Honeywell D896 Installation Instructions Manual Download Page 5

69-1088B

5

D896 AUTOMATIC VENT DAMPER

SETTINGS

The service switch operates in normal (NORM) or service
(SERV) modes. See Fig. 4.

NORM—D896 opens on a call for heat and closes at

the end of the heating cycle.

SERV—D896 remains open at the end of a call for

heat. The switch must be in the SERV position
before manually opening the damper.

CHECKOUT

Heating

1. Turn on the power supply.
2. If using a thermostat, set the heat anticipator at .13A

plus the current draw for the control module and  the
system.

3. Set the thermostat or controller 10

°

F (6

°

C) above

the room temperature to call for heat.

4. Check that the D896 CALL FOR HEAT and

IGNITION GAS PWR LEDs are lit and that the
damper opens before the gas valve opens and the
pilot or main burner ignites. See Fig. 8.

NOTE:

If a boiler gas control is sequenced by the
Aquastat® controller, make sure that the
damper opens prior to the opening of the
gas control.

5. Turn the thermostat or controller 10

°

F (6

°

C) below

the room temperature. Make sure the LEDs turn off
and the D896 closes.

6. Cycle the heating system at least three times, using

the thermostat or controller to ensure the system is
operating safely.

THE AIR DUCT IS CLOSED WHEN THE
INDICATOR POINTS PERPENDICULAR TO
THE DIRECTION OF THE AIR DUCT

THE AIR DUCT IS OPEN WHEN 
THE INDICATOR POINTS IN THE 
DIRECTION OF THE AIR DUCT

M3431

Fig. 8. Determining damper position.

Cooling

CAUTION

Damage to air condtioner condenser possible.
Do not operate cooling if outdoor temperature is
below 50

°

F (10

°

C).

1. Set the thermostat or controller to COOL. Move the

setpoint 10

°

F (6

°

C) below the room temperature.

2. Make sure the cooling system operates.
3. Check that the D896 is in the closed position. See

Fig. 8.

4. Return the thermostat or controller to the desired

settings.

NOTE TO INSTALLER:

Explain to the homeowner that a yearly inspec-
tion by a trained, experienced service technician
is necessary for safe, efficient operation of the
vent damper and heating system. The home-
owner should check for deterioration from
corrosion or other sources between service
technician calls.

TROUBLESHOOTING

WARNING

Fire or explosion hazard. Can cause property
damage, severe injury or death.
Explosion or carbon monoxide poisoning possible.
Never apply a jumper across or short gas control
terminals or wires. This can force the D896 to
remain closed and cause an explosion.

Summary of Contents for D896

Page 1: ... damper is fully open the IGNITION GAS PWR LED lights and the furnace or boiler burner ignites When the heating cycle ends both LEDs are truned off the burner turns off and the damper automatically closes Heating system efficiency is increased because the closed damper reduces the loss of residual appliance heat and heated room air through the draft diverter INSTALLATION When Installing this Produ...

Page 2: ... sure the D896 is used to control only one appliance CAUTION Do not force damper open Damage to device can result Manually open damper using a screwdriver Place screwdriver in slotted knob see Fig 4 and rotate counterclockwise until arrow is pointing in the direction of the stack and both LEDs turn on Mounting The damper must be mounted as close as possible to the draft hood without modifying the ...

Page 3: ...nt explosion or carbon monoxide poisoning 2 Do not use the D896 with an L8148 or L8124 with a manual automatic switch because the switch can override the safety interlocks in the system wiring causing carbon monoxide buildup CAUTION 1 Remove the shorting plug on the S8600 S8610 or L8148E before attaching the wiring harness 2 Do not permit device wiring to contact high temperature surfaces 3 Label ...

Page 4: ...6 OPERATES ONLY WHEN VENT DAMPER IS CONNECTED LED 1 LIGHTS WHEN DAMPER IS OPEN LED 2 LIGHTS WITH CALL FOR HEAT SERVICE SWITCH THE NORMAL SWITCH SETTING IS NORM IF THE SWITCH IS MOVED TO THE SERV POSITION THE DAMPER REMAINS OPEN NO W Z TERMINALS ON L7148 M11382 D896 1 2 4 WIRING HARNESS 24 Vac THERMOSTAT 1K L8148E1166 L7148 1K1 L1 HOT L2 CIRCULATOR 3 4 1 3 2 6 PRONG FEMALE MOLEX RECEPTACLE IN L8148...

Page 5: ... using the thermostat or controller to ensure the system is operating safely THE AIR DUCT IS CLOSED WHEN THE INDICATOR POINTS PERPENDICULAR TO THE DIRECTION OF THE AIR DUCT THE AIR DUCT IS OPEN WHEN THE INDICATOR POINTS IN THE DIRECTION OF THE AIR DUCT M3431 Fig 8 Determining damper position Cooling CAUTION Damage to air condtioner condenser possible Do not operate cooling if outdoor temperature i...

Page 6: ...the absence of local codes to the National Fuel Gas Code ANSI Z223 1 1988 NFPA 54 for guidance 9 Place in operation the appliance being inspected Follow the lighting instructions Adjust thermostat so appliance will operate continuously 10 Determine that the pilot s when provided is burning properly and that main burner ignition is satisfactory by interrupting and reestablishing the electrical supp...

Page 7: ... thermostat to determine it is properly adjusted 9 Sequence the appliance through at least three normal operating cycles 10 Insofarasispractical closeallbuildingdoorsandwindowsandalldoorsbetweenthespaceinwhichtheappliance is located and other spaces of the building Turn on clothes dryers Turn on any exhaust fans such as range hoods and bathroom exhausts so they will operate at maximum speed Do not...

Page 8: ...ng Control Honeywell Limited Honeywell Limitée 155 Gordon Baker Road North York Ontario M2H 2C9 Helping You Control Your World 69 1088B J S 3 97 Printed in U S A Home and Building Control Honeywell Inc Honeywell Plaza P O Box 524 Minneapolis MN 55408 0524 ...

Page 9: ...ment et le générateur d air chaud ou la chaudière se met en marche Lorsque le cycle de chauffage prend fin le générateur ou la chaudière s éteint et le registre se referme L efficacité du système de chauffage s accroît car la fermeture du registre réduit la perte de chaleur résiduelle et de chaleur ambiante par l ouverture du coupe tirage INSTALLATION Avant D installer ce Produit 1 Lire les instru...

Page 10: ...VERTISSEMENT Ne pas forcer l ouverture du registre à la main au risque de l endommager Pour ouvrir le registre à la main utiliser un tournevis Insérer le tournevis dans le bouton fendu voir la Fig 4 et tourner dans le sens antihoraire jusqu à ce que la flèche pointe dans le sens de la cheminée et que les deux voyants soient allumés Montage Le registre doit être installé aussi près que possible du ...

Page 11: ...HON EN PLACE RETENIR LA PALETTE ET APPUYER SUR LE BOUCHON MF3429 DISPOSITIF DE COMMANDE DU MOTEUR BOUCHON DE PALETTE PALETTE DU REGISTRE Câblage MISE EN GARDE Peut causer des maladies graves et entraîner la mort Empêcher les explosions et l empoisonnement au monoxyde de carbone 1 L utilisation d un registre d aération D896 requiert l installation d un bloc combiné gaz à deux vannes ou de deux vann...

Page 12: ...ORM SI L INTERRUPTEUR EST À LA POSITION SERV LE REGISTRE RESTE OUVERT MF11374 D896 1 2 4 FAISCEAU DE FILS THERMOSTAT 24 V c a 1K L8148E1166 1K1 L1 SOUS TENSION L2 CIRCULATEUR 3 4 1 3 2 RÉCEPTACLE DE PRISE MOLEX FEMELLE À 6 BROCHES DANS LE L8148E ET PRISE MOLEX MÂLE À 5 BROCHES SUR LE CÂBLE 24V MISE 24V À LA TERRE PRISE MOLEX MÂLE À 4 BROCHES POLARISÉES ET PRISE MOLEX FEMELLE À 4 BROCHES CORRESPOND...

Page 13: ...on normal et la position service Voir la Fig 4 NORMAL Le D896 s ouvre lors d une demande de chaleur et se referme à la fin du cycle de chauffage SERVICE Le D896 reste ouvert à la fin de la demande de chaleur L interrupteur doit être à la position SERVICE avant que le registre ne soit ouvert à la main VÉRIFICATION Chauffage 1 Rétablir l alimentation électrique 2 Si on utilise un thermostat régler l...

Page 14: ...Cela pourrait forcer le registre D896 à rester en position de fermeture REMARQUE En cas de panne de courant le registre restera exactement à la position où il se trouve au moment de la panne ouvert fermé ou entre les deux Lorsque le courant sera rétabli le registre ouvrira si le thermostat demande de la chaleur ou se refermera si le thermostat ne demande pas de chaleur Régler le thermostat ou le r...

Page 15: ...ence de tels codes ou règlements se reporter au National Fuel Gas Code norme ANSI Z223 1 1988 NFPA 54 pour obtenir des conseils 9 Mettre en marche l appareil faisant l objet de l inspection Suivre les instructions d allumage Ajuster le thermostat de façon à ce que l appareil fonctionne de façon continue 10 Déterminer si la ou les veilleuses le cas échéant brûlent correctement et que l allumage du ...

Page 16: ... de déterminer si elle est correctement réglée 9 Faire fonctionner l appareil pendant au moins trois cycles de fonctionnement normal 10 Dans la mesure du possible fermer toutes les portes et fenêtres du bâtiment et toutes les portes entre la pièce où l appareil est situé et les autres pièces du bâtiment Faire fonctionner les sécheuses à linge Faire fonctionner les ventilateurs d extraction tels qu...

Reviews: