background image

2

ROME Series Installation Document —

 P/N 53530:B  9/14/2009

Wiring the Relay Module to an FACP 

Refer to the following table and illustration for wiring connections.

1. All connections/sources are to be power-limited and 

supervised.

2. 12 - 18 AWG (0.75 - 3.25 mm

2

) wire for 24 VDC circuit is 

acceptable.  Refer to the appropriate FACP manual.

3. Power wire distance limitation is set by 1.2 volt maximum line 

drop from source to end of circuit.

4. Maximum distance from FACP to last ANN-BUS device must 

not exceed 1,250 feet (380 m).  Refer to Wiring Distance 
Table in appropriate FACP manual for wire gauge and 
distance limitations.

Setting Relay Module DIP Switches

Each ANN-BUS device requires a unique address.  Relay Module DIP switch SW1 is used to set the address for the mod-
ule.  A maximum of 8 devices can be connected to the FACP ANN-BUS communication circuit.  ANN-BUS device 
addresses do not need to be sequential and can be set to any number between 01 and 08.  Note that 00 is not a valid 
address.  The following illustrates the DIP switch settings for each address (ID Number):

Relay Terminals (TB1) FACP ANN-BUS Terminals

Terminal 1 (B)

B (ANN-BUS)

Terminal 2 (A)

A (ANN-BUS)

Terminal 3 (+)

(+)

Terminal 4 (-)

(-)

B (ANN-BUS)
A (ANN-BUS)
+ (24 VDC)
- (GND)

}

Connect to FACP ANN-BUS and/or next device

}

Connect to FACP or next device

Relay Module

Summary of Contents for Fire-lite ROME Series

Page 1: ...more detailed programming information refer to the appro priate FACP installation manual Relay Module Specifications Relay Designations and Terminals The relay numbers and terminal designations are illustrated in the following illustration Operating Voltage 24 VDC Max Current 24 VDC Alarm 75 mA Standby 15 mA Operating Temperature 32 to 120 F 0 to 49 C Max Wiring Distance from FACP with 12 AWG wire...

Page 2: ...e in appropriate FACP manual for wire gauge and distance limitations Setting Relay Module DIP Switches Each ANN BUS device requires a unique address Relay Module DIP switch SW1 is used to set the address for the mod ule A maximum of 8 devices can be connected to the FACP ANN BUS communication circuit ANN BUS device addresses do not need to be sequential and can be set to any number between 01 and ...

Page 3: ...s a guide 3 Remove the ANN MBRLY from the ROME Series and drill two 3 32 dia 0 093 holes in the locations marked in step 2 Note that these holes will be used to secure the ANN MBRLY using the two supplied self tapping screws 4 Place the ANN MBRLY mounting bracket oblong holes in position over the mounting studs and install the two supplied nuts but do not tighten at this time 5 Install the two sup...

Page 4: ...odule on the ANN MBRLY mounting bracket by positioning the four module mounting holes over the four standoffs on the mounting bracket 2 Secure the Relay Module to the ANN MBRLY mounting bracket with the four supplied screws 3 Set the SW1 DIP switches and connect the wiring as described in the previous sections mounting hole mounting hole mounting hole mounting hole ROME Series Optional Relay Modul...

Page 5: ...KT as a guide 3 Remove the MULTIMOD BRKT from the ROME Series and drill two 3 32 dia 0 093 holes in the locations marked in step 2 Note that these holes will be used to secure the MULTIMOD BRKT using the two supplied self tapping screws 4 Place the MULTIMOD BRKT mounting bracket oblong holes in position over the mounting studs and install the two supplied nuts but do not tighten at this time 5 Ins...

Page 6: ... and flat against the bracket as illustrated below 8 Install the addressable Multi Module on the MULTIMOD BRKT mounting bracket by positioning the four module mounting holes over the four standoffs on the mounting bracket 9 Secure the addressable Multi Module to the MULTIMOD BRKT bracket with the four supplied mounting screws as illustrated below standoff standoff standoff standoff mounting screw ...

Reviews: