Honeywell Chronotherm T4600 Product Data Download Page 3

T4600 Chronotherm

 

®

 ELECTRONIC PROGRAMMABLE LINE VOLTAGE THERMOSTAT

68-0168—3

3

Fig. 1. T4600 dimensions in in. (mm).

CAUTION

Equipment Damage Hazard.
Improper wiring connections can damage
thermostat.
1.

Do not use on circuits protected by higher-rated, over-
current protection devices.  This thermostat is rated for
normal full load current on a dual residential 20A
circuit breaker or fuse block.

2.

Make sure thermostat is connected to equipment with
the same electrical rating.

3.

Use a separate limit control in the heating appliance.

Location

To mount the thermostat, install a vertical outlet box about 5 ft
(1.5m) above the floor in an area with good air circulation at
room temperature.

Do not install the thermostat where it can be affected by:

drafts or dead spots behind doors, in corners or under
cabinets.

hot air from convectors.

radiant heat from sun or appliances.

concealed pipes and chimneys.

unheated (uncooled) areas such as an outside wall
behind the thermostat.

Wiring and Mounting

Refer to Fig. 2 for typical wiring connections.

WARNING

Fire Hazard.
Improper wiring connections can cause property
damage, severe injury or death.
Avoid fire hazard. Use CO/ALR solderless wire
connectors when connecting with aluminum
conductors.

L1 
(HOT)

L2

1

1

2

2

3

3

4

4

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD 
PROTECTION AS REQUIRED.

SPECIAL SERVICE CO/ALR SOLDERLESS CONNECTORS MUST
BE USED WHEN CONNECTING ALUMINUM CONDUCTORS;
OTHERWISE, A FIRE HAZARD CAN RESULT.

THERMOSTAT BREAKS HEATING CIRCUIT ON TEMPERATURE RISE.

THERMOSTAT IS DESIGNED TO BE USED WITH APPLIANCES
EQUIPPED WITH A LIMIT CONTROL.

T4600A
ELECTRONIC
LINE VOLTAGE
THERMOSTAT

ELECTRIC
HEATER

BLACK

BLACK

M4788

Fig. 2. T4600A Typical wiring connections.

PROG

AUTO

+

3-1/8 (80)

4-3/4
(118)

1-1/8

(29)

1/2

(13)

3-1/4

(83)

2-1/8

(54)

1-1/16

(26)

M4787

AUTO   MAN   TEMPOR   NIGHT   DAY

AM
PM

Su     Mo     Tu     We     Th     Fr     Sa

Su 

WARNING

Electrical Shock and Fire Hazard.
Power supply can cause property damage,
severe injury, or death.
Do not use this thermostat on loads higher than
2500W.  This thermostat is rated for 10.4A (2500W,
8 ft of baseboard heater).

INSTALLATION

When Installing this Product…

1. Read these instructions carefully. Failure to follow these

instructions could damage the product or cause a
hazardous condition.

2.

Important! Check the ratings on the product to make
sure the product is suitable for your application. Use
only on:

a.

240V, 60 Hz supply

b.

Loads up to 10.4A (8 ft of connected baseboard
heater per thermostat).

3. Installer must be a trained, experienced service

technician.

4. After installation is complete, check out product

operation as provided in these instructions.

5. Follow local codes and ordinances.

WARNING

Electrical Shock Hazard.
Power supply can cause property damage,
severe injury, or death.
Disconnect the power supply before handling to
prevent electrical shock or equipment damage.

Summary of Contents for Chronotherm T4600

Page 1: ...d status Attractive contemporary styling Temperature range selectable between 45 F to 80 F 7 C to 27 C Simple pushbutton programming Weekday weekend 5 2 programming for permanent home normal operation Optional unoccupied low limit setting for seasonal residence cottage operation Temporary temperature override Program override for seasonal temperature setback Permanent override for seasonal shutdow...

Page 2: ...itions are changed TRADELINE Models TRADELINE models are selected and packaged to provide ease of stocking ease of handling and maximum replacement value TRADELINE Models Available T4600A Chronotherm Electronic Programmable Line Voltage Thermostat with spst switching makes heating circuit on temperature fall Features TRADELINE pack Temperature Ratings Operating Range 22 to 104 F 30 to 40 C Control...

Page 3: ... AS REQUIRED SPECIAL SERVICE CO ALR SOLDERLESS CONNECTORS MUST BE USED WHEN CONNECTING ALUMINUM CONDUCTORS OTHERWISE A FIRE HAZARD CAN RESULT THERMOSTAT BREAKS HEATING CIRCUIT ON TEMPERATURE RISE THERMOSTAT IS DESIGNED TO BE USED WITH APPLIANCES EQUIPPED WITH A LIMIT CONTROL T4600A ELECTRONIC LINE VOLTAGE THERMOSTAT ELECTRIC HEATER BLACK BLACK M4788 Fig 2 T4600A Typical wiring connections PROG AUT...

Page 4: ...ad per thermostat must not exceed 2500W 8 ft of baseboard heater 2 Disconnect power to the thermostat to prevent electrical shock or equipment damage All wiring must comply with local electrical codes and ordinances 3 Remove the T4600 cover at the top or bottom edge with a slotted screwdriver 4 Remove the old thermostat from the wall taking care not to damage the wiring insulation 5 Check the old ...

Page 5: ...ramming by holding down the PROG key for four seconds or until the display shows the room temperature IMPORTANT The T4600 uses the time and day that was last in its memory as the basis for control Unexpected thermostat operation can occur when the clock is not set properly ACTIVITY RESULT DISPLAY SET THE TIME AND DAY Hours Press and release the PROG key The hour display flashes in the 12 hour AM P...

Page 6: ...ease the PROG key to enter the time PROGRAM THE DAY SETBACK AND AFTERNOON RECOVERY TIMES Day Setback Press the up and down keys to select the desired day setback time The display flashes the DAY setback time Afternoon Recovery Press the up and down keys to select the desired afternoon recovery time The display flashes the afternoon recovery warm up time Press and release the PROG key to enter the ...

Page 7: ... 20 C Let the system operate for at least one hour and adjust the setting as necessary M4657 AUTO MAN TEMPOR NIGHT DAY Su Mo Tu We Th Fr Sa AM PM ACTIVITY RESULT DISPLAY Set Cottage Programs CAUTION Before using the COTTAGE program make sure there are no water pipes along outside walls sealed in cabinets or installed in a manner that can cause them to freeze when the room temperature falls to 45 F...

Page 8: ...rdon Baker Road North York Ontario M2H 3N7 Honeywell Latin American Region 480 Sawgrass Corporate Parkway Suite 200 Sunrise FL 33325 Home and Building Control Honeywell Inc Honeywell Plaza P O Box 524 Minneapolis MN 55408 0524 Printed in U S A on recycled paper containing at least 10 post consumer paper fibers www honeywell com yourhome 68 0168 3 J S Rev 2 99 The electrical power industry of the U...

Reviews: