Honeywell DT92 Manual Download Page 15

DT92 WIRELESS DIGITAL ROOM THERMOSTAT

15

INSTALLER MODE – HOW TO SET PARAMETERS 

Each parameter is identified by a 2-letter code, and has a range of values. These are shown in the table below, 
followed by instructions on how to enter Installer Mode, how to select a parameter and change its value, and finally 
how to exit Installer Mode.

Description 

Parameter 

Range of values 

Factory (default) value 

Minimum ON/OFF time 

Ot 

1, 2, 3, 4, 5 minutes 

1 minute 

Cycle rate 

Cr 

3, 6, 9, 12 cycles/hour 

Proportional band width 

Pb 

1.5 to 3.0°C 

1.5°C 

Temperature measurement offset 

tO 

-3 to 3°C

Upper setpoint limit 

uL 

21 to 35°C 

35°C 

Lower setpoint limit 

LL 

5 to 21°C 

5°C 

Energy saving ECO temperature 
(this parameter is only available on 
the DT92E model) 

ES 

5 to 35°C 

18°C 

Selection of heat/cool changeover 

HC 

0 = disable 

1 = enable 

* Off/standby setpoint

OS 

-- = off, 

5 to 16°C 

5°C 

** Room temperature sensor use 

Su 

0 = DT92 alone 

1 = DT92 with HR80, using 

HR80 sensors 

2 = DT92 with HR80, using 

DT92 sensor 

Failsafe mode (loss of RF 
communications) 

LC 

0 = switch OFF 

1 = operate at 20% ON 

** Enable HR80 window-open 
function 

H0 

0 = disable 

1 = enable 

** Enable HR80 local override 

HL 

0 = disable 

1 = enable 

Reset parameters 

FS 

0, 1 

1 (factory settings) 

* In cooling mode the off/standby setpoint defaults to OFF
** Only required if system contains HR80 programmable radiator valves

Specific Applications 

Setting 

What requires to be changed? 

Cycle

s/ 

hour 

Minimum 

on/off time 

Gas boilers 
(<30kW) 

No changes required 

Oil boiler 

1. Set minimum ON/OFF time to 4 minutes
2. Set cycle rate to 3 cycles/hour

Thermal actuator 

12 

Set cycle rate to 12 cycles/hour 

Heating 

Zone valve 

No changes required 
1. Configure the thermostat to allow switching between

heating and cooling modes (set parameter HC = 1)

2. Set the thermostat to the required mode of operation

(heating or cooling) by pressing the 

 and 

buttons together for 3 seconds when in normal run
mode (does not work in off/standby mode).

Heatpump / Air 
conditioner 

1. Set minimum ON/OFF time to 4 minutes
2. Set cycle rate to 3 cycles/hour

Air 
conditionin

Fan-coil unit 

No changes required 

Some parameters require to be set to match specific applications. Recommended settings are shown in the table 
below.

Summary of Contents for DT92

Page 1: ...isplay and easy to read characters Display shows room temperature with option to inquire about setpoint 5 C to 35 C setpoint range with 0 5 C increments using and buttons Off standby button allowing manual switch off with frost protection active Adjustable off standby setpoint 5 C to 16 C or DT92 can be set to off completely Room thermostat is battery powered by 2 x AA LR6 alkaline cells giving up...

Page 2: ...02 EN55014 1 2006 EN55014 2 1997 ETSI EN300 220 3 ETSI EN301 489 3 WEEE RoHS compliant TEMPERATURE CONTROL Sensing element 10K 25 C NTC thermistor Temperature setting range 5 C to 35 C setpoint range in 0 5 C increments Control form Self learning TPI Fuzzy Logic algorithm Proportional band 1 5 C adjustable up to 3 C in 0 1 C increments Minimum on off time 1 minute adjustable up to 5 min in 1 min i...

Page 3: ...ry This means they will recognize and communicate with each other as soon as they are powered up The complete device is therefore ready for immediate installation CONTROLS DISPLAY LAYOUT battery low warning fault indicator setpoint indicator off standby indicator off standby button temperature display frost protect indicator heating demand indicator ECO mode countdown timer ECO button ECO countdow...

Page 4: ...l between parameters and to make changes to their values MAIN FEATURES 2 Way RF Communications RF communications between the room thermostat and the relay box is 2 way making it more efficient and reliable and allowing the room thermostat to display information from the relay box such as actual relay status or communications loss Signal Strength Test Mode Another benefit of 2 way RF is to allow th...

Page 5: ...ork the 2 units must be reset and bound to each other by following the procedure for Binding Re binding 4 Take the DT92 thermostat to the proposed mounting location and initiate the Signal Strength Test This will indicate if the thermostat is suitably positioned to provide a reliable signal for the relay box If the signal strength is too low the thermostat must be repositioned 5 When a suitable po...

Page 6: ...ROOM THERMOSTAT 6 a Boiler b Boiler potential free connection c Zone valve d Air conditioner WIRING CONNECTIONS a b c d Note BDR91 Relay Box requires a permanent mains power supply Completing the BDR91 Relay Box Installation ...

Page 7: ...nication Test to confirm the BDR91 relay box is wired correctly and that both devices are bound linked to each other 2 3 m RF COMMUNICATION TEST Initiate RF Communication Test by the following sequence of actions applied to the DT92 thermostat If green LED does not flash units are not linked and must be bound together again If green LED flashes every 6 seconds units are correctly bound and a suita...

Page 8: ...ion SIGNAL STRENGTH TEST The Signal Strength Test is used to find a suitable position for the DT92 thermostat such that the signal received by the BDR91 relay box is high strength This will optimize system performance The BDR91 relay box measures the strength of the signal received from the room thermostat and upon request sends this measurement back to the room thermostat using the 2 way RF commu...

Page 9: ...DT92 WIRELESS DIGITAL ROOM THERMOSTAT 9 TEST AND BINDING FLOWCHART Mounting the DT92 Room Thermostat Wall mounting Optional table stand Completing the installation Press for 5 seconds to exit any mode ...

Page 10: ... around 1m 2 Reset stored data in relay box 3 Put relay box into binding mode 4 Reset stored data in room thermostat 5 Put room thermostat into binding mode 6 Bind room thermostat to relay box Reset Stored Data in Relay Box Press and hold the push button for 15s to reset the stored data in the BDR91 relay box The red LED will give a brief flash every second to verify reset has happened Put Relay B...

Page 11: ...t Put Room Thermostat into Binding Mode Bind Room Thermostat to Relay Box With both units in binding mode pressing the off standby button on the room thermostat will bind them together To verify it is now bound the red light on the relay box will immediately stop flashing After about 5 seconds the room thermostat will come out of binding mode and go back to off mode ...

Page 12: ...building the two products should communicate reliably within a 30m range It is important to take into consideration that walls and ceilings will reduce the RF signal The strength of the RF signal reaching the Relay Box depends on the number of walls and ceilings separating it from the room thermostat as well as the building construction the diagram below illustrates an example of typical signal st...

Page 13: ...rent relay operation The green LED will indicate the relay position Loss of RF Communications If RF communications is lost for whatever reason the BDR91 relay box will operate in failsafe mode as set in the Installer Mode and the red LED will illuminate The DT92 room thermostat will flash the RF symbol until communications are restored 92 90 27 90 30 5 ...

Page 14: ...e where it will control at this predefined temperature for as long as the user wishes This temperature can be set from 5 C to 35 C Heating or Cooling operation DT92 can be used for heating or cooling applications If heating cooling changeover is selected the thermostat can be manually switched from heating to cooling and back again by pressing and holding the and buttons together for 3 seconds in ...

Page 15: ...nications LC 0 switch OFF 1 operate at 20 ON 0 Enable HR80 window open function H0 0 disable 1 enable 0 Enable HR80 local override HL 0 disable 1 enable 1 Reset parameters FS 0 1 1 factory settings In cooling mode the off standby setpoint defaults to OFF Only required if system contains HR80 programmable radiator valves Specific Applications Setting What requires to be changed Cycle s hour Minimum...

Page 16: ...r value To select and change a parameter d Use the and buttons to move from one parameter to another e Press the off standby button to select the parameter value ready to change f Use the and buttons to adjust the parameter value When the correct value is flashing confirm the selection by pressing the off standby button again returning to the parameter menu To exit Installer Mode g Press and hold ...

Page 17: ...have this switched on all the time even when the house is occupied 5 Do not programme excessive heatup times for the central heating If the occupier is out of the house or still in bed much of this heating would be unnecessary 6 In the evening when the house is up to temperature it is often possible to switch the heating off up to an hour before going to bed without any noticeable reduction in com...

Reviews: