Commissioning

The units are supplied with the factory default settings shown below which 
render commissioning unnecessary in many applications.  To make use of the 
programmable settings, an infrared commissioning tool is required (HP2000). 
A ten-second "Walk Test" time delay is selectable to aid commissioning

Factory Default Settings

These are the settings to which the units have been programmed before they 
leave the factory.

Gold Series LightSpot for use with Analogue 1-10V Ballasts   

Only suitably qualified personnel should install this equipment. 

This high-performance presence detector forms a stand-alone lighting control 
unit.  It  is  equipped  with  a  regulating  photocell  to  control  analogue  1-10V 
ballasts (when using the detector’s Dimming Output) and a volt-free output to 
fully  extinguish  analogue  dimmable  loads  or  for  control  of  non-dimmable 
lighting  loads.  The  detector  incorporates  Ex-Or’s  OneSwitch  Dimming, 
allowing local manual  operation of any controlled lighting load. 

Electrical Connections

The detector should be connected in accordance with the diagrams opposite.
Each  luminaire  to  be  controlled  must  contain  an  analogue  regulating  type 
ballast with the appropriate analogue input.  Ballast types must not be mixed.  
The analogue input terminals on the ballasts should be connected in parallel 
with each other and to the analogue 1-10V output terminals on the rear of the 
detector,  observing  the  polarity.    Also  each  of  these  analogue  regulating 
ballast Live inputs (maximum load 6 Amps) must be provided by the Volt-free 
output  (see 1st Wiring Example) from the detector. 

When switching via the volt-free output multiple MS2421A detectors may be 
connected in parallel provided the controlled load does not exceed 6 Amps. 
(see 3rd Wiring Example). 

DO NOT CONNECT DIMMING OUTPUTS TOGETHER .

OneSwitch

OneSwitch Dimming affords local control to the end-user whereby a simple, 
momentary, push-to-make wallswitch can be used to raise or lower the lighting 
level  or  toggle  the  output  of  the  unit  ON  or  OFF. A  short  press  (less  than                           
1 second) toggles the relay output from OFF to ON or from ON to OFF. A long 
press will ramp the analogue output either up or down with no effect on the volt-
free output. If the output prior to pressing the switch is above 90% the output 
will ramp down; if below 90% it will ramp up. If the latest press and the current 
press are within 5 seconds of each other it will ramp in the opposite direction.  

Sensitivity to Movement

While the factory settings will be correct for many applications, the sensitivity 
can be adjusted if required.  

ON Sensitivity (ON Range):

 This sets the detector’s range when the lights are 

ON. (i.e. the space is Occupied) Choose setting from 1-100 where 1 is lowest 
and  100  is  maximum.    (Note:  Choose  the  lowest  level  possible  to  give 
adequate detection.)

OFF Sensitivity (OFF Range):

 This sets the detector’s range when the lights 

are OFF. (i.e. the space is Unoccupied/Vacant)  Choose % setting from 10% to 
100% where 10% = 10% of ON Sensitivity and 100% = same as ON Sensitivity. 
This is an approximation and should be tested on site during commissioning.

Generally  the  OFF  Sensitivity  should  be  significantly  less  than  the  ON 
Sensitivity  as  in  the  ON/Occupied  state  small  movements  of  e.g.  seated 
persons  must  be  detected  while  in  the  OFF/Vacant  state  only  the  gross 
movements  of  persons  entering  the  space  need  to  be  detected.  This 
differential sensitivity prevents false triggering of the Presence Detection logic.

  

Like all programmable parameters, the sensitivity settings will be retained in 
the event of a power failure and can be re-programmed any number of times.

Commissioning the Photocell

Commissioning the setpoints for Photocell based control requires the HP2000 
Hand-held Programmer.This tool should be used aimed squarely at the front of 
the Detector/Photocell at a distance of 1m although it can work at substantially 
greater distances if aimed carefully. 

Regulating  Only: 

For  this  mode  the  PCELL  RLY  action  should  be  set  to 

“DISABLED”  and  the  lights  will  be  on  continuously  during  periods  of 
occupancy. The Analogue 1-10V output dims the ballast(s) in the luminaires.      
It always tries to maintain a programmed light level on the working plane. It 
aims for the level stored in the parameter Set-point Low. 

Sometimes it is convenient to limit the extent to which the presence detector 
with photocell is allowed to dim the light output of the luminaire(s). This can be 
done by setting the "DIMMING" parameter. This setting determines the range 
over which dimming can be operated e.g. setting 80% allows the lumiaires to 
be dimmed down to a minimum of 20% of its possible output as natural light 
strengthens.

If it is desired to operate the lighting without any automatic photocell based 
control over the dimming process, (e.g. only manual control of dimming, by 
OneSwitch,  and/or  scene  setting  by  HC5  Infrared  Hand-held  Controller  is 
required) then the default values of 1023 should be retained in the parameters 
Set-point Low and Set-point High.

Programming  the  Regulating  level:   

Place  a  light  meter  on  the  working 

plane underneath the presence detector with photocell. Adjust the light output 
of the  luminaire  up or down manually by infrared.  (On  the  HP2000,  select 
“UTILITIES”  from  the  Main  Menu  and  then  “SET  LIGHT  LEVEL”  from  the 
UTILITIES Menu. The up and down Arrow keys allow adjustment of the light 
level up and down whilst pointing the handset at the presence detector with 
photocell.) When the light meter reads  the  desired  level, press and  hold the 
central    “OK”    button    until    the    lights  “blink”  to  acknowledge    that  the   

Parameter

Power up
Response
Off Delay
On Sensitivity
Off Sensitivity

Entry Scene
Lamp Max
Dimming
Fade to Off
When Vacant
PCell Rly
Set-Point Low
Set-Point High 

Start Lamps

Default
Setting

ON
AUTO
20 min
80
80%

1
100%
100%
NO
NO

1023
1023

MAX

Disabled

Options

ON/OFF
Auto/Semi-auto
1min-96hrs or Disabled
1-100
10-100% in 10% increments

1-6
10%-100%

YES/NO
10 Exit Scenes
Disabled, Passive, Active
0-1023
0-1023

MAX/MIN

REG 50%-100%

Options

Each of these settings
can be re-programmed,
if desired, by use of the
infrared programming
tool HP2000.

Location

This 
it be installed on a rigid surface that will not itself be subject to movement or 
vibration.   
Please note that microwave detectors are not recommended for applications 
where there are large surface areas of metal, e.g. metal ceiling or floor tiles, as 
unpredictable sensitivity may result.
The units are graded according to four variations in operating frequency.  Each 
type  can  be  identified  by  different  colour-coding  on  the  detector  label  and 
carton.  For reliable operation it is essential that units of the same colour code 
do not occupy adjacent positions in open-plan areas or in adjoining rooms (see 
below). 

 is an extremely sensitive movement detector; it is essential therefore that 

Note: 

Should  it  be  necessary  to  order  additional  detectors  for  an  existing 

installation and specific colour-coded detectors are needed, please add the 
following suffixes to the part number:  Y = Yellow, B= Blue, G= Green, R = Red. 
(There  is  normally  no  need  to  specify  the  colour  codes,  as  orders  are 
dispatched with a suitable colour code mix.) 

Fixing

 

MS2421ASM  - The housing may be secured to a hard surface or a BESA box.  
The unit fits into the housing with a simple bayonet action.
MS2421AF - Depth required behind ceiling: 62mm from front flange plus an 
allowance for the minimum bend radius of the cable.   Sinking box fits into a 
89mm diameter hole in ceiling tile or plasterboard ceiling.  To avoid damage to 
ceiling tile, do not overtighten.  No access above the ceiling is necessary. 

Please note: Do not position this product on a pitch narrower than 5m.

Do not mount within 0.25m of a luminaire.

Yellow

Blue

Red

Green

Red

Green

Green

Green

Blue

Red

Green

Red

Green

Blue

Blue

Red

Red

Blue

Yellow

Blue

Red

Green

Red

Green

Blue

Green

Green

Blue

Red

Green

Red

Green

Blue

Blue

Red

Red

Blue

Red

Green

Green

Red

Green

Blue

Red

Blue

Red

Green

Blue

Green

Red

Green

Blue

Red

Blue

Yellow

Yellow

Yellow

Yellow

Yellow

Yellow

Yellow

Yellow

Yellow

Yellow

Yellow

Yellow

Yellow

Yellow

Yellow

Yellow

Blue

Blue

Reviews: