DG..T · Edition 01.22

EN-4

Pressure switches (DG..t, DG..Ft, DG..st):

type

Adjust-

ing 

range

1)

 

"WC 

(mbar)

Mean 

switch-

ing 

differ-

ential

2)

 

"WC 

(mbar)

Max. inlet 

pressure  

psi (mbar)

With 

venting 

line

3)

no 

venting 

line

DG 6T

0.2–2.4 

(0.5–6)

0.08–

0.12 

(0.2–0.3)

8.5 

(600)

2.4 

(165)

DG 10T

0.4–4 

(1–10)

0.1–0.16 

(0.25–

0.4)

8.5 

(600)

(480)

DG 50T

1–20 

(2.5–50)

0.32–0.6 

(0.8–1.5)

8.5 

(600)

(480)

DG 150T

12–60 

(30–150)

1.2–2 

(3–5)

8.5 

(600)

(480)

DG 500T

40–200 

(100–

500)

3.2–6.8 

(8–17)

8.5 

(600)

(480)

Pressure switches with manual reset (DG..Ht, 
DG..nt):

type

Adjust-

ing 

range

1) 

"WC 

(mbar)

Reset 

pres-

sure

4)

 

"WC 

(mbar)

Max. inlet 

pressure  

psi (mbar)

With 

venting 

line

3)

no 

venting 

line

DG 10T

0.4–4 

(1–10)

0.16–

0.4 

(0.4–1)

8.5 

(600)

(480)

DG 50T

1–20 

(2.5–50)

0.4–0.8 

(1–2)

8.5 

(600)

(480)

DG 150T

12–60 

(30–150)

2–6 

(5–15)

8.5 

(600)

(480)

DG 500T

40–200 

(100–

500)

6–10 

(15–25)

8.5 

(600)

(480)

1) Adjusting tolerance = ± 15% of the scale value.

2) Mean switching differential at min. and max. setting 

"WC (mbar).

3) Connect the venting line to port 4. Connections, see 

page 2 (3 Installation).

4) Difference between switching pressure and possible 

reset.

6 PRessURe sWItCHes WItH MAn-
UAL Reset

 

DG..NT locks off if the pressure drops to the value 
set using the hand wheel.

 

DG..HT locks off if the pressure rises to the value 
set using the hand wheel.

 1 

Reset the pressure switch using the manual reset.

 

Requirement for reset: 
DG..NT: the pressure must have risen at least to the 
set switching point plus the pressure differential be-
tween the switching pressure and possible lock-off. 
DG..HT: the pressure must have dropped at least 
to the set switching point minus the pressure differ-
ential between the switching pressure and possible 
lock-off.

 

For details of the pressure differential between the 
switching pressure and possible reset, see table 
on page 3 (5 Adjustment).

7 tIGHtness test

 1 

Shut off the downstream gas pipeline close to the 

valve.

 2 

Open the valve and the gas supply.

 

Check all used ports for tightness.

 

N

2

 = 13 psi (max. 29 psi) <15 minutes

 3 

N

2

 

 4 

8 MAIntenAnCe CYCLes

Check for external tightness at least once per annum, 
at least twice per annum for operation with biogas.

9 ACCessoRIes

9.1 Blue pilot lamp for 110/120 V AC

110/120 V AC, I = 1.2 mA, Order No.: 74916121.

 1 

 

 2 

 

 3 

 

 4 

Summary of Contents for DG-T Series

Page 1: ...n accordance with the regulations and standards in force These instructions can also be found at www docuthek com 1 2 Explanation of symbols 1 2 3 a b c Action Instruction 1 3 Liability We will not be held liable for damage resulting from non observance of the instructions and non com pliant use 1 4 Safety instructions Information that is relevant for safety is indicated in the instructions as fol...

Page 2: ...h cover 2 Lower housing section 3 Hand wheel 4 1 2 conduit coupling 5 Manual reset DG NT and DG HT only 2 3 Type label DG T Approval and type see type label For detailed information on the adjusting range mean switching differential max inlet pressure lock off me dium and switching properties see page 5 10 Technical data und and the table on page 3 5 Adjustment 3 INSTALLATION CAUTION Please observ...

Page 3: ...articles in the surrounding air or in the medium Filter pad for port 4 The web app PartDetective for selecting spare parts is available at www ad latus org 4 WIRING CAUTION To ensure that the DL is not damaged during operation note the switching capacity see page 5 10 Technical data In the case of low switching capacities such as 24 V 8 mA for example we recommend using an RC mod ule 22 Ω 1 μF in ...

Page 4: ...n 4 Difference between switching pressure and possible reset 6 PRESSURE SWITCHES WITH MAN UAL RESET DG NT locks off if the pressure drops to the value set using the hand wheel DG HT locks off if the pressure rises to the value set using the hand wheel 1 Reset the pressure switch using the manual reset Requirement for reset DG NT the pressure must have risen at least to the set switching point plus...

Page 5: ...The set switching point may palpably change in media and ambient temperatures below 22 F 30 C Transport temperature ambient temperature Storage temperature 4 to 104 F 20 to 40 C Enclosure IP 65 This unit is not suitable for cleaning with a high pres sure cleaner and or cleaning products 10 3 Mechanical data Gas types natural gas town gas LPG gaseous flue gas biogas max 0 1 by vol H2S and air Max i...

Page 6: ...the ambient conditions described Storage time 6 months in the original packaging before using for the first time If stored for longer than this the overall service life will be reduced by the corresponding amount of extra storage time 13 DISPOSAL Devices with electronic components WEEE Directive 2012 19 EU Waste Electrical and Electronic Equipment Directive At the end of the product life number of...

Reviews: