Installation Guidelines
The MSM2000A Control Module is designed to be mounted within the luminaire on fixing centres of 135mm.
2
Connections to the control module as shown above should be made using single-core wire (0.5-1.5mm ).
The interconnect cable between the detector head and control module should be routed away from the other
luminaire internal wiring and away from the lamp end-caps.
The recommended position for the detector is in the middle of the luminaire. Where this is not possible and the
sensor is fitted near one end of the lamps, please ensure that the sensor is at the ”cold” end of the lamps.
The DHW/S Mini Head should be mounted such that only the raised front section of the bezel protrudes through the
cut out in the louvre or infill panel. This should be constructed in accordance with the dimensions above.
1. The Mini Detector Head must be mounted within the luminaire. Do not mount remotely.
2. The connecting cable must not be extended.
3. Artificial light illuminating the Mini Head must only be reflected from the room - i.e. there must be no direct
illumination.
4. In order to receive satisfactory light-level regulating operation, a detector must observe a substantially greater
proportion of artificial light from the luminaire(s) under its control than from neighbouring luminaires not under its
control. This is particularly important when planning the installed layout of linear luminaires that have an integral
detector positioned at one end.
Mounting Details
Analogue 1-10V
Control Module
Please read instructions prior to installation
Neutral
OneSwitch Input
Live OUT
Live IN
Control Module Part No
MSM2000A
Detector
Connection
_
+
}
1-10V
Analogue
Control
Operating voltage 230V 50Hz 10%
Power consumption: <2W
tc 70 C
Max Load (Live OUT): 2 Amps
Max Number of Ballasts: 4
For use only with electronic, high-frequency
ballasts
+_
Made in EC
TM
0.5 - 1.5
Neutral
OneSwitch Input
Live OUT
Live IN
_
+
}
1-10V
Analogue
Control
TM
MSM2000A
Neutral
Live IN
_
+
}
1-10V
Analogue
Control
Analogue 1-10V Ballast(s)
OneSwitch Input
for manual control
Mains Supply
Electrical Connections
800mm
Flying Lead
RJ12
Plug
14.9mm
21.5mm
TOP VIEW
SIDE VIEW
32mm
21.5mm
18.8mm 17.5mm
21.3mm
Mini Detector
Head
147.5mm
135mm
(Height = 22mm)
30mm