Honeywell DELUXEHEATPUMP T8511G Installation Instructions Manual Download Page 6

69-1052—1

6

T8511G DELUXE HEAT PUMP ZONE THERMOSTAT

IMPORTANT

Review the settings to confirm that they match
the system. To exit the Installer Setup, press and
hold the Information   

i

   key until the display

returns to normal (approximately three seconds).

INSTALLER SYSTEM-TEST

Use the Installer System-Test to check the thermostat
operation. Refer to Table 3 for a list of the available
system-tests.

To start the system-test:

CAUTION

The minimum off time for compressors is bypassed
during the Installer System-Test. Equipment damage
can occur if the compressor is cycled too quickly.

Press and hold the increase 

 and decrease 

▼ 

keys at

the same time, until two zeros appear. All segments of the
LCD will be displayed before the two zeros appear. See
Fig. 11 and 12.

Table 3. Tests Available In the Installer System-Test.

Fig. 11. Display of all the segments of the LCD.

Fig. 12. Display of test number.

Refer to Table 4 for the directions and results of the
specific tests.

NOTE:

Press and hold the increase 

 and decrease 

keys together for three seconds to exit the
system-test. The system-test will time out after
ten minutes without any key presses.

Table 4. Installer System-Test Options.

(Continued)

Em HeatOffCool Auto Only

Heat Cool

OnAuto

System

Fan

Room

Outdoor

Em Ht Temporary Setting

Wait

%Humid

Aux Ht

Remote

Repl

Batt

M4844

M6792

TEST MODE NUMBER

Test  

Number

System-Test Description

10-19

Heating equipment can be turned on  
and off

20-29

Emergency heat (select models)
equipment can be turned on and off

30-39

Cooling equipment can be turned on  
and off

40-49

Fan equipment can be turned on and off  

60-69

Keyboard keys test

70-79

Thermostat information including date
code and software versions are displayed

Key to

Press

Test

Number

Description

Heating Equipment System-Test

i 

 

10

Enter heating equipment system-test.

  

11

Stage-one heat comes on. System fan is also energized.

  

12

Stage-two heat comes on. Stage-one heat and system fan remain on.

  

11

Stage-two heat turns off.

  

10

Stage-one heat and system fan turn off.

Emergency Heating Equipment System-Test (select models)

i 

 

20

Changing from heating to emergency heating equipment system-test.

  

21

Emergency heat comes on. System fan also comes on.

  

20

Emergency heat turns off.

Cooling Equipment System-Test

 

30

Change from heating or emergency heating to cooling equipment system-test.  

  

31

Cool and system fan come on.

  

30

Cool and system fan turn off.

Summary of Contents for DELUXEHEATPUMP T8511G

Page 1: ...application 3 Installer must be a trained experienced service technician 4 After completing installation use these instructions to check out the product operation Location Install the thermostat about 5 ft 1 5m above the floor in an area with good air circulation at average temperature See Fig 1 Do not install the thermostat where it can be affected by drafts or dead spots behind doors and in corn...

Page 2: ...nect power before wiring to prevent electrical shock or equipment damage 1 Loosen the terminal screws on the wallplate and connect the system wires See Fig 5 IMPORTANT Use 18 gauge color coded thermostat cable for proper wiring 2 Securely tighten each terminal screw 3 Push excess wire back into the hole 4 Plug the hole with nonflammable insulation to prevent drafts from affecting the thermostat 5 ...

Page 3: ...erature select models set the system operation set the fan operation See Fig 7 for the location of the keys Fig 7 Key locations and descriptions O G B L C R Y E W2 OT OT O1 T8 G1 T7 B1 T6 E1 T5 T4 M1 THERMOSTAT CHANGEOVER CONTROL OUTDOOR TEMPERATURE SENSOR ZONE 1 M12188 B E L G Y R O W2 C OT W2 L G Y R W M6 M4 M1 OT THERMOSTAT TotalZone PANEL THERMOSTAT CONNECTIONS OUTDOOR TEMPERATURE SENSOR OPTIO...

Page 4: ...figuration options and the factory settings for the T8511G A combination of key presses are required to use the Installer Setup feature To enter the Installer Setup press and hold the Information i key with the increase and decrease keys until the first number is displayed All display segments appear for approximately three seconds before the number is displayed See Fig 9 and 10 To advance to the ...

Page 5: ...ure displaya 24 00 No outdoor temperature is displayed 01 Outdoor temperature is displayed Needs a C7089B1000 Outdoor Sensor to operate Not used 25 thru 32 Minimum off time for the compressor 33 05 5 minute minimum off time for the compressor 00 01 02 03 or 04 Minimum number of minutes 0 thru 5 the compressor will be off between calls for the compressor Heating setpoint range stopa 34 90 Heating s...

Page 6: ... after ten minutes without any key presses Table 4 Installer System Test Options Continued Em HeatOffCool Auto Only Heat Cool OnAuto System Fan Room Outdoor Em Ht Temporary Setting Wait Humid Aux Ht Remote Repl Batt M4844 M6792 TEST MODE NUMBER Test Number System Test Description 10 19 Heating equipment can be turned on and off 20 29 Emergency heat select models equipment can be turned on and off ...

Page 7: ... software revision number Example 001 Revision number 1 M4864 M10444 M4866 M6791 Key to Press Test Number Description Fan Equipment System Test i 40 Change from cooling to fan equipment system test 41 Fan comes on 40 Fan turns off Key Operation System Test IMPORTANT Test numbers will only be displayed when the system is configured for the selected function EXAMPLE Numbers 60 61 and 62 are the only...

Page 8: ... if the circuit breaker is tripped reset the circuit breaker check if the system fuse is blown replace the fuse check if the power switch on the HVAC equipment is in the Off position set to the On position check wiring between thermostat and HVAC equipment replace any broken wires and tighten any loose connections If 24 Vac is present proceed with troubleshooting Thermostat microprocessor is locke...

Page 9: ...f the system fuse is blown replace the fuse check if the system switch at the equipment is in the Off position set to the On position check wiring between thermostat and HVAC equipment replace any broken wires and tighten any loose connections If 24 Vac is present proceed with troubleshooting Thermostat minimum off time is activated Wait up to five minutes for the system to respond Enter Installer...

Page 10: ...69 1052 1 10 T8511G DELUXE HEAT PUMP ZONE THERMOSTAT ...

Page 11: ...69 1052 1 11 T8511G DELUXE HEAT PUMP ZONE THERMOSTAT ...

Page 12: ... PUMP ZONE THERMOSTAT 69 1052 1 J H Rev 6 97 Printed in Taiwan R O C www honeywell com yourhome Helping You Control Your World Honeywell Trol A Temp 57 Bushes Lane Elmwood Park NJ 07407 3204 201 794 8004 800 828 8367 Fax 201 794 1359 ...

Reviews: