Installation and Commissioning

Instructions

 Note: QuickSet Pro required for commissioning
 

1

MLS2021DSM

MLS2021DALISM

MLS2021DF & MLS2021DSM for DSI ballasts

MLS2021DALIF & MLS2021DALISM for DALI ballasts

Digital Gold PIR Detector 

with regulating photocell

MLS2021DF

MLS2021DALIF

Summary of Contents for Ex-Or MLS2021DF

Page 1: ...uctions Note QuickSet Pro required for commissioning 1 MLS2021DSM MLS2021DALISM MLS2021DF MLS2021DSM for DSI ballasts MLS2021DALIF MLS2021DALISM for DALI ballasts Digital Gold PIR Detector with regulating photocell MLS2021DF MLS2021DALIF ...

Page 2: ...or DALI luminaires a switched load of up to 6 Amps or a combination of the two When controlling DSI or DALI ballasts the ballast type must not be mixed The DSI or DALI input terminals on the ballasts should be connected in parallel with each other and to the Polarity Free Digital Output terminals on the rear of the detector Each DSI or DALI luminaire is controlled completely by its digital input a...

Page 3: ... maintained NC NC 2 x MLS2021D In Parallel using Switched Output only LOAD Max 6Amps N E L Permanent or switched supply VOLT FREE OUTPUT VOLT FREE OUTPUT LIVE IN LIVE IN NEUTRAL NEUTRAL EARTH EARTH Any connection not shown is NO CONNECTION ONE SWITCH NC NC ONE SWITCH Relay outputs may be connected together in parallel to cover larger areas however the total load on all combined relay outputs must ...

Page 4: ...ogrammed if desired by use of the infrared programming tool QuickSet Pro All settings are retained in the event of a power failure Commissioning The units are supplied with the factory default settings shown below which make further commissioning unnecessary in many applications To make use of the programmable settings an infrared commissioning tool is required QuickSet Pro A ten second time delay...

Page 5: ...rolled lighting on entry when natural light is sufficient i e SET POINT LOW is exceeded but only ACTIVE mode will extinguish the lighting if natural light increases sufficiently during occupancy i e SET POINT HIGH is exceeded continuously for a period equal to OFF DELAY The lighting is restored immediately if the illumination level subsequently drops below SET POINT LOW iii Photocell DISABLED If t...

Page 6: ...ready on switch them on manually by pressing UTILITIES LIGHTSPOT MLS LCM IR REMOTE Luminaire OK QuickSet Pro or HC5A Fluorescent lights do not reach full output until up to 15 minutes after being switched on so ensure that the lights are fully warmed up before continuing 2 Wait until the time of day when the natural light level is at the point below which you would want the lights to be on and abo...

Page 7: ...neSwitch Dimming and the HC5A ImportantAdditional Notes 1 All terminals on this product are provided for final connections It is not intended that the productbe used as a junction box for loopingcables 2 A means for disconnection must be incorporated in the fixed wiring in accordance with the currentwiringregulations 3 Although nominally 12V the dimming output is not SELV and therefore should be t...

Page 8: ...NDED LOAD VOLT FREE 6 Amps MAXIMUM RECOMMENDED LOAD DSI DALI 25 Ballasts COLOUR White RAL9010 MATERIAL Flame retardant PC ABS WEIGHT 210g flush version 187g surface version IP RATING 3X o o OPERATING TEMPERATURE 0 C to 40 C W4426G 6 0m 2 5m Fascia 10mm deep 8 100mm Honeywell Ex Or St Marks Court North Street Horsham West Sussex RH12 1BW UK Tel 44 0 1942 719229 Fax 44 0 1942 508753 Email technicals...