Fig. 84. Excel 500-XCL5010 C-Bus DIP switch location
Table 23. DIP switch settings for C-Bus termination
(Excel 500-XCL5010)
DIP switch Communication Controller
Com-
setting
speed
location
patibility
XD505A,
up
max. 9.6 Kbaud
-
XL20XD
middle of
XD508,
middle
max. 76.8 Kbaud
bus
XL20XD508
beginning or XD508,
down
max. 76.8 Kbaud
end of bus
XL20XD508
NOTE:
Modules listed in Compatibility column are used in
Excel 20/100B/500/600 Controllers.
Excel 600 Cable Specifications
For connection to the XI582 Operator Interface, two tailor
made cables are available.
—
XW564
cable, length 7 ft (2.5 m)
—
XW565
cable, length 15 ft (5 m)
EXCEL 500/600 INSTALLATION INSTRUCTIONS
For connection to the XI584 Operator and Service Computer,
a tailor-made cable is available with plugs on both ends.
—
XW567
cable, length 7 ft (2.5m)
Fig. 86. Excel 600 / XI584 cable details
Fig. 85. Excel 500 / XI582 cable details