EKM-E ETHER-MON KEY DE-211
25
31-00160—01
33.
Click the
Serial Settings
tab and click to check the box for
Change Serial Port Settings
.
Fig. 43.
34.
Set Serial Settings exactly as shown in the window above.
a. Baud Rate 9600
b. Parity None
c.
Data Bits 8
d. Stop Bit 1
e.
Flow Control None
f.
UART FIFO Enable
35.
Click the
Password
tab.
36.
Select the box Change Password.
37.
Honeywell E-Mon recommends using
emon
(lower case) as the defalt password in the event technical support
requires remote access to configure the E10039 settings.