S7999 CONTROLINKS™ DISPLAY MODULE
9
65-0262
a
If XmA Hold is configured as “None”, temperature may show other values outside the -40°F to +1400°F range for S7999 software builds prior to
2007.
b
UNKNOWN will be displayed for R7999 software builds prior to 170.
Prog Stop FGR
Programmed stop of actuator.
00% to 100
F2(1) Idle Stop
Current inactive fuel
00% to 100
Either F2 or F1 will be shown,
whichever is the inactive fuel.
Config Settings
Top level prompt for
configuration parameter
settings.
Press the Change Level button to
enter the submenu.
XmA Hold
Temperature Sensor hold
None
LOP
FGR
LOP + FGR
Indicates if auxiliary temperature
sensor is used and type of hold:
lightoff point, FGR closed, or both.
XmA Minimum
Temperature Sensor minimum
input
-40°F to +1400°F
a
N/A
Not Applicable (N/A) is indicated if
XmA Hold is configured as None.
XmA Maximum
Temperature Sensor maximum
input
-40°F to +1400°F
a
N/A
Not Applicable (N/A) is indicated if
XmA Hold is configured as None.
XmA Enforce
Temperature Sensor setting to
enforce XmA Hold condition.
-40°F to +1400°F
a
N/A
Not Applicable (N/A) is indicated if
XmA Hold is configured as None.
XmA Release
Temperature Sensor setting to
release the XmA Hold
condition.
-40°F to +1400°F
a
N/A
Not Applicable (N/A) is indicated if
XmA Hold is configured as None.
Purge FGR
FGR Actuator position during
PURGE
On curve
Closed
b
Man Limit
Manual Limit configuration
setting.
Enabled
Disabled
b
Indicates if the R7999 was
commissioned to enable the Manual
Potentiometer to limit the maximum
firing rate.
CL Rev. M.NvV BBB
ControLinks™ R7999 software
revision and build code
M = major; N = minor; V = version;
BBB = build code.
Display Rev. BBB
Display S7999 Software Build
Code
BBB = build code.
DiagCode
Diagnostic Codes
Possibly useful for debugging display
problems.
Fault History
(Six most recent faults)
Top level prompt for fault
history information.
Press the Change Level button to
enter the submenu.
*Fault Code nn* Fault Code Number
0-94
For fault descriptions, see form 65-
0238, R7999A,B ControLinks™
Controller.
*Fault Message*
Description of the fault code.
*In (state)*
State in which the fault
occurred.
*Fault Cycle nnn*
Cycle when fault occurred.
0 to 999999
Line 2 Legend
Top level prompt for on-line
help to describe letter codes
on the second line of the main
display.
The Line 2 legend submenu describes each of the letter codes
that may appear on the second line of the main display. Each
item in this submenu shows a flashing letter code on the second
line, in the position where it normally appears on the main
display, along with a description of the letter code in the first line
of the display.
Table 3. Selectable Messages.
Selectable Message/Display
Description
Possible States/Range
Comments