− load:
approx. 50 Ω
•
max. measurement error:
±0.05 % of the measurement
(in the measuring range 4 ... 20 mA and between −10 to +55 °C
ambient temperature)
•
max. cable length:
500 m
Hints on parameterization
Branch
<device> – Basic System – I/O boards –
Board <x>: MFE7
Set the following values:
•
channel
A1+ A1−
or
A2+ A2−
: type
Current input
•
parameter
Power supply
: value
Off
(sink mode)
6.4.8 HART Measurement Transmitter (EEx i) via ExMFE5 Board
Hazardous Area
Safe Area
enCore device
ExMFE5 board
P+
SH
HART pressure
transmitter, EEx i
HART temperature
transmitter, EEx i
HART
communicator
P−
Fig. 6-13: HART pressure and temperature transmitter (EEx i) via ExMFE5 – example