background image

Installation Guidelines

The  MSM2000A  Control  Module  is  designed  to  be  mounted  within  the  luminaire  on  fixing  centres  of  135mm. 

2

Connections to the control module as shown above should be made using single-core wire (0.5-1.5mm  ).

The  interconnect  cable  between  the  detector  head  and  control  module  should  be  routed  away  from  the  other 
luminaire internal wiring and away from the lamp end-caps.

The recommended position for the detector is in the middle of the luminaire.   Where this is not possible and the 
sensor is fitted near one end of the lamps, please ensure that the sensor is at the ”cold” end of the lamps. 

The DHW/S Mini Head should be mounted such that only the raised front section of the bezel protrudes through the 
cut out in the louvre or infill panel. This should be constructed in accordance with the dimensions above. 

1.  The Mini Detector Head must be mounted within the luminaire.  Do not mount remotely.

2.  The connecting cable must not be extended. 

3.  Artificial  light  illuminating  the Mini  Head  must only  be  reflected  from the room  - i.e. there  must be  no  direct 

illumination. 

4.  In order to receive satisfactory light-level regulating operation, a detector must observe a substantially greater 

proportion of artificial light from the luminaire(s) under its control than from neighbouring luminaires not under its 
control.  This is particularly important when planning the installed layout of linear luminaires that have an integral 
detector positioned at one end.

Mounting Details 

Analogue 1-10V 
Control Module

Please read instructions prior to installation

Neutral
OneSwitch  Input

Live OUT
Live IN

Control Module Part No

MSM2000A

Detector

Connection

_

+

}

1-10V

Analogue

Control

Operating voltage 230V 50Hz   10%
Power consumption: <2W
tc 70 C
Max Load (Live OUT): 2 Amps
Max Number of Ballasts: 4
For use only with electronic, high-frequency 
ballasts                 

+_

Made in EC

TM

0.5 - 1.5

Neutral
OneSwitch  Input

Live OUT
Live IN

_

+

}

1-10V

Analogue

Control

TM

MSM2000A

Neutral
Live IN

_

+

}

1-10V

Analogue

Control

Analogue 1-10V Ballast(s)

OneSwitch Input
for manual control

Mains Supply

Electrical Connections

800mm 

Flying Lead

RJ12

Plug

14.9mm

21.5mm

TOP VIEW

SIDE VIEW

32mm

21.5mm

18.8mm 17.5mm

21.3mm

Mini Detector 
Head 

147.5mm

135mm

(Height = 22mm)

30mm

Summary of Contents for Ex-Or MSM2000A

Page 1: ...g Instructions Note QuickSet Pro required for commissioning LightSpot Digital Luminaire Controllers MSM2000A Control Module DHW DHS Mini Detector Head for use with Analogue 1 10V and Fixed Output Electronic High frequency Ballasts ...

Page 2: ...y be reflected from the room i e there must be no direct illumination 4 In order to receive satisfactory light level regulating operation a detector must observe a substantially greater proportion of artificial light from the luminaire s under its control than from neighbouring luminaires not under its control This is particularly important when planning the installed layout of linear luminaires t...

Page 3: ... download operation took place Tip turn the lights off first using the IR Remote HC5 menu found in Utilities if you want to measure the perceived ambient light level with no contribution from the controlled lighting Note When setting the regulating light level as described in the previous section the Threshold is also set to the current measured level OneSwitch Dimming OneSwitch dimming affords lo...

Page 4: ...0 C CAPACITY Total load must not exceed 2 AMPS up to 4 Ballasts MAX Electronic high frequency ballasts ONLY o INTERCONNECT CABLE TEMPERATURE RATING 60 C COLOUR White RAL9010 or silver bezel DHW White DHS Silver MATERIAL UV stabilised polycarbonate DHW DHS Flame retardant PC ABS MSM2000A IP RATING 20 DIMENSIONS See diagrams overleaf WEIGHT 32g incl 0 8m cable DHW DHS 48g MSM2000A 6 0m 2 5m Honeywel...

Reviews: