S7999 CONTROLINKS™ DISPLAY MODULE
65-0262
4
Fig. 3. Remote mounting of a Display Module using
a 203765 Remote Display Mounting Bracket.
WIRING
WARNING
Electrical Shock Hazard.
Can cause serious injury or death.
To prevent electrical shock and equipment damage,
disconnect the power supply from the main disconnect
before beginning installation. More than one
disconnect can be involved.
1.
Refer to Fig.4, 5 and 6 for proper wiring.
2.
Make sure all wiring complies with all applicable
electrical codes, ordinances and regulations.
3.
For recommended wire size and type, see Table 1.
4.
For Recommended grounding practices, see Table 2.
5.
For DM: The DM is powered from a low voltage,
energy-limited source. It can be mounted outside of a
control panel if it is protected from mechanical damage.
NOTE:
A 13 Vdc power supply must be used any time the
DM is used.
Table 1. Recommended Wire Size and Part Number.
Table 2. Recommended Grounding Practices.
6.
Recommended wire routing:
a. Display Module:
(1) Do not route the Display Module wiring in
conduits that carry line voltage circuits.
(2) Avoid routing the Display Module wiring close to
ignition transformer leadwires.
(3) Route the Display Module wiring outside of
conduit if properly supported and protected from
damage.
7.
Maximum wire lengths:
a. DM: The maximum length interconnecting wire is
4000 ft (1219m).
8.
Install all electrical connectors.
9.
Restore power to the panel.
Fig. 4. Wiring the display module.
Application
Recommended Wire Size
Recommended Part Number
Display Module
22 AWG two-wire twisted pair with ground or five-wire. Belden 8723 shielded cable or equivalent.
13 Vdc full wave rectified
transformer power input.
18 AWG wire insulated for voltages and temperatures
for given application.
TTW60C, THW75C, THHN90C.
Ground Type
Recommended Practice
Signal ground (DM)
Use the shield of the signal wire to ground the device to the signal ground terminal of each device.
Connect the shield at both ends of the daisy chain to ground.
L1
(HOT)
L2
1
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.
M17923
1
A
B
C (std)
A
B
C
+ 13 vdc
2
S7999
R7999
3
1
2
3
5
4