbers Organization Phone Number Americas Honeywell Analytics Inc ...

Page 28: ...1998M0950 Revision A July 2014 2014 Honeywell International Inc ...

Reviews: