9.5 Assigning a PROFIBUS Channel to PIOMB
After you assign a PDC to a PIOMB, you must assign a PROFIBUS channel to the Control Module containing
the C300CEE. You must perform this to view the data of the input or the output channel.
The following are the types of PROFIBUS I/O channel blocks that are available and you must select the
appropriate channel block based on the channel type.
• PbAiChannel - If the channel type is analog input channel.
• PbDiChannel - If the channel type is digital input channel.
• PbAoChannel - If the channel type is analog output channel.
• PbDoChannel - If the channel type is digital output channel.
For example, if the channel type of a PDC is Digital input (DI), you must drag-and-drop the PBDICHANNEL
from the PGM_IF library into the Control Module containing the CEE.
Perform the following steps to assign a PROFIBUS channel to a PIOMB
1
Drag-and-drop the appropriate PROFIBUS I/O channel block from the PGM_IF library to the Control
Module containing the C300 Controller.
2
Double-click the PROFIBUS I/O channel block.
The PROFIBUS I/O channel block configuration form appears.
3
In the
Module Name
list, select the PIOMB associated with this channel block.
4
In the
Module Type
list, select the module type of this channel.
The number of channels that can be assigned to this block and the channel names appear under the
Module
Type
field.
5
Select the appropriate channel number to which you must assign the channel block.
9 PROFIBUS I/O MODULE (PIOMB) FUNCTION BLOCK
223
Summary of Contents for Experion PKS
Page 1: ...Experion PKS PROFIBUS Gateway Module User s Guide EPDOC XX88 en 431E June 2018 Release 431 ...
Page 8: ...CONTENTS 8 www honeywell com ...
Page 10: ...1 ABOUT THIS GUIDE 10 www honeywell com ...
Page 32: ...4 PROFIBUS GATEWAY MODULE PGM INSTALLATION 32 www honeywell com ...
Page 58: ...5 PROFIBUS GATEWAY MODULE PGM BLOCK 58 www honeywell com ...
Page 69: ...6 PROTOCOL BLOCK 69 ...
Page 103: ...5 Click OK 6 PROTOCOL BLOCK 103 ...
Page 110: ...6 PROTOCOL BLOCK 110 www honeywell com ...
Page 183: ...PDC Details tab Figure 6 Detail Display of PDC Details tab 7 DEVICE SUPPORT BLOCK DSB 183 ...
Page 186: ...7 DEVICE SUPPORT BLOCK DSB 186 www honeywell com ...
Page 231: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 231 ...
Page 232: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 232 www honeywell com ...
Page 236: ...10 PROFIBUS GATEWAY MODULE PGM CONFIGURATION EXAMPLE 236 www honeywell com ...
Page 264: ...13 PROFIBUS GATEWAY MODULE PGM TROUBLESHOOTING 264 www honeywell com ...