CS8800 WATER HEATER PILOT BURNER ASSEMBLY

Automation and Control Solutions

Honeywell International Inc.

Honeywell Limited-Honeywell Limitée

1985 Douglas Drive North

35 Dynamic Drive

Golden Valley, MN  55422

Toronto, Ontario  M1V 4Z9

customer.honeywell.com

® U.S. Registered Trademark
© 2008 Honeywell International Inc.
69-1863—03    M.S.  Rev. 07-08

Fig. 1. Mount pilot burner on main burner.

3.

Mount the pilot burner so the ignition flame 
remains properly positioned with respect to the 
main burner flame.

4.

Supply the pilot flame with ample air that is free 
of combustion products.

5.

Do not impinge the pilot flame on adjacent parts. 
Do not impinge the main burner flame on the pilot 
burner.

6.

Do not expose the pilot flame to falling scale that 
could impair ignition of the main burner.

7.

Do not expose the pilot burner to the main burner 
rollout while igniting or extinguishing.

8.

Do not expose the pilot flame to drafts that push 
or pull the pilot flame away from the thermopile.

STARTUP AND CHECKOUT

Perform Gas Leak Test

WARNING

Fire or Explosion Hazard.
Can cause property damage, serious injury 
or death.

Check for gas leaks with soap and water solution 
any time work is done on a gas system.

Gas Leak Test

1.

Ensure that the gas supply is turned on at the 
appliance service valve.

2.

Paint the pipe connections upstream from the pilot 
burner with a rich soap and water solution. Bubbles 
indicate a gas leak.

3.

If a leak is detected, tighten the pipe connections.

4.

Stand clear of the main burner while lighting to 
prevent injury from hidden leaks that could cause 
flashback in the appliance vestibule. Light the main 
burner.

5.

With the main burner in operation, paint the pipe 
joints (including the adapters) and gas control inlet 
and outlet with a rich soap and water solution. 

6.

If another leak is detected, tighten the adapter 
screws, joints and pipe connections.

7.

Replace the part if the leak cannot be stopped.

Pilot Flame

The pilot flame should envelop 3/8 in. to 1/2 in.
(10 to 13 mm) of the thermopile tip. 

Ignite Pilot Burner

1.

Before lighting the pilot burner, turn the knob to its 
lowest setting. Wait for unburned gas to vent.

WARNING

Explosion or Fire Hazard.
Can cause severe injury, death or property 
damage.

LP gas is heavier than air and does not vent 
upward. Smell for LP gas next to the floor. If you 
smell gas, shut off the main valve in the gas 
piping or “ON LP” at the tank. Perform the Gas 
Leak Test to recheck the connections.

2.

Light the pilot burner according to the appliance 
manufacturer instructions.

SERVICE

WARNING

Fire or Explosion Hazard.
Can cause property damage, serious injury 
or death.

Perform Gas Leak Test anytime work is done to 
the system.

Thermopile Performance

Thermopiles require proper temperature differential 
between the hot-junction (tip) and cold-junction (base) to 
provide satisfactory operation of millivoltage gas controls. 
Thermopiles perform less effectively when exposed to 
excessive cold-junction or hot-junction temperatures.
Excessive cold-junction temperatures can be caused by 
heat radiation from adjacent surfaces or high ambient air 
temperatures. Excessive cold-junction temperatures can 
be eliminated by shielding the pilot flame, or construct a 
baffle to direct secondary air over the pilot burner base.

Excessive hot-junction temperatures can be eliminated 
by proper flame adjustment.

M13697