EXCEL 10 FCU CONTROLLER LNS PLUG-INS USER GUIDE
37 EN2B-0285GE51
R0909
Table C2. Configuration Variables for Excel 10 FCU Controllers
NV name
field name
engineering units:
English (metric) or states
plus range
digital
state
or
value
default comments
nciApplVer
application_type
UBYTE, 0 to 255
0
This configuration variable specifies the current application number of
the Excel 10 application.
nciApplVer
version_no
UBYTE, 0 to 255
0
This configuration variable specifies the version number of the Excel
10 application.
nciApplVer
time[0]
UBYTE, 0 to 255
0
The time stamp of the last change to the Excel 10 application con-
figuration. Time meets the ANSI C time stamp requirement specifying
the number of seconds elapsed since midnight (0:00:00), January 1,
1970. It is represented in the Intel Format and is four bytes in length.
nciApplVer
time[1]
UBYTE, 0 to 255
0
See above.
nciApplVer
time[2]
UBYTE, 0 to 255
0
See above.
nciApplVer
time[3]
UBYTE, 0 to 255
0
See above.
nciDeviceName
ch[0-17]
UBYTE, 0 to 255
0
This configuration variable specifies the name of each device. This is
an ASCII string with the a size of 18 characters. A name with all NULLs
means that the device has not been configured.
nciLocation
SNVT_str_asc
0x00
This configuration variable is used to provide more descriptive physical
loacation information than can be provided by the Neuron chip's 6 byte
location string.
nciMaxSendTime
SNVT_temp_p
0 to 6553 seconds
0 s from factory
This configuration variable specifies the maximum time that expires
before the node object automatically transmits nvoStatus. This pro-
vides a heartbeat output that can be used by the destination objects to
ensure that the node is still healthy. The heartbeat output may be
disabled by setting nciMaxSendTime = 0.
Summary of Contents for Excel 10 W7752D