General
Description
Indications
LED Status
Fully charged
Charging
Battery fault or
emergency mode
Operational test
Light source fault
Autonomy test
Duration fault
CHARGE
(
green
)
LAMP
FAULT
(
red
)
BATT.
FAULT
(
yellow
)
Note
:
Permanently
ON
Blink
Indifferent
Off
Every 15 days the luminaire will perform an
emergency operation test. This will light the white
LEDs for approximately 3 seconds. The red LED will
flash during this test sequence. Every 6 months the
luminaire will perform a battery condition test. The
test will last for the stated duration. The white LEDs
will be lit and the yellow LED will flash during this
test sequence.
Cube
is a self-contained luminary with selftest
function.
It can be configured as maintained or non-
maintained.
Selftest Functions
Emergency Operation Test
Press the TEST button less than 5 seconds. The
white LEDs light for about 3 seconds and the red
LED flashes.
Battery Condition Test
Press the TEST button for 5 to 10 seconds. This test
will last for for the stated duration and can only be
performed when the battery is fully charged (steady
green LED). The white LEDs light and the yellow LED
flashes.
Manual Test Functions
Resetting Errors
Press the TEST button more than 10 seconds to
delete all indicated errors. The luminaire enters
regular
operation mode.
Note:
When using DALI or Wireless communication,
the frequencies and schedules for tests will instead
be determined by the connected PC software.
In case that the luminaire no longer meets its rated
duration of operation, the battery must be
replaced.
To avoid that luminaires perform their battery test
at the same day, connect the battery packs with
more than 1,5 minutes in between.
Important notice when installing luminaires
within the same area!!!
1. Operations for installation, maintainance or
testing must be done by authorized personnel
only
.
Always use in any case round mains cable,
with a diameter of 5-10mm (H05RN-F type
2
2x1mm ) or any other type, at least equal to it's
mechanical and electrical properties).
3. In case of battery replacement, it must be
replaced by the same type, by the manufacturer
or a competent person.
5.
The control gear within this luminaire is a built in
control gear which relies on the luminaire for
protection against electric shock.
4. In case of inactive use for a period greater than 2
months, disconnect the battery by pulling out
the battery’s connector.
6. The control gear is proof against supply voltage
polarity reversal.
7. This control gear has mains connected primary
windings.
8.
I
s not allowed to discard batteries into
t i
common trash bins, they must be discarded
only
in battery recycling points. Do not
incinerate.
ΑΤΤΕΝΤΙΟΝ!
!!
2. The device must be connected to the mains
power supply through a fuse that is dependent
on the total line’s power load.
Connectors
CN15:
Indication LEDs connector
CN2:
Communication Connector
CN5:
Module connector
CN1:
Power connector
CN13:
Non user connector
CN11:
Non user connector
2
Installation Methods
1
1
1
1
1
Luminaire
Manual
Package Contents
Mounting accessories
Indication sign
The luminaire can be installed in 3 different ways. It can be installed either at the ceiling, either hanging
(hanging with
chain and hanging with eye bolts. For ceiling installation special accessories are including. For hanging installation only
eye bolts are including.
Installation Instructions
Ceiling Mounting
1
2
A
C
B
Ceiling
mounting
Hanging installation
with chain
Hanging installation
with hooks
1
2
3
1
4
1
2
Changing Pictogram
Hanging Installation
5
6
3
3
4
4
2
Mind the orientation of placement
!!
The top cover placement is achieved
according to the bottom part of the
luminaire and the already installed
pictograms.
L N
C1C2
L N
C1C2
L N
C1 C2
L N
C1 C2
Battery Connection
Battery Connection
1
2
1
2
5
6
Follow the same steps for the remaining sides of the pictogram.
Make a hole in the center
of the
rubber gasket by using a small
screwdriver. Pass the round
cable through the rubber
gasket and install the gasket in
the appropriate hole.
Connect the mains cable to
the respective terminal block:
L for live wire, N for neutral
and for ground. Install the
included tie (if needed) to
fasten securely the power cables. Power supply cables cross
2
section should be 0.8 – 3 mm . The C1 and C2 terminals are
used for elBus communication (optional), DALI communication
(optional) or voltage free contact (optional).
Connect the mains cable to
the respective terminal block:
L for live wire, N for neutral
and for ground. Install the
included tie (if needed) to
Make a hole in the center of the
rubber gasket by using a small
screwdriver. Pass the round
cable through the rubber
gasket and install the gasket in
the appropriate hole.
cables. Power supply cables cross section should be 0.8 – 3
2
mm . The C1 and C2 terminals are used for elBus
communication (optional), DALI communication (optional) or
voltage free contact (optional).