Average temperature measurement with VITO temperature probes
___________________________________________________________________________
Instruction manual VITO
Page 14
With the VITO temperature probes and also with an 864 MTT, it might be required to disable the lowest spot
element from the average temperature calculation. That can be done by setting the first position in item
MW
to
any other hexa-decimal number than ‘0’, for instance: ‘F’. In fact, with item
MW
any spot temperature element (or
more spots) can be disabled from average temperature calculation.
Item
Name
Description
W2
=
Protection level 2
Enter protection level 2
MW
=
MTT wiring connection
Sixteen hexa-decimal characters; default: 0000000000000000
When one (or more) of the elements must be disabled from
average temperature calculation, set the desired position to a
hexa-decimal value other than ‘0’.
For instance, to disable lowest spot element:
MW=F000000000000000
Note:
When entering item MW with the Portable Enraf Terminal,
the display will be cleared after entering the 15
th
character.
Continue with entering the last character and press return.
All 16 entered characters will be repeated at the top line of
the PET.
EX
Exit
Exit protection level 2
2.2.2
Additional temperature settings for 877 FDI
Item
Name
Description
W2
=
Protection level 2
Enter protection level 2
OB
= Option board *)
Three ASCII characters. This item informs the XPU what option
board is installed. That can be:
MPU : for HCU option board in MPU emulation mode
HPU : for HCU option board in HPU emulation mode
EG
= Enable temperature
One ASCII character; either ‘D’ or ‘E’. With this item can be
transmission *)
selected if the 877 FDI shall answer on a temperature request
(C-record), addressed to the connected level gauge.
E : transmission of temperature record enabled
D : transmission of temperature record disabled
Note:
When item
EG
is set to ‘E’, make sure the related level gauge
has no temperature option installed.
TF
= Temperature source
One ASCII character; either ‘I’ or ‘E’. this item selects if there is
selection
a temperature measurement inside the indicator (internal) or to
be fetched from the Enraf field bus (external).
I : Internal
E : External
EX
Exit
Exit protection level 2
*) This item is not implemented in the XPU-2.