Fire Sentry FS7-130-SX and FS-130-SX2
Controllers
Installation Guide and Operating Manual
MAN0933_V1_1521-001_Rev E_08-12
Page 9
3.3.3 Detector Test
The Controller automatically performs FS7-2173 Detector self-tests every 10
minutes (factory set) to check the operation of its Detector. While these Detector
self-tests are occurring, the FS System 7 is still functional and able to detect and
alarm to a fire.
3.3.4
Manual Detector Test
Test the system “end-to-end” by activating each Detector separately on the
standard SX system. SX2 system requires at least two Detectors in a voting group
be activated.
Note: Use FSC’s Model FT-S7 or FS-746 Test Lamps to test each Detector
individually.
WARNING: DISABLE RESPONSES TO CONTROLLER
RELAY OUTPUTS TO AVOID ACTIVATING
EXTERNAL ALARMS AND/OR SUPPRESSION
SYSTEMS DURING TESTING.