Honeywell F200E Product Data Download Page 4

F200E CHARGED-MEDIA AIR CLEANER

68-0238

4

Fig. 5. Highboy furnace, with closet installation. Media air
cleaner is mounted vertically on furnace between furnace

and louvered return air opening in closet door.

Fig. 6. Lowboy furnace, with media air cleaner mounted

horizontally in return plenum just above furnace and

opposite heating plenum.

Fig. 7. Counterflow furnace, with media air cleaner

mounted horizontally in return duct or plenum just

above furnace.

M941A

Fig. 8. Central fan installation, with media air cleaner

mounted horizontally in central return duct.

M14788

M14789

M14790

Summary of Contents for F200E

Page 1: ...reased pressure drop threshold at filter Filter change status is transmitted to wall mounted AIRWATCH Indicator The RF AIRWATCH Indicator is included SPECIFICATIONS IMPORTANT The specifications in this publication do not include normal manufacturing tolerances therefore an individual unit may not exactly match the listed specifications This product is tested and calibrated under closely controlled...

Page 2: ...ated for greater media capacity Filter Element Underwriters Laboratories Inc UL 900 Class 2 Listed Capacity And Pressure Drop See Fig 2 Initial Pressure Drop 0 177 in wc at 492 fpm Temperature Rating 40 to 140 F 40 to 60 C Dimensions See Fig 1 Fig 1 Installation dimensions in in mm of air cleaner Mounting Mounts in any position in the return air duct usually next to the furnace blower compartment ...

Page 3: ...ton on the F200E door to reset both the door indicator light and the RF AIRWATCH Air Cleaner Indicator See Table 1 for AIRWATCH operation Fig 2 Capacity Pressure Drop and Area of F100F Filter Media PLANNING THE INSTALLATION Location The media air cleaner should be installed where all the air passing through the system is circulated through it The best location is in the return air duct next to the...

Page 4: ...ing in closet door Fig 6 Lowboy furnace with media air cleaner mounted horizontally in return plenum just above furnace and opposite heating plenum Fig 7 Counterflow furnace with media air cleaner mounted horizontally in return duct or plenum just above furnace M941A Fig 8 Central fan installation with media air cleaner mounted horizontally in central return duct M14788 M14789 M14790 ...

Page 5: ... of expansion on each side of a transition fitting Turning Vanes If the media air cleaner is installed next to an elbow or angle fitting add turning vanes inside the angle to distribute airflow more evenly across the face of the media See Fig 12 Offsets If the duct connection to the furnace in a side installation allows less than 7 in 178 mm for mounting media air cleaner cabinet attach an offset ...

Page 6: ...ll them whenever an abrupt 90 degree elbow is installed directly against the media air cleaner cabinet Fasten Cabinet To Ductwork Fasten side of cabinet to the ductwork using sheet metal screws rivets or slip joints as appropriate Connect Ductwork Connect the vertical duct section to the elbow If the vertical drop of the duct is less than 7 in 178 mm from the side of the furnace shorten the horizo...

Page 7: ... again at step 2 Mount AIRWATCH Indicator 1 Remove the AIRWATCH Indicator from the base a Depress the tab on the bottom edge of the base b Pull off the bottom of the front cover 2 Position the base on the wall in the desired mounting position using the holes in the base as a template mark the locations for the anchors and screws provided Also mark location of round hole in center of base when usin...

Page 8: ...e 1 AIRWATCH Indicator LCD Description AIRWATCH Indicator Condition Meaning Action No indicator on AIRWATCH has no power replace battery On Battery indicator on continuously AIRWATCH is functioning normally On Battery indicator flashing Flashing two seconds on six seconds off Replace battery in the F200E door Do not press any reset buttons after battery change Flashing two seconds on two seconds o...

Reviews: