DC1010/1020/1030/1040 PRODUCT MANUAL
1
Before using this manual, please check whether the range, input and output match
your requirement.
1.
Front Panel Instruction
1.1
Display
PV
:Process Value, 4-digit display (red color)
SP
:Set Point, 4-digit display (green color)
1.2
LED
OUT1
:Output 1, green color
OUT2
:Output 2, green color
AT
:Auto-Tuning, yellow color
PRO
:Program, yellow color
AL1
:Alarm 1, red color
AL2
:Alarm 2, red color
MAN
:Manual, yellow color
1.3
Key
SET
:MODE(LEVEL) & SET key
:SHIFT key
:DOWN key
:UP key
A/M
:Auto/Manual key
2.
Auto Tuning
2.1
Once AT set ‘YES’, auto tuning is to be performed.
2.2
After auto tuning finished, PID parameter is to be set automatically.
2.3
ATVL = auto tuning offset, and it will be deduced from SP.
(It prevents over-shooting during auto tuning)
SP-ATVL = Auto-tuning value, ATVL = Auto tuning offset
Ex.) SP = 200
°
C, ATVL = 5, Auto tuning point is at 195
°
C
* ATVL means auto-tuning point (195
°
C) in program type model
2.4
Auto tuning failure
2.4.1 ATVL is too big
Æ
If no sure, set ATVL = 0)
2.4.2 System time is too long.
Æ
Set PID parameter individually.